Plan Review Details - Permit 22010791
Plan Review Stops For Permit 22010791 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2022-02-15 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-02-15 |
Time |
14:14 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-02-15 |
Time |
14:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2022-02-07 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2022-02-07 |
Time |
16:42 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2022-02-07 |
Time |
16:42 |
Sent To |
|
|
Notes |
2022-02-07 16:45:28 | ELECTRIC REVIEW FAILED | | 1) PLANS ARE BLURRY AND UNREADABLE FBC 107.2 | | 2) SUBMITTAL DOES NOT APPEAR TO INCLUDE A PHOTOMETRIC | | PLAN. FBC 107.2 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2022-02-23 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2022-02-23 |
Time |
09:57 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2022-02-15 |
Time |
14:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-02-15 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2022-02-15 |
Time |
11:32 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2022-02-02 |
Time |
08:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2022-02-15 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-02-15 |
Time |
14:14 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-02-15 |
Time |
14:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2022-02-07 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2022-02-07 |
Time |
16:52 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2022-02-07 |
Time |
16:52 |
Sent To |
|
|
Notes |
2022-02-07 16:55:49 | SIGNATURE REVIEW FAILED | | IT APPEARS ALL DRAWINGS ARE COPIES OR SCANS OF | | ENGINEERED DRAWINGS, OR COPIES OR SCANS OF DIGITALLY | | SIGNED AND SEALED DRAWINGS. COPIES OR SCANS OF | | DOCUMENTS WITH ENGINEERS DIGITAL SIGNATURES CANNOT BE | | CERTIFIED USING SIGNATURE, CERTIFYING, SOFTWARE. PLANS | | SUBMITTED ELECTRONICALLY MUST BE DIGITALLY SIGNED AND | | SEALED BY THE ENGINEER OF RECORD. PLEASE FOLLOW THE | | DIRECTIONS OUTLINED BELOW TO CORRECT THIS ISSUE. | | | | FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR | | ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND | | SIGNED. | | EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN | | TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF | | APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX, | | OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER | | ORIGINAL WITH A WET SIGNATURE TO THE BUILDING | | DEPARTMENT. | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO | | BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED | | DOCUMENTS ARE PREFERRED. | | PLEASE EMAIL [email protected] AND CC TO | | [email protected] WITH ANY QUESTIONS | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2022-02-22 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2022-02-22 |
Time |
17:14 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2022-02-22 |
Time |
16:55 |
Sent To |
|
|
Notes |
2022-02-22 17:14:36 | FIXTURES/LIGHTS TO BE INSTALL SO THAT NO GLARE OCCURS | | OFFSITE OR ONTO ROAD RIGHT-OF-WAY. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2022-02-15 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2022-02-15 |
Time |
10:08 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2022-02-15 |
Time |
10:08 |
Sent To |
|
|
Notes |
2022-02-15 10:12:52 | CONTRACTOR REQUESTED ZONING FAIL PRIOR TO ZONING REVIEW | | BEING INITIATED. THIS DOES NOT COUNT AS A ZONING | | REVIEW. |
|
|
|