2022-02-14 09:44:48 | 02/14/22 1ST LP GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. THE ISOMETRIC SHOWS A METER, AND THIS IS AN LP |
| TANK; PLEASE CLARIFY IF THE LP TANK IS NOT BEING USED |
| OR A GAS METER WILL BE ADDED PER THE WPB AMENDMENTS TO |
| THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| 2. WOULD YOU PLEASE SHOW WHAT IS NEW AND EXISTING PER |
| THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| ON CONSTRUCTION DOCUMENTS. |
| |
| 3. THE CITY OF WEST PALM BEACH HAS A PERMIT (07030314) |
| ON FILE FOR THE GENERATOR, AND IT IS NOT SHOWN ON THE |
| SYSTEM OR NOTE. WOULD YOU PLEASE CORRECT PER THE WPB |
| AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| 4. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF |
| THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH |
| FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA |
| STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 107.1 GENERAL. |
| |
| |
| 5. THE TOTAL BTU LOAD FOR THE SYSTEM IS INCORRECT. THE |
| EXISTING GAS SYSTEM MUST BE ADDED TO THE TOTAL BTU LOAD |
| TO ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. THE |
| EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE |
| OPERATING SYSTEM IF UNDERSIZED. SUBMIT A GAS PIPING |
| RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING |
| APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE |
| SIZE, AND THE TYPE OF PIPE TO EACH APPLIANCE. |
| |
| 6. THIS TANK-LESS UNIT CALL FOR A 10.5" WATER COLUMN, |
| AND THE PRESSURE MAY REQUIRE A REGULATOR FOR THIS UNIT |
| AS PER THE MANUFACTURER'S SPECIFICATION. SUBMIT |
| MANUFACTURER?S SPECIFICATIONS FOR THE PRESSURE |
| REGULATORS. REGULATORS INSTALLED ON THE EXTERIOR OF THE |
| BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION PER |
| THE 2020 FBC RES. SEC. G2421.1. |
| |
| 7. WOULD YOU PLEASE SUBMIT A HOUSE PLAN SHOWING THE |
| LOCATION OF THE TANK-LESS WATER HEATER AND THE LOCATION |
| AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| RELATION TO THE WATER HEATER? THE LOCATION OF THE WATER |
| HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE |
| HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 8. WOULD YOU PLEASE SHOW ALL UNIONS IN FRONT OF |
| REGULATOR 1' OF EITHER SIDE FOR THE TANKLESS PER THE |
| 2020 FBC RES. SEC G2421.2. |
| |
| 9. WOULD YOU PLEASE SHOW AND LABEL THE SHUTOFF VALVE ON |
| GAS ISOMERIC FOR THE TANKLESS PER THE 2020 FBC RES. |
| SEC. G2420.5. |
| |
| 10. WOULD YOU PLEASE LABEL AND SHOW DRIP LEG ON |
| TANKLESS 2020 FBC RES. SEC. G2419.2. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |
| WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON |
| REQUEST. |
| |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |