Plan Review Details - Permit 22010746
Plan Review Stops For Permit 22010746
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-03-29 Cont ID  
Sent By jleahy Date 2022-03-29 Time 15:35 Rev Time 0.00
Received By jleahy Date 2022-03-29 Time 15:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-02-07 Cont ID  
Sent By jleahy Date 2022-02-07 Time 09:18 Rev Time 0.00
Received By jleahy Date 2022-02-07 Time 09:18 Sent To  
Notes
2022-02-07 09:27:50 
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-WAS-05 SHOWS CONDUIT RUN ALONG WALL IN GEAR ROOM
 IF THIS IS FOR FIRE PUMP IT WILL NEED TO BE INSTALLED
 WITHIN 2" OF CONCRETE. 605.6(A)(2)(D)(1,2)
  
 INSTALLATION SHOWS MORE THAN ONE MEANS OF DISCONNECT
 FOR PUMP 695.4(B)(1)

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-02-07 Cont ID  
Sent By jleahy Date 2022-02-07 Time 09:28 Rev Time 0.00
Received By jleahy Date 2022-01-20 Time 10:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-01-20 Cont ID  
Sent By mpeterso Date 2022-01-20 Time 15:44 Rev Time 0.00
Received By mpeterso Date 2022-01-20 Time 15:44 Sent To  
Notes
2022-01-20 15:45:241/20/2022 SIGNATURE REVIEW PASSED AND PLANS ROUTED TO
 STORAGE.M.P.