Plan Review Stops For Permit 22010971 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2022-01-27 |
|
|
Cont ID |
|
Sent By |
cwalker |
Date |
2022-01-27 |
Time |
|
Rev Time |
|
Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2022-01-27 10:44:45 | FIRE PROVISO COMMENTS: | | 1) RELOCATED DROPS MAY NOT BE ABLE TO BE ISOLATED; | | HOWEVER, THE FLOOR AREA MAY AND BE TESTED AT 200 PSI | | FOR 2 HOURS. | | IF COMMENT (1) IS NOT PERFORMED: | | 2) TEST AT WORKING PRESSURE FOR 2 HOURS PER NFPA 13. | | 3) USE OF FIRE PUMP TEST PRESSURE FOR WORKING PRESSURE | | CALCULATIONS MINUS 5 PSI PER FLOOR FOR ELEVATION | | PRESSURE LOSS. | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2022-01-28 |
Time |
|
Rev Time |
0.00 |
Received By |
cdecoeur |
Date |
2022-01-26 |
Time |
06:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
N |
Date |
2022-01-28 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2022-01-28 |
Time |
10:45 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2022-01-28 |
Time |
10:45 |
Sent To |
|
|
Notes |
|
|
|