Plan Review Details - Permit 22010940
Plan Review Stops For Permit 22010940
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-05-16 Cont ID  
Sent By jbrooks Date 2022-05-16 Time 09:11 Rev Time 0.00
Received By jbrooks Date 2022-05-16 Time 09:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-05-02 Cont ID  
Sent By pvalenti Date 2022-05-02 Time 11:04 Rev Time 0.00
Received By pvalenti Date 2022-05-02 Time 10:03 Sent To  
Notes
2022-05-02 11:05:13PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 3.) FBC B 107, THE PLAN AND APPLICATION REFER TO
 WINDOWS IN SEVERAL AREAS. NO PRODUCT APPROVAL FOR
 WINDOWS WAS SUBMITTED AND THERE IS NOTHING ON THE
 OPENING SCHEDULE FOR WINDOWS. IF WINDOWS ARE NOT
 PROPOSED, SUBMIT A NEW APPLICATION AND PLAN REMOVING
 WINDOWS FROM SCOPE OF WORK.
  
 4.) FBC B 107, ALL PLAN SHEETS NEED TO BE SIGNED BY THE
 PERSON TAKING RESPONSIBILITY FOR THE PLAN SHEETS. IF
 THE PLAN SHEETS ARE FROM SIW WINDOWS & DOORS, AS TITLE
 BLOCK INDICATES, THEN THE PRINTED NAME & SIGNATURE
 (INCLUDING SEAL IF ARCHITECT OR ENGINEER IS SIGNING)
 MUST BE ON EACH PLAN SHEET. IF THERE IS NOT A TITLE
 BLOCK ON PLANS, THEN IT WILL BE CONSIDERED DESIGNED BY
 THE INDIVIDUAL THAT PRINTS NAME AND SIGNS NAME, SUCH AS
 A GENERAL CONTRACTOR.
 THE (3) PLAN SHEETS NEED TO BE NUMBERED AS A SET OF (3)
 AS FOLLOWS:
  
 PLAN SHEET (LAYOUT-SCHEDULE-ELEVATION) SHOULD BE
 LABELED 1 OF 3 NOT 1 OF 1.
 PLAN SHEET (DOOR LAYOUT) SHOULD BE LABELED 2 OF 3 NOT 1
 OF 1.
 PLAN SHEET (DOOR LAYOUT/OCCUPANCY INFORMATION) SHOULD
 BE LABELED AS IS 3 OF 3.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-03-05 Cont ID  
Sent By shill Date 2022-03-05 Time 11:58 Rev Time 0.00
Received By shill Date 2022-03-05 Time 11:58 Sent To  
Notes
2022-03-05 12:04:05****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. REVISE PLAN TO STATE OCCUPANCY CLASSIFICATION, FBC B
 CHAPTER 3. THE APPLICATION STATES THIS IS FOR
 "NORTHWOOD RESIDENCE". THIS IS A COMMERCIAL BUILDING.
  
 2. SHOW THE ACCESSIBLE ROUTE. COASTAL DOOR HAS THE
 STANDARD THRESHOLD HIGHLIGHTED RATHER THAN THE ADA
 THRESHOLD. COMPLIANCE NOT CLEAR, FBC ACCESSIBLITY. SEE
 DEFINITION OF "ACCESSIBLE ROUTE" IN CHAPTER 2.
  
 3. FBC 107, THE PLAN AND APPLICATION REFER TO WINDOWS,
 BUT NO WINDOWS SHOWN ON THE PLAN, NO PRODUCT APPROVAL
 SUBMITTED. IF WINDOWS ARE NOT PROPOSED, SUBMIT A NEW
 APPLICATION AND PLAN REMOVING WINDOWS FROM SCOPE.
  
 4. INCLUDE THE PRINTED NAME AND SIGNATURE OF THE PERSON
 TAKING RESPONSIBILITY FOR THE PLAN, FBC 107.
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-04-13 Cont ID  
Sent By pleduc Date 2022-04-13 Time   Rev Time 0.00
Received By pleduc Date 2022-04-13 Time 09:22 Sent To  
Notes
2022-04-13 09:42:29FIRE PROVISO COMMENTS:
  
 THERE ARE INDCIATIONS OF DOORS TO REMIAN UNLOCKED
 DURING OPERATION HOURS PER 7.2.1.5.
  
