Plan Review Details - Permit 22010791
Plan Review Stops For Permit 22010791
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-02-15 Cont ID  
Sent By jleahy Date 2022-02-15 Time 14:14 Rev Time 0.00
Received By jleahy Date 2022-02-15 Time 14:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-02-07 Cont ID  
Sent By mpeterso Date 2022-02-07 Time 16:42 Rev Time 0.00
Received By mpeterso Date 2022-02-07 Time 16:42 Sent To  
Notes
2022-02-07 16:45:28ELECTRIC REVIEW FAILED
 1) PLANS ARE BLURRY AND UNREADABLE FBC 107.2
 2) SUBMITTAL DOES NOT APPEAR TO INCLUDE A PHOTOMETRIC
 PLAN. FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-02-23 Cont ID  
Sent By aoliver Date 2022-02-23 Time 09:57 Rev Time 0.00
Received By aoliver Date 2022-02-15 Time 14:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-02-15 Cont ID  
Sent By lmarchan Date 2022-02-15 Time 11:32 Rev Time 0.00
Received By lmarchan Date 2022-02-02 Time 08:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-02-15 Cont ID  
Sent By jleahy Date 2022-02-15 Time 14:14 Rev Time 0.00
Received By jleahy Date 2022-02-15 Time 14:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-02-07 Cont ID  
Sent By mpeterso Date 2022-02-07 Time 16:52 Rev Time 0.00
Received By mpeterso Date 2022-02-07 Time 16:52 Sent To  
Notes
2022-02-07 16:55:49SIGNATURE REVIEW FAILED
 IT APPEARS ALL DRAWINGS ARE COPIES OR SCANS OF
 ENGINEERED DRAWINGS, OR COPIES OR SCANS OF DIGITALLY
 SIGNED AND SEALED DRAWINGS. COPIES OR SCANS OF
 DOCUMENTS WITH ENGINEERS DIGITAL SIGNATURES CANNOT BE
 CERTIFIED USING SIGNATURE, CERTIFYING, SOFTWARE. PLANS
 SUBMITTED ELECTRONICALLY MUST BE DIGITALLY SIGNED AND
 SEALED BY THE ENGINEER OF RECORD. PLEASE FOLLOW THE
 DIRECTIONS OUTLINED BELOW TO CORRECT THIS ISSUE.
  
 FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND
 SIGNED.
 EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF
 APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX,
 OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER
 ORIGINAL WITH A WET SIGNATURE TO THE BUILDING
 DEPARTMENT.
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO
 BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED
 DOCUMENTS ARE PREFERRED.
 PLEASE EMAIL [email protected] AND CC TO
 [email protected] WITH ANY QUESTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop Z ZONING
Rev No 2 Status P Date 2022-02-22 Cont ID  
Sent By eschneid Date 2022-02-22 Time 17:14 Rev Time 0.25
Received By eschneid Date 2022-02-22 Time 16:55 Sent To  
Notes
2022-02-22 17:14:36FIXTURES/LIGHTS TO BE INSTALL SO THAT NO GLARE OCCURS
 OFFSITE OR ONTO ROAD RIGHT-OF-WAY.

Review Stop Z ZONING
Rev No 1 Status F Date 2022-02-15 Cont ID  
Sent By eschneid Date 2022-02-15 Time 10:08 Rev Time 0.00
Received By eschneid Date 2022-02-15 Time 10:08 Sent To  
Notes
2022-02-15 10:12:52CONTRACTOR REQUESTED ZONING FAIL PRIOR TO ZONING REVIEW
 BEING INITIATED. THIS DOES NOT COUNT AS A ZONING
 REVIEW.