2022-02-03 11:17:46 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1 |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 22010486 1400 CENTREPARK BLVD # 500 |
| |
| 1ST REVIEW |
| PLUMBING COMMENTS: DENIED |
| A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| APPROVAL. |
| |
| 1. A-4/DETAIL 4: PER FBC ACC 603.3, MIRRORS LOCATED |
| ABOVE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH |
| THE BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES |
| MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. PER WPB FBC |
| 107.2.1, PLEASE REVISE TO CLARIFY THE SAME. |
| |
| 2. A-4/DETAIL 1 AND 2: ACCESSIBLE URINALS SHALL BE THE |
| STALL-TYPE OR THE WALL-HUNG TYPE WITH THE RIM 17 INCHES |
| MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC ACC |
| 605.2. PER WPB FBC 107.2.1, PROVIDE DETAIL. |
| |
| 3. PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER |
| SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE |
| INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST |
| CONTACT. PER WPB FBC 107.2.1, PROVIDE NOTE. |
| |
| 4. A-2 AND A-11: PER WPB FBC 107.2.1, PROVIDE CLEAR |
| FLOOR SPACE FOR SINK IN CAF? RM 512 COMPLYING WITH FBC |
| ACC 305 POSITIONED FOR A FORWARD APPROACH AND CENTERED |
| ON THE UNIT. |
| |
| 5. PER WPB FBC 107.2.1, PROVIDE LOCATION OF DRINKING |
| FOUNTAIN SHOWING COMPLIANCE WITH FBC PL 403.1, TABLE |
| 403.1 AND 403.5. IF THERE ARE NONE, PROVIDE DRINKING |
| FOUNTAIN(S) COMPLYING WITH FBC PL 410.3, FBC ACC 211.2 |
| AND 602.1 THROUGH 602.6 AND 602.7. |
| |
| 6. PER WPB FBC 107.2.1, PROVIDE LOCATION OF SERVICE |
| SINK SHOWING COMPLIANCE WITH FBC PL TABLE 403.1. |
| |
| 7. P0.1/PLUMBING FIXTURE SCHEDULE SPECIFIES NEW WALL |
| HUNG WATER CLOSETS (TAG HWC); THE SANITARY RISER |
| DIAGRAM INDICATES FLOOR MOUNTED. PER WPB FBC 107.2.1, |
| CLEARLY SHOW ON THE RISER DIAGRAM THE CARRIER ASSEMBLY |
| AND VENTING. RECONCILE P2.1 WITH REVISED RISER DIAGRAM. |
| |
| 8. P0.1 PLUMBING NOTES: |
| ...A) NOTES 1, 11,24,25 ALL REFER TO 6TH EDITION FOR |
| 2020 FLORIDA BUILDING CODES. PER WPB FBC 107.2.1, |
| CORRECT TO STATE 7TH EDITION. |
| ...B) NOTE 11 CALLS FOR TYPE L COPPER FOR WATER |
| DISTRIBUTION PIPE BUT ALLOWS ALTERNATE MATERIALS. PRIOR |
| TO INSPECTION, A PLAN REVISION REFLECTING THE ACTUAL |
| MATERIAL SHALL BE SUBMITTED TO THE BUILDING DEPARTMENT, |
| APPROVED AND ON SITE. WPB FBC 107.2.1. |
| ...C) NOTE 12 CALLS FOR CAST IRON OR PVC FOR THE |
| SANITARY PIPING. PRIOR TO INSPECTION, A PLAN REVISION |
| REFLECTING THE ACTUAL MATERIAL SHALL BE SUBMITTED TO |
| THE BUILDING DEPARTMENT, APPROVED AND ON SITE. WPB FBC |
| 107.2.1. |
| ...D) NOTE 24 CALLS FOR TYPE L COPPER WITH ARMAFLEX |
| INSULATION FOR CONDENSATE PIPING THEN ALLOWS PVC WITH |
| INSULATION IN RETURN AIR PLENUMS. PER WPB FBC 107.2.1, |
| CLARIFY. ADDITIONALLY, PROVIDE THE FIRE/SMOKE RATING |
| FOR THE INSULATION. PRIOR TO INSPECTION, A PLAN |
| REVISION REFLECTING THE ACTUAL MATERIAL SHALL BE |
| SUBMITTED TO THE BUILDING DEPARTMENT, APPROVED AND ON |
| SITE. WPB FBC 107.2.1. |
| ...E) NOTES 26 AND 28: BOTH ALLOW USE OF AIR ADMITTANCE |
| VALVES/STUDOR VENTS TO BE USED FOR VENT PIPING THROUGH |
| THE ROOF. |
| ......1) PLEASE NOTE; FBC PL 918.3.1 REQUIRES AIR |
| ADMITTANCE VALVES ARE LOCATED MORE THAN FOUR BRANCH |
| INTERVALS FROM THE TOP OF THE STACK, THE HORIZONTAL |
