Plan Review Details - Permit 22010238
Plan Review Stops For Permit 22010238
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-06-13 Cont ID  
Sent By rmcphers Date 2023-06-09 Time 11:39 Rev Time 0.00
Received By rmcphers Date 2023-06-09 Time 11:39 Sent To  
Notes
2023-06-09 11:48:19PROVISO- PLEASE PROVIDE A SIGNED AND SEALED EQUIPMENT
 STAND DETAIL FROM A DESIGN PROFESSIONAL AND OR
 CALCULATIONS AS STATED IN THE RESPONSE LETTER FROM THE
 DESIGNER BEFORE INSTALLATION.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-04-05 Cont ID  
Sent By rmcdouga Date 2023-04-05 Time 09:14 Rev Time 0.00
Received By rmcdouga Date 2023-04-05 Time 09:14 Sent To  
Notes
2023-04-05 09:14:07PLAN
 REVIEW COMMENTS
 BEACHSIDE POOL
  
 3RD REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED.
  
 2) COMPLIED.
  
 3) NOT COMPLIED. [ THE RESPONSE LETTER STATES THAT THE
 POOL EQUIPMENT IS LOCATED IN THE PARKING GARAGE. THE
 PLANS SHOW THE POOL EQUIPMENT LOCATED TO THE SOUTH EAST
 OF THE BEACH CLUB.] THE POOL IS LOCATED IN A SPECIAL
 FLOOD HAZARD AREA. SHOW HOW THE POOL AND POOL EQUIPMENT
 WILL COMPLY WITH FBC 1612.4.2.
  
 4) COMPLIED.
  
 5) COMPLIED.
  
 6) NOT COMPLIED. [ THE RESPONSE LETTER STATES THAT THE
 POOL EQUIPMENT IS TO BE ANCHORED PER THE MANUFACTURER
 INSTALLATION INSTRUCTIONS. THE MANUFACTURER DOES NOT
 SPECIFIY ANCHORING FOR WINDLOADS. IF THE EQUIPMENT IS
 LOCATED INSIDE OF A BUILDING, THE EQUIPMENT DOES NOT
 HAVE TO BE ANCHORED TO RESIST WIND LOADS.] SHOW HOW THE
 POOL EQUIPMENT IS ANCHORED TO RESIST WIND LOADS. FBC
 1601.1 AND 1603.1.4
  
 7) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-12-14 Cont ID  
Sent By rmcdouga Date 2022-12-14 Time 14:41 Rev Time 0.00
Received By rmcdouga Date 2022-12-14 Time 14:41 Sent To  
Notes
2022-12-14 14:45:24PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED.
  
 2) COMPLIED.
  
 3) NOT COMPLIED. THE POOL IS LOCATED IN A SPECIAL FLOOD
 HAZARD AREA. SHOW HOW THE POOL AND POOL EQUIPMENT WILL
 COMPLY WITH FBC 1612.4.2.
  
 4) NOT COMPLIED.PROVIDE STRUCTURAL DETAILS FOR THE
 POOL. FBC AMENDMENTS 107.2.1
  
 5) COMPLIED.
  
 6) NOT COMPLIED. SHOW HOW THE POOL EQUIPMENT IS
 ANCHORED TO RESIST WIND LOADS. FBC 1601.1 AND 1603.1.4
  
 7) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-03-24 Cont ID  
Sent By rmcdouga Date 2022-03-24 Time 17:14 Rev Time 0.00
Received By rmcdouga Date 2022-03-24 Time 17:14 Sent To  
Notes
2022-03-24 17:14:08PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHOW THAT THE SANITARY FACILITIES FOR THE POOL MEET
 THE REQUIREMENTS OF FBC 454.1.6.1.
  
 2) REVISE THE POOL RULES SIGN ON SHEET 011-PL0.22 TO
 REFLECT THE 2020 FBC 454.1.2.3.5 REQUIREMENTS FOR
 MAXIMUM POOL DEPTH AND ALLOWING COMMERCIALLY BOTTLED
 WATER ON THE WET DECK.
  
 3) THE POOL IS LOCATED IN A SPECIAL FLOOD HAZARD AREA.
 SHOW HOW THE POOL AND POOL EQUIPMENT WILL COMPLY WITH
 FBC 1612.4.2.
  
