Plan Review Details - Permit 22010358
Plan Review Stops For Permit 22010358
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-03-15 Cont ID  
Sent By jbrooks Date 2022-03-15 Time 14:09 Rev Time 0.00
Received By jbrooks Date 2022-03-15 Time 11:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-02-28 Cont ID  
Sent By jbrooks Date 2022-02-28 Time 13:35 Rev Time 0.00
Received By jbrooks Date 2022-02-28 Time 08:04 Sent To  
Notes
2022-02-28 13:36:13JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected].
  
 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL1654-R28 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 1-5 TO
 INCLUDE LIMITATIONS PAGE(S). THE EVALUATION REPORTS CAN
 BE PRINTED FROM THE SUMMARY OF PRODUCTS LOCATED AT THE
 BOTTOM OF THE COVER PAGE. PRINT PAGES 1-5 ONLY. SELECT
 SYSTEM USED TO MEET MINIMUM DESIGN PRESSURE REQUIREMENT
 FOR EXPOSURE CATEGORY C AREA. (-108.17)
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL4595.19-R6 COVERS MULTIPLE FASTENER SPACING
 TO MEET DESIGN UPLIFT PRESSURES. PLEASE SELECT CORRECT
 FASTENER PATTERN & SPACING FROM TABLE ?A? PAGE #2 OF
 THE EVALUATION REPORT THAT MEET OR EXCEED THE MINIMUM
 DESIGN PRESSURE REQUIREMENT FOR ZONE 3 EXPOSURE
 CATEGORY C AREAS. (-108.17). ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING. SECOND REQUEST.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-02-10 Cont ID  
Sent By jbrooks Date 2022-02-10 Time 08:54 Rev Time 0.00
Received By jbrooks Date 2022-02-10 Time 07:31 Sent To  
Notes
2022-02-10 08:54:19JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R33
 HAS BEEN REVISED TO FL5259-R34. PLEASE PROVIDE A
 COMPLETE SET; IT COVERS MULTIPLE PRODUCT TYPES; ROOF
 COVER OPTIONS; ALLOWABLE UNDERLAYMENT/TILE-ADHESIVE
 COMBINATIONS & ALLOWABLE SUBSTRATES. SELECT OPTIONS TO
 BE USED. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE
 CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN
 PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
 2. SUBMITTED PRODUCT APPROVAL FL1654-R27 HAS BEEN
 REVISED TO FL1654-R28. PROVIDE THE FOLLOWING: COVER
 PAGE, EVALUATION REPORTS PAGES 1-5 TO INCLUDE
 LIMITATIONS PAGE(S) AND INSTALLATION INSTRUCTIONS FOR
 SYSTEM USED. SELECTED SYSTEM W-209 DO NOT MEET OR
 EXCEEDS EXPOSURE CATEGORY C MINIMUM DESIGN PRESSURE
 ZONE 3 REQUIREMENTS OF -108.17. PLEASE SELECT SYSTEM
 NO. THAT MEETS OR EXCEEDS REQUIREMENTS OR PROVIDE
 SIGNED AND SEALED ENGINEERED NAILING CALCULATION FOR
 ZONE 3.
 3. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL11602-R11
 HAS BEEN REVISED TO FL11602-R13. PLEASE PROVIDE A
 COMPLETE SET; IT COVERS MULTIPLE PRODUCT TYPES; ROOF
 COVER OPTIONS; ALLOWABLE UNDERLAYMENT/TILE-ADHESIVE
 COMBINATIONS & ALLOWABLE SUBSTRATES. SELECT OPTIONS TO
 BE USED. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE
 CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN
 PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
 4. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL4595.19-R6 COVERS MULTIPLE FASTENER SPACING
 TO MEET DESIGN UPLIFT PRESSURES. PLEASE SELECT CORRECT
 FASTENER PATTERN & SPACING FROM TABLE ?A? PAGE #2 OF
 THE EVALUATION REPORT THAT MEET OR EXCEED THE MINIMUM
 DESIGN PRESSURE REQUIREMENT FOR ZONE 3 EXPOSURE
 CATEGORY C AREAS. (-108.17). ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-03-15 Cont ID  
Sent By jbrooks Date 2022-03-15 Time 14:10 Rev Time 0.00
Received By jbrooks Date 2022-03-07 Time 07:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-02-28 Cont ID  
Sent By jbrooks Date 2022-02-28 Time 13:36 Rev Time 0.00
Received By jbrooks Date 2022-02-16 Time 06:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-02-10 Cont ID  
Sent By jbrooks Date 2022-02-10 Time 08:54 Rev Time 0.00
Received By jbrooks Date 2022-02-08 Time 06:52 Sent To  
Notes
***NONE***