| BRANCH SHALL BE PROVIDED WITH A RELIEF VENT THAT SHALL |
| CONNECT TO A VENT STACK OR STACK VENT, OR EXTEND |
| OUTDOORS TO THE OPEN AIR. THE SCOPE OF WORK IS ON THE |
| 5TH FLOOR OF A 10 STORY BUILDING. PER WPB FBC 107.2.1, |
| CLARIFY. IS IT THE INTENT THAT ONE OF THE TWO NOTES |
| ALLOW AIR ADMITTANCE VALVES/STUDOR VENTS FOR |
| INDIVIDUAL/BRANCH VENTS? PRIOR TO INSPECTION, A PLAN |
| REVISION REFLECTING ANY ACTUAL USE OF AIR ADMITTANCE |
| VALVES/STUDOR VENTS SHALL BE SUBMITTED TO THE BUILDING |
| DEPARTMENT, APPROVED AND ON SITE. WPB FBC 107.2.1. |
| ...F) NOTE 33 SEEMS TO HAVE NO BEARING ON THE PROJECT. |
| PER WPB FBC 107.2.1, IF THIS IS THE CASE, PLEASE DELETE |
| IT. |
| ...G) PER WPB FBC 107.2.1, PROVIDE NOTE STATING "ALL |
| COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE LEAD |
| FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1." |
| |
| 9. P0.1 WATER RISER: PER WPB FBC 107.2.1, PROVIDE |
| SCHEMATIC DETAIL FOR THE DISHWASHER/SINK/ IWH TO |
| INCLUDE VALVES AND WATER HAMMER ARRESTOR (SEE FBC PL |
| 604.9). |
| |
| 10. PER WPB FBC 107.2.1, PROVIDE A BACKFLOW PREVENTER |
| SCHEDULE AND SPECIFY BACKFLOW PREVENTER TYPE AND |
| STANDARD (ASSE, ASME ETC.). PROVIDE NOTE, BACKFLOW |
| PREVENTERS SHALL BE LEAD FREE. |
| |
| 11. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL |
| WITH A NOTE STATING, "HORIZONTAL PIPE SHALL BE |
| SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5." |
| |
| 12. PER WPB FBC 107.2.1, PROVIDE A DETAIL FOR THE |
| DISHWASHER SHOWING COMPLIANCE WITH FBC PL 409.4. THE |
| WASTE CONNECTION OF A RESIDENTIAL DISHWASHER SHALL |
| CONNECT DIRECTLY TO A WYE BRANCH FITTING ON THE |
| TAILPIECE OF THE KITCHEN SINK, DIRECTLY TO THE |
| DISHWASHER CONNECTION OF A FOOD WASTE DISPOSER, OR |
| THROUGH AN AIR BREAK TO A STANDPIPE. THE WASTE LINE OF |
| A RESIDENTIAL DISHWASHER SHALL RISE AND BE SECURELY |
| FASTENED TO THE UNDERSIDE OF THE SINK RIM OR COUNTER |
| TOP. |
| |
| 13. PER WPB FBC 107.2.1, PROVIDE APPLICABLE RATED |
| WALL/FLOOR DETAILS FOR PLUMBING PENETRATIONS COMPLYING |
| WITH THE REQUIREMENTS OF FBC CHAPTER 7. |
| |
| 14. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S |
| SPECIFICATION/INSTALLATION MANUALS FOR ANY EQUIPMENT |
| REQUIRING A PLUMBING CONNECTION THAT IS NOT LISTED ON |
| THE PLUMBING FIXTURE SCHEDULE. IF THESE MAY BE DEFERRED |
| IN ACCORDANCE WITH WPB FBC 107.3.4.2 AS LONG AS THEY |
| ARE LISTED ON THE PLANS. SAID DOCUMENTS SHALL BE |
| SUBMITTED, APPROVED AND ON SITE PRIOR TO FINAL |
| INSPECTION. |
| |
| 15. PER WPB FBC 107.2.1, PROVIDE A PLUMBING FIXTURE |
| CONNECTION SCHEDULE; DFU/TRAP SIZE AND WSFU/CONNECTION |
| SIZE |
| |
| 16. P2.1/FLOOR DRAIN FOR ICEMAKER |
| ...A) WASTE RECEPTORS SHALL NOT BE INSTALLED IN |
| CONCEALED SPACES. READY ACCESS SHALL BE PROVIDED TO |
| WASTE RECEPTORS PER FBC PL 802.4. PER WPB FBC 107.2.1, |
| SHOW COMPLIANCE. |
| ...B) PER WPB FBC 107.2.1, PROVIDE DETAIL AND |
| SPECIFICATION FOR TRAP PRIMER |
| ...C) PER WPB FBC 107.2.1, PROVIDE DETAIL OF FLOOR |
| DRAIN AND ICE MAKER DISCHARGE WITH AIR GAP |
| |
| 17. PER WPB FBC 107.2.1, PROVIDE AC CONDENSATE PIPE |
| ROUTING AND SIZES. COMPLY WITH THE REQUIREMENTS OF FBC |
| PL 314. |
| |
| 18. P0.1/WATER RISER: PER WPB FBC 107.2.1, CORRECTLY |
| IDENTIFY SK-2. |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| |