 4) PROVIDE STRUCTURAL DETAILS FOR THE POOL. FBC
 AMENDMENTS 107.2.1
  
 5) THIS IS AN AREA OF QUESTIONABLE SOILS. SUBMIT A
 GEOTECHNICAL REPORT FOR THE POOL. FBC 1603.1 AND
 1603.1.6
  
 6) SHOW HOW THE POOL EQUIPMENT IS ANCHORED TO RESIST
 WIND LOADS. FBC 1601.1 AND 1603.1.4
  
 7) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-03-30 Cont ID  
Sent By fgiaquin Date 2023-03-30 Time 20:46 Rev Time 0.00
Received By fgiaquin Date 2023-03-30 Time 18:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-12-06 Cont ID  
Sent By fgiaquin Date 2022-12-06 Time 07:42 Rev Time 0.00
Received By fgiaquin Date 2022-12-06 Time 07:34 Sent To  
Notes
2022-12-06 07:42:08ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. SHOW WIRING
 DIAGRAM FOR POOL EQUIPMENT, ETC.. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-02-08 Cont ID  
Sent By fgiaquin Date 2022-02-08 Time 19:34 Rev Time 0.00
Received By fgiaquin Date 2022-02-07 Time 23:18 Sent To  
Notes
2022-02-08 19:33:58ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL FS
 471.003(2)(H); 471.025; WPB FBC 107.2.1, 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2023-03-20 Cont ID  
Sent By ccole Date 2023-03-20 Time 14:43 Rev Time 0.00
Received By ccole Date 2023-03-20 Time 14:05 Sent To  
Notes
2023-03-20 14:44:05SEPARATE PERMIT REQUIRED FOR GAS PIPING AND GAS POOL
 HEATER INSTALLATIONS.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-11-21 Cont ID  
Sent By ccole Date 2022-11-21 Time 12:05 Rev Time 0.00
Received By ccole Date 2022-11-21 Time 12:05 Sent To  
Notes
2022-11-21 12:10:151ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 22010208
 11/21/22
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE GAS PIPING PLANS AND DETAILS FOR
 INSTALLATION OF THE GAS-FIRED HEATER INCLUDING A GAS
 RISER, A PIPING LAYOUT PLAN, AND COMBUSTION AIR AND
 VENTING- SEC. 107.2.1 & 107.3.5.1.3 WPB. THE GAS CAN BE
 SUBMITTED UNDER A SEPARATE PERMIT BY REQUEST.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-06-09 Cont ID  
Sent By rmcphers Date 2023-06-09 Time 11:49 Rev Time 0.00
Received By rmcphers Date 2023-06-06 Time 11:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-04-05 Cont ID  
Sent By rmcdouga Date 2023-04-05 Time 09:14 Rev Time 0.00
Received By rmcdouga Date 2023-03-17 Time 16:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-14 Cont ID  
Sent By rmcdouga Date 2022-12-14 Time 14:45 Rev Time 0.00
Received By rmcdouga Date 2022-11-14 Time 08:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-19 Cont ID  
Sent By cpuell Date 2022-05-19 Time 13:10 Rev Time 0.00
Received By cpuell Date 2022-01-21 Time 11:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-03-20 Cont ID  
Sent By ccole Date 2023-03-20 Time 14:42 Rev Time 0.00
Received By ccole Date 2023-03-20 Time 14:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-11-21 Cont ID  
Sent By ccole Date 2022-11-21 Time 12:04 Rev Time 0.00
Received By ccole Date 2022-11-21 Time 08:44 Sent To  
Notes
2022-11-21 12:05:062ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22010238
 11/21/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 BEACHSIDE POOL. THE REQUESTED RESPONSE NARRATIVE TO
 HELP EXPEDITE THE REVIEW WAS NOT PROVIDED. THE PLANS
 HAVE NOT BEEN COMPLETED CORRECTED. PLEASE CORRECT THE
 PLANS BASED ON THE COMMENTS AND PROVIDE A NARRATIVE
 RESPONSE
  
 1) 2ND REQUEST. PL0.20: REFER TO FAC 64 E-9.004 PRINTED
 BELOW AND VERIFY THE IRRIGATION SYSTEM WILL BE
 INSTALLED IN COMPLIANCE-
 64E-9.004: LANDSCAPE IRRIGATION WATER THAT WETS THE WET
 DECK AREA OF THE POOL, THE POOL ITSELF, ENTERS THE
 COLLECTOR TANK, OR WETS AN INTERACTIVE WATER FEATURE
 MUST BE POTABLE WATER FROM A PUBLIC WATER SYSTEM OR
 SHALL MEET THE BACTERIOLOGICAL QUALITY OF POTABLE WATER
 AS EVIDENCED BY ANNUAL LABORATORY ANALYSIS SUBMITTED TO
 THE DEPARTMENT. RECLAIMED WATER MAY NOT BE USED IN
 THESE AREAS. IF RECLAIMED WATER IS USED IN THE VICINITY
 OF THE POOL (INSIDE OF THE POOL FENCE OR WITHIN 100
 FEET OF THE POOL WATER'S EDGE) IT MUST EMPLOY DRIP
 IRRIGATION OR SOAKER HOSES. SIGNS SHALL BE POSTED
 NOTIFYING POOL PATRONS THAT RECLAIMED WATER IS IN USE
 AND IS NOT TO BE CONSUMED.
  
