Plan Review Details - Permit 22010536
Plan Review Stops For Permit 22010536
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-02-25 Cont ID  
Sent By cpuell Date 2022-02-25 Time 12:15 Rev Time 0.00
Received By cpuell Date 2022-02-25 Time 12:15 Sent To  
Notes
2022-02-25 12:16:35ADDRESS IDENTIFIED AS BEING 250 N OLIVE AVE WITH THE
 PCN 74434322460010000, APPLICANT UPDATED PERMIT
 APPLICATION.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-01-24 Cont ID  
Sent By cpuell Date 2022-01-24 Time 17:20 Rev Time 0.00
Received By cpuell Date 2022-01-24 Time 17:20 Sent To  
Notes
2022-01-24 17:20:29ADDRESS AND AND PARCEL CONTROL NUMBER ARE NOT ACTIVE.
 PLEASE PROVIDE A SITE PLAN, I HAVE BEEN WORKING WITH
 JASON FOSSELMAN [email protected] FOR THE PROJECT
 THAT IS ON BANYAN BETWEEN OLIVE AND DIXIE, PLEASE
 CONTACT HIM SO THAT HE CAN GIVE YOU THE CORRECT ADDRESS
 ASSIGNED FOR YOUR SPACE. PLEASE EMAIL [email protected] OR
 CALL 561-805-6659 ONCE THE CORRECT ADDRESS HAS BEEN
 ESTABLISHED, OR TO DISCUSS THE ADDRESSING OPTIONS.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2022-02-15 Cont ID  
Sent By rmcdouga Date 2022-02-15 Time 08:23 Rev Time 0.00
Received By rmcdouga Date 2022-02-15 Time 08:23 Sent To  
Notes
2022-02-15 08:27:48BUILD OUT OF PREVIOUSLY UNDEVELOPED SPACE IN A NEW
 BUILDING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-03-10 Cont ID  
Sent By rmcdouga Date 2022-03-10 Time 16:59 Rev Time 0.00
Received By rmcdouga Date 2022-03-10 Time 16:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-03-02 Cont ID  
Sent By rmcdouga Date 2022-03-02 Time 14:08 Rev Time 0.00
Received By rmcdouga Date 2022-03-02 Time 14:08 Sent To  
Notes
2022-03-02 13:01:12PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) RESOLVED. [SEE NEW COMMENTS TO #2]
  
 2) [ NOT RESOLVED. THE REVISED LIFE SAFETY PLAN SHOWS A
 MAXIMUM COMMON PATH OF TRAVEL THAT IS MORE THAN 100
 FEET. THEREFORE TWO EXITS FROM THE SPACE ARE REQUIRED.
 SHOW THE EXIT SEPARATION DISTANCE, THE COMMON PATH OF
 TRAVEL, TOTAL TRAVEL DISTANCES, EXIT SIGN LOCATIONS,
 ETC. FOR THE TWO REQUIRED EXITS. FBC CHAPTER 10 ] FBC
 1006.2.1 REQUIRES TWO EXITS FROM ANY SPACE THAT EXCEEDS
 THE OCCUPANT LOAD OR THE COMMON PATH OF EGRESS TRAVEL
 DISTANCE VALUES LISTED IN TABLE 1006.2.1. FOR A
 BUSINESS OCCUPANCY THE MAXIMUM OCCUPANT LOAD IS 49 AND
 THE MAXIMUM COMMON PATH OF EGRESS TRAVEL DISTANCE IN A
 FULLY SPRINKLERED BUILDING IS100 FEET. IF THE MAXIMUM
 COMMON PATH OF EGRESS TRAVEL DISTANCE FROM THE WORK
 ROOM EXCEEDS 100 FEET ANOTHER EXIT WILL BE REQUIRED.
  
 3) RESOLVED.
  
 4) RESOLVED.
  
 5) RESOLVED.
  
