Plan Review Details - Permit 22010852
Plan Review Stops For Permit 22010852
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-02-16 Cont ID  
Sent By cpuell Date 2022-02-16 Time 15:31 Rev Time 0.00
Received By cpuell Date 2022-02-16 Time 15:31 Sent To  
Notes
2022-02-16 15:32:34PARCEL HAS BEEN READDRESSED, FRONT BOULDGING IS NOW 517
 31ST ST AND REAR BLDG IS 519 31ST ST, UPDATED PERMIT

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-02-11 Cont ID  
Sent By cpuell Date 2022-02-11 Time 12:54 Rev Time 0.00
Received By cpuell Date 2022-02-11 Time 12:54 Sent To  
Notes
2022-02-11 12:56:13WHICH BUILDING IS THE WORK TO BE DONE, NORTH OR SOUTH?
 THE NORTH BUILDING HAS A HALF ADDRESS WHICH WILL NEED
 TO BE READDRESSED. PLEASE HAVE THE OWNER CONTACT
 [email protected] OR CALL 561-805-6659 TO READDRESS THE
 HALF ADDRESS.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-02-22 Cont ID  
Sent By fgiaquin Date 2022-02-22 Time 19:56 Rev Time 0.00
Received By fgiaquin Date 2022-02-22 Time 19:51 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2022-04-18 Cont ID  
Sent By ccole Date 2022-04-18 Time 10:47 Rev Time 0.00
Received By ccole Date 2022-04-18 Time 10:46 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2022-03-31 Cont ID  
Sent By ccole Date 2022-03-31 Time 08:51 Rev Time 0.00
Received By ccole Date 2022-03-31 Time 07:46 Sent To  
Notes
2022-03-31 08:51:552ND REVIEW FBC-2020 RES. GAS
 PERMIT- 22010852
 3/31/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST GAS REVIEW ARE LISTED BELOW. A NARRATIVE RESPONSE
 TO 1ST REVIEW COMMENTS BY TETRIS CONSTRUCTION HAS BEEN
 SUBMITTED HOWEVER TETRIS CONSTRUCTION IS NOT A PERMIT
 APPLICANT FOR EITHER PLUMBING OR GAS INSTALLATIONS ON
 THE PROJECT.
  
 A) FAILED ITEMS B, C, E, F, G, H, K LISTED BELOW.
 PROVIDE A COMPLETE GAS RISER DRAWING THAT INCLUDES ALL
 NEW AND EXISTING GAS PIPING AND APPLIANCES AT THE
 RESIDENCE- SECTION G2412.3 & G2412.4 FBC RES. REFER TO
 FBC RES. CHAPTER 24 FUEL GAS- THE RISER SHALL INDICATE:
 B) FAILED. DELIVERY PRESSURE AT THE METER. NOT
 PROVIDED.
 C) FAILED. TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU
 LOADS. NOT PROVIDED.
 E) FAILED. TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM
 THE METER TO THE MOST REMOTE APPLIANCE OUTLET. NOT
 PROVIDED.
 F) FAILED. BRANCH AND CUT PIPE LENGTH MEASUREMENTS
 INCLUDING THE PIPE SUPPLYING THE WATER HEATER. NOT
 PROVIDED.
 G) FAILED. LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND
 PIPE UNIONS. NOT PROVIDED
 H) FAILED. OUTLET PRESSURES AT REGULATORS. NOT
 PROVIDED.
 K) FAILED. PIPE SIZING TABLES. NOT PROVIDED.
  
 B) FAILED. PROVIDE COMBUSTION AIR CALCULATIONS AND
 INDICATE HOW THE AIR WILL BE SUPPLIED- SECTIONS G2406.1
 & G2407.1 FBC RES. NOT PROVIDED
  
 C) FAILED. PROVIDE A GAS VENTING DIAGRAM- SECTIONS
 G2427.1 & G2448.1 FBC RES. THE DIAGRAM SHALL SHOW THE
 TYPE AND SIZE OF VENTING, VENT RUN LENGTH AND
 TERMINATION LOCATION.
  