 HOWEVER, SHOULD THE NEED APPLY TO THESE DOORS OF OTHERS
 WITHIN THIS OCCUPANCY,
  
 PER NFPA 101 CH 38 NEW BUSINESS OCCUPANCY
  
 38.2.2.2.2* DOOR LOCKING TO PREVENT UNWANTED ENTRY.
 WHERE
 APPROVED, DOORS, OTHER THAN THOSE COMPLYING WITH
 38.2.11.2, SHALL BE
 PERMITTED TO BE LOCKED TO PREVENT UNWANTED ENTRY
 PROVIDED THAT ALL OF
 THE FOLLOWING CONDITIONS ARE MET:
 (1) THE LOCKING MEANS SHALL BE CAPABLE OF BEING ENGAGED
 WITHOUT
 OPENING THE DOOR.
 (2) THE UNLOCKING AND UNLATCHING OPERATION FROM THE
 EGRESS SIDE OF
 THE DOOR SHALL BE ACCOMPLISHED WITHOUT THE USE OF A
 KEY, TOOL, OR
 SPECIAL KNOWLEDGE OR EFFORT.
 (3) THE RELEASING MECHANISM SHALL OPEN THE DOOR LEAF
 WITH NOT MORE
 THAN ONE RELEASING OPERATION.
 (4) THE RELEASING MECHANISM FOR UNLOCKING AND
 UNLATCHING SHALL BE
 LOCATED AT A HEIGHT NOT LESS THAN 34 IN. (865 MM) AND
 NOT EXCEEDING
 48 IN. (1220 MM) ABOVE THE FINISHED FLOOR.
 (5) LOCKS, IF REMOTELY ENGAGED, SHALL BE UNLOCKABLE
 FROM THE EGRESS
 SIDE OF THE DOOR WITHOUT THE USE OF A KEY, TOOL, OR
 SPECIAL KNOWLEDGE
 OR EFFORT.
 (6) THE DOOR SHALL BE CAPABLE OF BEING UNLOCKED AND
 OPENED FROM
 OUTSIDE THE ROOM WITH THE NECESSARY KEY OR OTHER
 CREDENTIAL.
 (7) THE LOCKING MEANS SHALL NOT MODIFY THE DOOR CLOSER,
 PANIC HARD WARE, OR FIRE EXIT HARDWARE.
 (8) MODIFICATIONS TO REQUIRED FIRE DOOR ASSEMBLIES,
 INCLUDING DOOR
 HARDWARE, SHALL BE IN ACCORDANCE WITH NFPA 80.
  
 A.38.2.2.2.2 THE INTENT OF THIS SECTION IS TO APPLY
 ONLY WHERE SPECIALIZED
 SECURITY MEASURES ARE NEEDED TO PREVENT UNWANTED ENTRY.
 EXAMPLES OF
 DOORS THAT MIGHT USE THESE PROVISIONS INCLUDE COLLEGE
 AND UNIVERSITY
 CLASSROOM DOORS, AREAS OF OFFICE SPACES OPEN TO THE
 PUBLIC, LABORATORIES,
 OR INSTRUCTIONAL ROOMS OR SPACES
  
 BE MINDFUL OF NFPA 101 CH 38
  
 38.2.2.2.3* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED ONLY ON
 PRINCIPAL ENTRANCE/EXIT DOORS.
  
 A.38.2.2.2.3 THE WORDS ?PRINCIPAL ENTRANCE/EXIT DOORS?
 DESCRIBE DOORS
 THAT THE AUTHORITY HAVING JURISDICTION CAN REASONABLY
 EXPECT TO BE
 UNLOCKED IN ORDER FOR THE FACILITY TO DO BUSINESS.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-03-10 Cont ID  
Sent By pleduc Date 2022-03-10 Time   Rev Time 0.00
Received By pleduc Date 2022-03-10 Time 11:06 Sent To  
Notes
2022-03-10 11:07:40THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) PLEASE PROVIDE THE OCCUPANCY CLASSIFICATION AND
 PROPSED OCCUPANCY LOAD OF THAT OCCUPANCY PER THE
 FLORIDA FIRE PREVENTION CODE.
  
 EXIT DOOR HARDWARE/REQUIREMENTS CAN BE DIFFERENT BASED
 ON THE OCCUPANCY/OCCUPANCY LOAD.
  
  
 2) EXIT DOOR HARDWARE IS NOT PROVIDED THAT ENSURES
 COMPLIANCE WITH THE LIFE SAFETY CODE, NFPA 101 CH 7,
 MEANS OF EGRESS
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
  
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM THE
 EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
  
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL,
 OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE.
  
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT APPLY
 WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH 23.
  
 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR
 LEAF SHALL BE
 PROVIDED WITH A RELEASING DEVICE THAT HAS AN OBVIOUS
 METHOD OF OPERATION
 AND THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS.
  
 7.2.1.5.10.1 THE RELEASING MECHANISM FOR ANY LATCH
 SHALL BE LOCATED AS
 FOLLOWS:
 (1) NOT LESS THAN 34 IN. (865 MM) ABOVE THE FINISHED
 FLOOR FOR OTHER
 THAN EXISTING INSTALLATIONS
 (2) NOT MORE THAN 48 IN. (1220 MM) ABOVE THE FINISHED
 FLOOR
 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN THE
 DOOR LEAF WITH NOT
 MORE THAN ONE RELEASING OPERATION, UNLESS OTHERWISE
 SPECIFIED IN
 7.2.1.5.10.3, 7.2.1.5.10.4, 7.2.1.5.10.6, OR
 7.2.1.5.10.7.
  
 PLEASE REVIEW AND PROVIDE DETAILS OF COMPLIANCE.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2022-05-24 Cont ID  
Sent By amhamilt Date 2022-05-24 Time 13:42 Rev Time 0.00
Received By amhamilt Date 2022-05-24 Time 13:42 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-03-08 Cont ID  
Sent By amhamilt Date 2022-03-08 Time 16:08 Rev Time 0.00
Received By amhamilt Date 2022-03-08 Time 16:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-05-25 Cont ID  
Sent By jbrooks Date 2022-05-25 Time 08:05 Rev Time 0.00
Received By lmarchan Date 2022-05-02 Time 12:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-02 Cont ID  
Sent By pvalenti Date 2022-05-02 Time 11:32 Rev Time 0.00
Received By pvalenti Date 2022-04-12 Time 09:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-10 Cont ID  
Sent By lmarchan Date 2022-03-10 Time 14:17 Rev Time 0.00
Received By lmarchan Date 2022-02-22 Time 09:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-03-05 Cont ID  
Sent By shill Date 2022-03-05 Time 12:04 Rev Time 0.00
Received By shill Date 2022-03-05 Time 12:04 Sent To  
Notes
***NONE***