 6) PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
 NEW COMMENTS:
  
 7) SHOW HOW THE EXIT ACCESS THROUGH WORKROOM #113
 COMPLIES WITH FBC 1016.2 EGRESS THROUGH INTERVENING
 SPACES.
 (2) EGRESS FROM A ROOM OR SPACE SHALL NOT PASS THROUGH
 ADJOINING OR INTERVENING ROOMS OR AREAS, EXCEPT WHERE
 SUCH ADJOINING ROOMS OR AREAS AND THE AREA SERVED ARE
 ACCESSORY TO ONE OR THE OTHER, ARE NOT A GROUP H
 OCCUPANCY AND PROVIDE A DISCERNIBLE PATH OF EGRESS
 TRAVEL TO AN EXIT.
 (3) AN EXIT ACCESS SHALL NOT PASS THROUGH A ROOM THAT
 CAN BE LOCKED TO PREVENT EGRESS.
  
 8) THE DOOR FROM WORKROOM #113 TO THE SECOND MEANS OF
 EGRESS SWINGS OUT INTO A PATH OF EGRESS TRAVEL. FBC
 1005.7.1 REQUIRES THAT DOORS IN ANY POSITION SHALL NOT
 REDUCE THE REQUIRED WIDTH BY MORE THAN ONE-HALF AND
 WHEN FULLY OPEN SHALL NOT REDUCE THE REQUIRED WIDTH BY
 MORE THAN 7 INCHES. SHOW THAT THIS DOOR COMPLIES. NOTE:
 WHEN THE OCCUPANT LOAD IS 50 PERSONS OR LESS FBC
 1010.1.2.1 ALLOWS THE DOOR TO SWING AGAINST THE
 DIRECTION OF EGRESS TRAVEL. THEREFORE, THIS DOOR COULD
 SWING INTO THE WORKROOM.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-02-15 Cont ID  
Sent By rmcdouga Date 2022-02-15 Time 16:40 Rev Time 0.00
Received By rmcdouga Date 2022-02-15 Time 08:23 Sent To  
Notes
2022-02-15 17:07:56PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: BC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE LIFE SAFETY PLAN SHOWS ONLY ONE EXIT. IT APPEARS
 THAT THE MOST REMOTE EXIT ACCESS TRAVEL DISTANCE WOULD
 BE FROM THE WORK ROOM #113, RATHER THAN THE SALES
 BALCONY #108. PLEASE SHOW THE COMMON PATH OF TRAVEL
 DISTANCE FROM THE MOST REMOTE POINT IN THE WORK ROOM TO
 THE SINGLE EXIT. FBC 1017.3
  
 2) FBC 1006.2.1 REQUIRES TWO EXITS FROM ANY SPACE THAT
 EXCEEDS THE OCCUPANT LOAD OR THE COMMON PATH OF EGRESS
 TRAVEL DISTANCE VALUES LISTED IN TABLE 1006.2.1. FOR A
 BUSINESS OCCUPANCY THE MAXIMUM OCCUPANT LOAD IS 49 AND
 THE MAXIMUM COMMON PATH OF EGRESS TRAVEL DISTANCE IN A
 FULLY SPRINKLERED BUILDING IS100 FEET. IF THE MAXIMUM
 COMMON PATH OF EGRESS TRAVEL DISTANCE FROM THE WORK
 ROOM EXCEEDS 100 FEET ANOTHER EXIT WILL BE REQUIRED.
  
 3) THE ORIGINAL PLANS FOR THE BUILDING SHOWS TWO SETS
 OF IN-SWING DOUBLE DOORS AT THE WEST SIDE OF THIS AREA.
 THE FLOOR PLAN SHOWS ONE SET OF THE DOORS EITHER BEING
 INOPERABLE OR REPLACED WITH STOREFRONT WINDOWS AND THE
 SOUTH SET OF DOORS BEING OUT-SWING. ARE THESE DOORS
 BEING REPLACED OR CHANGED? PLEASE CLARIFY. FBC
 AMENDMENTS 107.2.1
  
 4) ALL OF THE GLAZED DOORS, INTERIOR STOREFRONTS AND
 ELSEWHERE THAT ARE CONSIDERED AS HAZARDOUS LOCATIONS
 PER FBC 2406.4 ARE REQUIRED TO BE SAFETY GLAZING.
 SPECIFY THESE ON THE PLANS.
  