 NEW COMMENTS BASED ON THE RESUBMITTED PLANS AND
 NARRATIVE.
 1) THE NEW GAS RISER APPEARS TO INDICATE GAS PIPING TO
 TWO HEATERS. THE ORIGINAL APPLICATION BY ORIGINAL
 PLUMBING INC. INDICATED INSTALLATION OF ONE HEATER.
 PLEASE CLARIFY THE SCOPE OF WORK FOR THE PROJECT AND
 ADJUST THE COSTS OF LABOR, MATERIALS, AND THE SECOND
 WATER HEATER- SEC. 109.3 WPB. THE COMMENTS LISTED ABOVE
 UNDER A SHALL APPLY TO BOTH RISERS.
 2) THE NEW GAS RISER SHALL BEAR THE PRINTED NAME,
 SIGNATURE, AND LICENSE NUMBER OF THE CONTRACTOR
 (ORIGINAL PLUMBING- HARRIS HAUGHTON?) WHO PREPARED THE
 DRAWING- SEC. 107.2.1 WPB.
 3) PLEASE PROVIDE A SITE AND/OR FLOOR PLAN DRAWING
 SHOWING THE LOCATIONS OF THE TWO WATER HEATERS.
 COMBUSTION AIR AND VENTING REQUIREMENTS LISTED ABOVE
 UNDER B AND C ARE APPLIABLE TO BOTH WATER HEATERS.
 BASED ON THE NARRATIVE BY TETRIS CONSTRUCTION MORE
 INFORMATION ABOUT THE EXTERIOR METAL ENCLOSURE THAT IS
 HOUSING THE GAS WATER HEATER IS REQUIRED. PROVIDE A
 DETAILED DIMENSIONED DRAWING THAT SHOWS THE STRUCTURAL
 AND ARCHITECTURAL COMPONENTS OF THE BUILDING. THE
 INSTALLATION INSTRUCTIONS FOR THE WATER HEATER INDICATE
 IT IS DESIGNED FOR INDOOR INSTALLATION. THE DRAWINGS
 AND DETAILS MUST VERIFY THAT THE EXTERIOR ENCLOSURE
 PROVIDE ADEQUATE SPACE AND WEATHER PROTECTION FOR THE
 UNIT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-02-18 Cont ID  
Sent By ccole Date 2022-02-18 Time 08:51 Rev Time 0.00
Received By ccole Date 2022-02-18 Time 08:36 Sent To  
Notes
2022-02-18 08:51:441ST REVIEW FBC-2020 RES. GAS
 PERMIT- 22010852
 2/18/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) WPB BUILDING DEPT. RECORDS DO NOT SHOW A PREVIOUS
 PERMIT ISSUED FOR THE GAS WATER HEATER. PLEASE PROVIDE
 A PLAN SHOWING THE LOCATION OF THE WATER HEATER. A
 COMPLETE REVIEW OF THE WATER HEATER INSTALLATION CANNOT
 BE COMPLETED AT THIS TIME BECAUSE OF A LACK OF
 INFORMATION ABOUT THE WATER HEATER GAS PIPING, VENTING,
 AND COMBUSTION AIR SYSTEMS. PLEASE PROVIDE THE
 FOLLOWING ITEMS:
 A) PROVIDE A COMPLETE GAS RISER DRAWING THAT INCLUDES
 ALL NEW AND EXISTING GAS PIPING AND APPLIANCES AT THE
 RESIDENCE- SECTION G2412.3 & G2412.4 FBC RES. REFER TO
 FBC RES. CHAPTER 24 FUEL GAS- THE RISER SHALL INDICATE:
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS INCLUDING
 THE PIPE SUPPLYING THE WATER HEATER.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 K) PIPE SIZING TABLES.
  
 B) PROVIDE COMBUSTION AIR CALCULATIONS AND INDICATE HOW
 THE AIR WILL BE SUPPLIED- SECTIONS G2406.1 & G2407.1
 FBC RES.
  
 C) PROVIDE A GAS VENTING DIAGRAM- SECTIONS G2427.1 &
 G2448.1 FBC RES. THE DIAGRAM SHALL SHOW THE TYPE AND
 SIZE OF VENTING, VENT RUN LENGTH AND TERMINATION
 LOCATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2022-03-31 Time   Rev Time 0.00
Received By aoliver Date 2022-03-29 Time 10:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-02-22 Cont ID  
Sent By fgiaquin Date 2022-02-22 Time 19:56 Rev Time 0.00
Received By fgiaquin Date 2022-02-10 Time 09:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2022-04-18 Cont ID  
Sent By ccole Date 2022-04-18 Time 15:57 Rev Time 0.00
Received By ccole Date 2022-04-18 Time 15:57 Sent To  
Notes
2022-04-18 16:18:06PLUMBING SUB-PERMIT REQUIRED FOR INSTALLATION OF THE
 GAS-FIRED WATER HEATER.
2022-04-18 16:02:07 
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2022-04-18 Cont ID  
Sent By ccole Date 2022-04-18 Time 10:56 Rev Time 0.00
Received By ccole Date 2022-04-18 Time 10:56 Sent To  
Notes
2022-04-18 16:14:58PLUMBING SUB-PERMIT REQUIRED- 3RD REQUEST.

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-03-31 Cont ID  
Sent By ccole Date 2022-03-31 Time 08:04 Rev Time 0.00
Received By ccole Date 2022-03-31 Time 07:46 Sent To  
Notes
2022-03-31 08:30:282ND REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22010852
 3/31/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 1) PROVIDE A PLUMBING SUB-PERMIT APPLICATION FOR
 INSTALLATION OF THE GAS WATER HEATER- SEC. 105.1 WPB.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-02-18 Cont ID  
Sent By ccole Date 2022-02-18 Time 08:32 Rev Time 0.00
Received By ccole Date 2022-02-18 Time 07:41 Sent To  
Notes
2022-02-18 08:33:041ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22010852
 2/18/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) WPB BUILDING DEPT. RECORDS DO NOT SHOW A PREVIOUS
 PERMIT ISSUED FOR THE WATER HEATER. PLEASE PROVIDE A
 PLAN SHOWING THE LOCATION OF THE WATER HEATER. CLARIFY
 IF THE UNIT IS REPLACING AN EXISTING UNIT IN THE SAME
 LOCATION AS THE PREVIOUS OR IF THE LOCATION HAS
 CHANGED- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-02-22 Cont ID  
Sent By fgiaquin Date 2022-02-22 Time 19:56 Rev Time  
Received By fgiaquin Date   Time   Sent To  
Notes
***NONE***