  
 2) 2ND REQUEST. PL0.20: SHOW THE LOCATION OF THE
 REQUIRED HOSE BIB OR BIBS WITH VACUUM BREAKERS FOR THE
 POOL DECK- SEC. 454.1.3.1.5 FBC B.
  
 3) PL6.00 & PL6.20: THE 4???6??? DEPTH AT THE POOL LIFT
 LOCATION EXCEEDS THE MAXIMUM 4??? ALLOWABLE- SEC.
 1009.2.1 FBC ACC.
  
 4) 2ND REQUEST FOR POOL LIFT SPECS. THE SPECS MAY BE A
 DEFERERED SUBMITTAL BY REQUEST. PL0.22 & PL6.00: PLEASE
 PROVIDE ENLARGED DIMENSIONED DETAILS ON THE PLANS AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL LIFT
 INSTALLATION IN COMPLIANCE WITH THE FOLLOWING FBC ACC
 CODE SECTIONS:
 A) 1009.2.2 SEAT LOCATION.
 IN THE RAISED POSITION, THE CENTERLINE OF THE SEAT
 SHALL BE LOCATED OVER THE DECK AND 16 INCHES MINIMUM
 FROM THE EDGE OF THE POOL. THE DECK SURFACE BETWEEN THE
 CENTERLINE OF THE SEAT AND THE POOL EDGE SHALL HAVE A
 SLOPE NOT STEEPER THAN 1:48.
 B) 1009.2.3 CLEAR DECK SPACE.
 ON THE SIDE OF THE SEAT OPPOSITE THE WATER, A CLEAR
 DECK SPACE SHALL BE PROVIDED PARALLEL WITH THE SEAT.
 THE SPACE SHALL BE 36 INCHES WIDE MINIMUM AND SHALL
 EXTEND FORWARD 48 INCHES MINIMUM FROM A LINE LOCATED 12
 INCHES BEHIND THE REAR EDGE OF THE SEAT. THE CLEAR DECK
 SPACE SHALL HAVE A SLOPE NOT STEEPER THAN 1:48.
 C) 1009.2.4 SEAT HEIGHT.
 THE HEIGHT OF THE LIFT SEAT SHALL BE DESIGNED TO ALLOW
 A STOP AT 16 INCHES (405 MM) MINIMUM TO 19 INCHES
 MAXIMUM MEASURED FROM THE DECK TO THE TOP OF THE SEAT
 SURFACE WHEN IN THE RAISED (LOAD) POSITION.
 D) 1009.2.6 FOOTRESTS AND ARMRESTS.
 FOOTRESTS SHALL BE PROVIDED AND SHALL MOVE WITH THE
 SEAT. IF PROVIDED, THE ARMREST POSITIONED OPPOSITE THE
 WATER SHALL BE REMOVABLE OR SHALL FOLD CLEAR OF THE
 SEAT WHEN THE SEAT IS IN THE RAISED (LOAD) POS
 E) 1009.2.7 OPERATION.
 THE LIFT SHALL BE CAPABLE OF UNASSISTED OPERATION FROM
 BOTH THE DECK AND WATER LEVELS. CONTROLS AND OPERATING
 MECHANISMS SHALL BE UNOBSTRUCTED WHEN THE LIFT IS IN
 USE AND SHALL COMPLY WITH 309.4.
 F) 1009.2.8 SUBMERGED DEPTH.
 THE LIFT SHALL BE DESIGNED SO THAT THE SEAT WILL
 SUBMERGE TO A WATER DEPTH OF 18 INCHES MINIMUM BELOW
 THE STATIONARY WATER LEVEL.
 G) 1009.2.9 LIFTING CAPACITY.
 SINGLE PERSON POOL LIFTS SHALL HAVE A WEIGHT CAPACITY
 OF 300 POUNDS MINIMUM AND BE CAPABLE OF SUSTAINING A
 STATIC LOAD OF AT LEAST ONE AND A HALF TIMES THE RATED
 LOAD.
  