 5) THE FLOOR PLAN SHOWS STEPS FROM THE SIDE WALK TO THE
 ENTRANCE, HOWEVER, NO RAMPS ARE SHOWN. SHOW THE
 ACCESSIBILE ROUTE TO THE MAIN ENTRANCE TO THE SPACE.
 FBC ACCESSIBILITY 201.1.1 AND 402
  
 6) PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-02-25 Cont ID  
Sent By mpeterso Date 2022-02-25 Time 11:21 Rev Time 0.00
Received By mpeterso Date 2022-02-25 Time 11:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-02-02 Cont ID  
Sent By mpeterso Date 2022-02-02 Time 15:28 Rev Time 0.00
Received By mpeterso Date 2022-02-02 Time 15:28 Sent To  
Notes
2022-02-02 15:33:47ELECTRIC REVIEW FAILED
 1) PANEL SCHEDULES FOR PANEL "A" ON PLANS LABELED
 "EO.1" AND ES.1 DO NOT MATCH, PLEASE UPDATE OR REMOVE
 THE INCORRECT SCHEDULE FBC 107.2
 2) PROVIDE CLARITY AS TO WHETHER THIS SPACE WILL
 REQUIRE SHOW WINDOW RECEPTACLES. FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-03-08 Cont ID  
Sent By pleduc Date 2022-03-08 Time   Rev Time 0.00
Received By pleduc Date 2022-03-08 Time 10:11 Sent To  
Notes
2022-03-08 10:12:09FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED
 THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO,
 SHALL BE DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-02-25 Cont ID  
Sent By pleduc Date 2022-02-25 Time   Rev Time 0.00
Received By pleduc Date 2022-02-25 Time 12:32 Sent To  
Notes
2022-02-25 12:33:06FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED
 THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO,
 SHALL BE DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-01-25 Cont ID  
Sent By pleduc Date 2022-01-25 Time   Rev Time 0.00
Received By pleduc Date 2022-01-25 Time 12:09 Sent To  
Notes
2022-01-25 12:19:16FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED
 THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO,
 SHALL BE DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-03-10 Cont ID  
Sent By rmcdouga Date 2022-03-10 Time 16:59 Rev Time 0.00
Received By rmcdouga Date 2022-03-07 Time 06:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-02 Cont ID  
Sent By rmcdouga Date 2022-03-02 Time 14:08 Rev Time 0.00
Received By rmcdouga Date 2022-02-23 Time 07:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-02-15 Cont ID  
Sent By rmcdouga Date 2022-02-15 Time 17:25 Rev Time 0.00
Received By rmcdouga Date 2022-01-24 Time 09:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-02-28 Cont ID  
Sent By medwards Date 2022-02-28 Time 07:54 Rev Time 0.00
Received By medwards Date 2022-02-28 Time 07:51 Sent To  
Notes
2022-02-28 07:58:38APPROVED WITH PRIVISO:
  
 THE OUTDOOR AIR PROVIDED TO THE CONFERENCE ROOM SHALL
 NOT BE LESS THAN THE REQUIRED OUTDOOR AIR.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-01-26 Cont ID  
Sent By medwards Date 2022-01-26 Time 16:44 Rev Time 0.00
Received By medwards Date 2022-01-26 Time 16:44 Sent To  
Notes
2022-01-26 16:44:181ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22010536
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THIS TENANT SPACE. FBC EC C403.2.1
  
 2) THE OUTDOOR AIR CALCULATIONS DOES NOT PROVIDE
 CALCULATIONS FOR THE RECEPTION AREA OR THE STORAGE
 AREA, THE CORRIDOR OR THE KITCHENETTE/COPY ROOM. PLEASE
 PROVIDE THE REQUIRED OUTDOOR AIR CALCULATIONS FOR EACH
 USE OF SPACE IN THIS TENANT SPACE. FBC M 403.3.1.1 AND
 TABLE 403.3.1.1
  
 3) PLEASE SHOW THE ANCHORING OF THE CONDENSING UNITS.
 FBC 107.2.1
  
 4) PLEASE EXPLAIN WHY THE BATH EXHAUST IS
 NON-FUNCTIONING IS THE SALES MASTER BATH.
  
