Plan Review Details - Permit 22010665
Plan Review Stops For Permit 22010665
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2022-01-31 Cont ID  
Sent By pvalenti Date 2022-01-31 Time 10:20 Rev Time 0.00
Received By pvalenti Date 2022-01-31 Time 10:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-03-11 Cont ID  
Sent By pvalenti Date 2022-03-11 Time 09:56 Rev Time 0.00
Received By pvalenti Date 2022-03-11 Time 09:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-03-07 Cont ID  
Sent By pvalenti Date 2022-03-07 Time 09:43 Rev Time 0.00
Received By pvalenti Date 2022-03-07 Time 09:21 Sent To  
Notes
2022-03-07 09:47:37PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT PER FLORIDA BUILDING
 CODE, BUILDING 3303:
  
 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED (WE STILL
 NEED AN APPROVED FINAL INSPECTION FOR THE SEWER LATERAL
 CAPPING PERMIT # 22010866).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-01-31 Cont ID  
Sent By pvalenti Date 2022-01-31 Time 10:25 Rev Time 0.00
Received By pvalenti Date 2022-01-31 Time 10:01 Sent To  
Notes
2022-01-31 11:06:09PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT PER FLORIDA BUILDING
 CODE, BUILDING 3303:
  
 1. UTILITY RELEASE - FLORIDA POWER & LIGHT (ELECTRIC)
 RELEASE OF SERVICE CONFIRMATION
 2. UTILITY RELEASE - FLORIDA PUBLIC UTILITIES (GAS)
 RELEASE OF SERVICE CONFIRMATION
 3. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER
 DEPARTMENT, REQUEST FOR METER PULL, ON
 THEIR FORM "DEMOLITION APPLICATION"
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
 WATERDOWN METHOD:
 IF A WATER TRUCK IS DESIRED, PROVIDE DETAILED
 INFPRMATION OF THE WATER TRUCK SUCH AS: THE
 GALLON CAPACITY OF THE WATER TANK AND A LETTER
 INCLUDING A STATEMENT THAT THE WATER
 USED WILL BE POTABLE AND FROM AN OFF-SITE LOCATION ONLY
 AND WILL BE ON-SITE AT ALL TIMES
 DURING DEMOLITION.
 IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE NOTED
 ON THEIR FORM. IF THE BACKFLOW PREVENTER DEVICE IS
 SELECTED, A PLUMBING PERMIT IS REQUIRED. BEFORE
 SCHEDULING THE 703(PLUMBING FINAL INSPECTION), THE
 BACKFLOW DEVICE NEEDS TO BE TESTED AND CERTIFIED BY
 THE CITY?S UTILITIES DEPT, 561-822-2244. FAX THE
 COMPLETED "DEMOLITION APPLICATION" FORM TO
 561-822-2183.
 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT
 APPLICATION TO BUILDING DIVISION);
 SCHEDULE A FINAL PLUMBING #703.
 6. COMPLETE THE DEMO DEBRIS FORM: THE SUBMITTED
 INFORMATION ON THE DEMO FORM IS NOT CLEAR AS TO IF YOU
 WILL BE HAULING OFF DEBRIS YOURSELF OR IF YOU WILL BE
 USING AN AUTHORIZED FRANCHIZE, (SUCH AS WASTE
 MANAGEMENT).
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2022-01-24 Cont ID  
Sent By rrossano Date 2022-01-24 Time   Rev Time  
Received By rrossano Date 2022-01-24 Time   Sent To  
Notes
2022-01-24 08:33:28PASSED WITH PROVISOS:
  
 PROVIDE ALL REQUIRED ASSOCIATED DOCUMENTS AS REQUIRED
 BY BUILDING DEPT. - STORMWATER POLLUTION PREVENTION
 PLAN, AND UTILITY SIGNOFFS - WATER/SEWER, PEST, FPL,
 FPU, ASBESTOS ETC.
  
 THANKS,
  
 RICK ROSSANO, SENIOR PROJECT COORDINATOR,
 CITY OF WPB ENGINEERING SERVICES DEPARTMENT
 DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE:
 (561) 246-9525
 EMAIL: [email protected]
 HTTPS://WWW.WPB.ORG/GOVERNMENT/ENGINEERING/ENGINEERING-
 STANDARDS-DETAILS
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-02-01 Cont ID  
Sent By amhamilt Date 2022-02-01 Time 16:05 Rev Time 0.00
Received By amhamilt Date 2022-02-01 Time 16:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-03-11 Cont ID  
Sent By pvalenti Date 2022-03-11 Time 09:57 Rev Time 0.00
Received By pvalenti Date 2022-03-10 Time 12:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-07 Cont ID  
Sent By pvalenti Date 2022-03-07 Time 09:50 Rev Time 0.00
Received By pvalenti Date 2022-03-03 Time 14:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-02-02 Cont ID  
Sent By lmarchan Date 2022-02-02 Time 07:55 Rev Time 0.00
Received By lmarchan Date 2022-01-20 Time 07:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-03-07 Cont ID  
Sent By pvalenti Date 2022-03-07 Time 09:49 Rev Time 0.00
Received By pvalenti Date 2022-03-07 Time 09:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-01-31 Cont ID  
Sent By pvalenti Date 2022-01-31 Time 10:17 Rev Time 0.00
Received By pvalenti Date 2022-01-31 Time 10:00 Sent To  
Notes
2022-01-31 10:20:07PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 SIGNATURE REVIEW DENIED:
  
 THE SUBMITTED SITE PLAN SIGNATURE BY SANDRA PUERTA IS
 NOT VERIFIABLE. PLEASE SEE COMMENTS BELOW:
  
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
 UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY
 VERIFIED) PLAN OR YOU CAN DELIVER AN ORIGINAL
 SIGNED/SEALED PAPER ORIGINAL TO:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 FEEL FREE TO CONTACT ME AT 561 805 6673.
  

Review Stop Z ZONING
Rev No 1 Status P Date 2022-02-01 Cont ID  
Sent By amhamilt Date 2022-02-01 Time 16:05 Rev Time 0.00
Received By amhamilt Date 2022-02-01 Time 16:05 Sent To  
Notes
***NONE***