 5) IS THE SALES KITCHEN A FUNCTIONING KITCHEN? IF SO,
 IS THERE A HOOD ABOVE THE RANGE?
  
 6) PLEASE SHOW THE CONDENSATE PIPING MATERIAL, SIZE AND
 TERMINATION LOCATION. FBC M 307
  
 7) PLEASE SHOW THAT THE NEW CONDENSING UNITS WILL MEET
 THE CLEARANCES FROM THE ROOF EDGE IN FBC M 304.11
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-02-24 Cont ID  
Sent By jesmith Date 2022-02-24 Time 14:25 Rev Time 0.00
Received By jesmith Date 2022-02-24 Time 09:52 Sent To  
Notes
2022-02-24 14:25:0622010536 250 N OLIVE AVE
  
 PLUMBING COMMENTS: APPROVED
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 PROVISO: A WATER HAMMER ARRESTOR SHALL BE INSTALLED IN
 THE HOT WATER LINE SERVICING THE DISHWASHER PER FBC PL
 604.9
  
 PROVISO: INDIVIDUAL SHUTOFF VALVES SHALL BE INSTALLED
 ON THE HOT WATER FIXTURE SUPPLY FOR THE DISHWASHER AND
 FOR THE SINK PER FBC PL 606.2(1)
  
 PROVISO: PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1,
 PROVIDE AS DEFERRED SUBMITTALS, MANUFACTURER?S
 SPECIFICATION/INSTALLATION MANUAL FOR THE PLUMBING
 FIXTURES, KITCHEN EQUIPMENT AND BACKFLOW PREVENTERS AS
 INDICATED ON PLAN SHEET P0.1. SUBMITTAL SHALL BE
 SUBMITTED, APPROVED AND ON SITE PRIOR TO FINAL
 INSPECTION. PROCEED AT YOUR OWN RISK.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-01-27 Cont ID  
Sent By jesmith Date 2022-01-27 Time 16:36 Rev Time 0.00
Received By jesmith Date 2022-01-25 Time 16:35 Sent To  
Notes
2022-01-27 16:34:01CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22010536 215 N OLIVE AVE
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1. A2.3/DETAIL 18: PER WPB FBC 107.2.1, PROVIDE CLEAR
 FLOOR SPACE FOR THE ACCESSIBLE SINK, SHOWING COMPLIANCE
 WITH FBC ACC 606.2 AND 305.
  
 2. A2.3: PER WPB FBC 107.2.1, SHOW DIMENSIONED KNEE AND
 TOE CLEARANCE FOR THE ACCESSIBLE DRINKING FOUNTAIN
 SHOWING COMPLIANCE WITH FBC ACC 602.2 AND 306.
  
 3. A2.4/DETAIL 2 AND 5: DETAIL 2 AND 5 SHOW SPACING FOR
 REAR GRAB BAR TO BE 6 INCHES MINIMUM FROM THE SIDE
 WALL. FBC ACC 604.2 REQUIRES THE CENTERLINE OF THE
 WATER CLOSET FROM THE SIDE WALL TO BE 16 INCHES
 MINIMUM/18 INCHES MAXIMUM. PER WPB FBC 107.2.1, SHOW
 THE CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL
 TO BE 16 INCHES MINIMUM/18 INCHES MAXIMUM AND EITHER
 NOTE THE 6 INCHES SPACE AS MAXIMUM OR REMOVE THE
 DIMENSION ENTIRELY. PLEASE SHOW THE WATER CLOSET
 CENTERLINE DIMENSION ON DETAIL 2 AND DETAIL 5.
  
 4. A2.4/DETAIL 5: PER WPB FBC 107.2.1, PROVIDE CLEAR
 FLOOR SPACE FOR THE ACCESSIBLE LAVATORY, SHOWING
 COMPLIANCE WITH FBC ACC 606.2 AND 305.
  
 5. PER WPB FBC 107.2.1 AND FBC PL 310.3, PROVIDE WALL
 FINISH SCHEDULE OR DETAIL FOR THE MOP SINK IN STORAGE
 RM. 115. SHOW COMPLIANCE WITH FBC 1210.2.2.
 WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NON-ABSORBENT SURFACE TO A HEIGHT NOT LESS THAN 4 FEET
 ABOVE THE FLOOR PER FBC-BUILDING SEC. 1210.2.2. SECTION
 1210.2.2 STIPULATES THAT THE MATERIAL BE "HARD." THE
 INTENT OF THIS SECTION IS THAT THE SURROUNDING MATERIAL
 SHOULD NOT BE OF A TYPE THAT IS EASILY DAMAGED SUCH
 THAT THE MATERIAL COULD BECOME ABSORBENT AND THUS, NOT
 READILY CLEANABLE AND SANITIZED. PAINTED DRYWALL, EVEN
 WHERE COATED WITH HIGHLY DURABLE PAINTS, DOES NOT MEET
 THE INTENT OF SECTION 1210.2.2. THE TYPICAL MATERIALS
 USED FOR THIS APPLICATION ARE CERAMIC TILE, FIBERGLASS
 REINFORCED PLASTIC (FRP) PANELS, PHENOLIC PANELS,
 LAMINATED PLASTIC PANELS, PAINTED STEEL AND STAINLESS
 STEEL.
  
 6. P0.1 PLUMBING NOTES:
 ...A) NOTES 1, 11,24,25 ALL REFER TO 6TH EDITION FOR
 2020 FLORIDA BUILDING CODES. PER WPB FBC 107.2.1,
 CORRECT TO STATE 7TH EDITION.
 ...B) N/A
 ...C) N/A
 ...D) N/A
 ...E) NOTES 26 AND 28: BOTH ALLOW USE OF AIR ADMITTANCE
 VALVES/STUDOR VENTS TO BE USED FOR VENT PIPING THROUGH
 THE ROOF. PER WPB FBC 107.2.1, CLARIFY. IS IT THE
 INTENT THAT ONE OF THE TWO NOTES ALLOW AIR ADMITTANCE
 VALVES/STUDOR VENTS FOR INDIVIDUAL/BRANCH VENTS? PLEASE
 NOTE THAT PER FBC PL 904.1, THE VENT SYSTEM SERVING
 EACH BUILDING DRAIN SHALL HAVE NOT LESS THAN ONE VENT
 PIPE THAT EXTENDS TO THE OUTDOORS. PRIOR TO INSPECTION,
 A PLAN REVISION REFLECTING ANY ACTUAL USE OF AIR
 ADMITTANCE VALVES/STUDOR VENTS SHALL BE SUBMITTED TO
 THE BUILDING DEPARTMENT, APPROVED AND ON SITE. WPB FBC
 107.2.1.
 ...F) NOTE 33 SEEMS TO HAVE NO BEARING ON THE PROJECT.
 PER WPB FBC 107.2.1, IF THIS IS THE CASE, PLEASE DELETE
 IT.
 ...G) PER WPB FBC 107.2.1, PROVIDE NOTE STATING ?ALL
 COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE LEAD
 FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1.?
  
 7. P0.1 SANITARY RISER DIAGRAM:
 ...A) IT APPEARS THAT THE INDIVIDUAL VENT FOR THE MOP
 SINK VENTS THROUGH THE ROOF AND THE BRANCH VENTS FROM
 OTHER FIXTURES CONNECT TO IT. HOWEVER, THE SYMBOL FOR
 VTR IS BELOW THE CONNECTION POINT. PER WPB FBC 107.2.1,
 PLEASE CLARIFY.
 ...B) PER WPB FBC 107.2.3, PLEASE CLARIFY THAT THE VENT
 FOR THE BATHROOM GROUPS IS A VENT THROUGH THE ROOF. A
 VTR SYMBOL WOULD BE HELPFUL.
  
 8. P0.1 WATER RISER:
 ...A) PER WPB FBC 107.2.1, PROVIDE SCHEMATIC DETAIL FOR
 THE DISHWASHER/SINK/ IWH TO INCLUDE VALVES AND WATER
 HAMMER ARRESTOR (SEE FBC PL 604.9).
 ...B) PER WPB FBC 107.2.1, CONFIRM THAT THE WATER
 HAMMER ARRESTOR PLACEMENT FOR THE SALES KITCHEN
 ADEQUATELY SERVICES THE COLD WATER MAKE UP TO THE
 REFRIGERATOR AND FREEZER ICEMAKERS. IF NECESSARY, PLACE
 THEM IN A MORE SUITABLE LOCATION FOR THE TWO
 CONNECTIONS.
  
 9. PER WPB FBC 107.2.1, PROVIDE A BACKFLOW PREVENTER
 SCHEDULE AND SPECIFY BACKFLOW PREVENTER TYPE AND
 STANDARD (ASSE, ASME ETC.). PROVIDE NOTE, BACKFLOW
 PREVENTERS SHALL BE LEAD FREE.
  
 10. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL
 WITH A NOTE STATING, "HORIZONTAL PIPE SHALL BE
 SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5."
  
 11. PER WPB FBC 107.2.1, PROVIDE A DETAIL FOR THE
 DISHWASHER SHOWING COMPLIANCE WITH FBC PL 409.4. THE
 WASTE CONNECTION OF A RESIDENTIAL DISHWASHER SHALL
 CONNECT DIRECTLY TO A WYE BRANCH FITTING ON THE
 TAILPIECE OF THE KITCHEN SINK, DIRECTLY TO THE
 DISHWASHER CONNECTION OF A FOOD WASTE DISPOSER, OR
 THROUGH AN AIR BREAK TO A STANDPIPE. THE WASTE LINE OF
 A RESIDENTIAL DISHWASHER SHALL RISE AND BE SECURELY
 FASTENED TO THE UNDERSIDE OF THE SINK RIM OR COUNTER
 TOP.
  
 12. PER WPB FBC 107.2.1, PROVIDE SCHEDULE/SPECIFICATION
 FOR THE CONDENSATE PUMP.
  
 13. P2.0: PER WPB FBC 107.2.1, NOTE SIZING OF
 CONDENSATE DRAINS.
  
 14. P2.0: PER WPB FBC 107.2.1, NOTE DESIGNATED AHU AT
 EACH CONDENSATE PIPING CONNECTION.
  
 15. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUALS FOR ANY EQUIPMENT
 REQUIRING A PLUMBING CONNECTION THAT IS NOT LISTED ON
 THE PLUMBING FIXTURE SCHEDULE. IF THESE MAY BE DEFERRED
 IN ACCORDANCE WITH WPB FBC 107.3.4.2 AS LONG AS THEY
 ARE LISTED ON THE PLANS. SAID DOCUMENTS SHALL BE
 SUBMITTED, APPROVED AND ON SITE PRIOR TO FINAL
 INSPECTION.
  
 16. PER WPB FBC 107.2.1, PROVIDE A PLUMBING FIXTURE
 CONNECTION SCHEDULE; DFU/TRAP SIZE AND WSFU/CONNECTION
 SIZE
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 22010536 215 N OLIVE AVE
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-03-10 Cont ID  
Sent By rmcdouga Date 2022-03-10 Time 16:55 Rev Time 0.00
Received By rmcdouga Date 2022-03-10 Time 16:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-03-02 Cont ID  
Sent By rmcdouga Date 2022-03-02 Time 11:20 Rev Time 0.00
Received By rmcdouga Date 2022-03-02 Time 11:20 Sent To  
Notes
2022-03-02 11:24:35THE RESUBMITTED PLANS ARE NOT SIGNED AND SEALED.
 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON THEM.
 YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED AND
 SEALED PAPER VERSION OF DRAWINGS. AFTER THE ELECTRONIC
 PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE
 CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT
 TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 481 & 61G1 OR FS 471 &
 61G15

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-02-15 Cont ID  
Sent By rmcdouga Date 2022-02-15 Time 17:25 Rev Time 0.00
Received By rmcdouga Date 2022-02-15 Time 17:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-02-25 Cont ID  
Sent By ckimmerl Date 2022-02-25 Time 10:51 Rev Time 0.00
Received By ckimmerl Date 2022-02-25 Time 10:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-02-08 Cont ID  
Sent By aaponte Date 2022-02-08 Time 09:33 Rev Time 0.00
Received By ckimmerl Date 2022-02-08 Time 09:33 Sent To  
Notes
***NONE***