  
 5) 2ND REQUEST. PL6.10: A) PROVIDE A SECTION VIEW OF
 THE POOL GUTTERS SHOWING COMPLIANCE WITH SECS.
 454.1.6.5.3.1 & 454.1.6.5.3.1.1 FBC. THE GUTTERS SHALL
 BE IDENTIFIED AS EITHER RECESSED OR OPEN TYPE. B) SHOW
 THE DRAIN SPACINGS ON THE PLAN OR PROVIDE A NOTE TO
 INDICATE SPACING NOT TO EXCEED 10FT. C) CONCERNING
 PERIMETER OVERFLOW GUTTERS: THE LIP OF THE GUTTER SHALL
 BE UNIFORMLY LEVEL WITH A MAXIMUM TOLERANCE OF 1/4 INCH
 BETWEEN THE HIGH AND LOW AREAS. THE BOTTOM OF THE
 GUTTER SHALL BE LEVEL OR SLOPE TO THE DRAINS. E) IT
 APPEARS THE GUTTERS DO NOT EXTEND ALONG THE ENTIRE
 PERIMETER OF THE POOL. THE EXCEPTION ALLOWS GUTTER
 ELIMINATION AT A LENGTH NOT TO EXCEED 15 FT. AND NOT TO
 EXCEED 10 PERCENT OF THE PERIMETER.
  
 13) 2ND REQUEST PL6.10: SHOW THE SPACING MEASUREMENTS
 BETWEEN THE WALL INLETS IN COMPLIANCE WITH SEC.
 454.1.6.5.9.1 FBC B. A) PROVIDE A POOL INLET DETAIL-
 SEC. 454.1.6.5.9 FBC P.
  
 14) 2ND REQUEST PL6.11, PL6.15: CLARIFY IF A GUTTER
 DRAIN OR INFINITY DRAIN WILL BE INSTALLED. IT APPEARS
 THAT THE INFINITY DESIGNATION ON PL6.15 IS AN ERROR.
 PLEASE CLARIFY- SEC. 107.2.1 WPB
  
 15) 2ND REQUEST PL6.11: CLARIFY IF PREVAILING WIND
 DIRECTION WAS CONSIDERED BY THE DESIGNER OF RECORD IN
 THE SELECTION OF THE SKIMMER LOCATIONS- SEC.
 454.1.6.5.3.2.2 FBC B.
  
 17) 2ND REQUEST. PL6.30: SHOW THE LOCATION OF THE
 REQUIRED HOSE BIB WITH VACUUM BEAKER IN THE EQUIPMENT
 ROOM- SEC. 454.1.5.9 FBC B.
  
 19) 2ND REQUEST PL6.30: PROVIDE AN ENLARGED
 INSTALLATION AND PIPING DETAIL FOR THE WASTEWATER SUMP
 PUMP AND PIT. PLEASE INCLUDE AN EQUIPMENT SCHEDULE FOR
 THE PUMP- SECS. 1113.1- 1113.1.2 FBC P. PLEASE NOTE THE
 WASTEWATER SHALL BE DECHLORINATED AND DRAIN INTO THE
 STORM SYSTEM- SEC. 90-205 (1) WPB.
  
 20) 2ND REQUEST. PL6.30: SHOW THE EQUIPMENT ROOM DOOR
 IS EQUIPPED WITH A LOCKABLE DOOR OR OTHERWISE PROTECTED
 FROM UNAUTHORIZED ACCESS- 454.1.5.9 FBC B.
  
 21) 2ND REQUEST. PL6.00 & PL6.30: PROVIDE A CLEANING
 SYSTEM FOR THE POOL IN ACCORDANCE WITH SEC.
 454.1.6.5.12 FBC B. PLEASE NOTE A PORTABLE, ROBOTIC OR
 PLUMBED-IN VACUUM CLEANING SYSTEM SHALL BE PROVIDED.
  
 23) 2ND REQUEST. PL6.30: PLEASE SHOW COMPLIANCE WITH
 THE FOLLOWING CODE SECTIONS FROM THE FBC EC:
 C404.9.1 HEATERS. THE ELECTRIC POWER TO ALL HEATERS
 SHALL BE CONTROLLED BY A READILY ACCESSIBLE ON-OFF
 SWITCH THAT IS AN INTEGRAL PART OF THE HEATER, MOUNTED
 ON THE EXTERIOR OF THE HEATER, OR EXTERNAL TO AND
 WITHIN 3 FEET (914 MM) OF THE HEATER. OPERATION OF SUCH
 SWITCH SHALL NOT CHANGE THE SETTING OF THE HEATER
 THERMOSTAT. SUCH SWITCHES SHALL BE IN ADDITION TO A
 CIRCUIT BREAKER FOR THE POWER TO THE HEATER. GAS-FIRED
 HEATERS SHALL NOT BE EQUIPPED WITH CONTINUOUSLY BURNING
 IGNITION PILOTS.
 C404.9.2 TIME SWITCHES. TIME SWITCHES OR OTHER CONTROL
 METHODS THAT CAN AUTOMATICALLY TURN OFF AND ON HEATERS
 AND PUMP MOTORS ACCORDING TO A PRESET SCHEDULE SHALL BE
 INSTALLED FOR HEATERS AND PUMP MOTORS. HEATERS AND PUMP
 MOTORS THAT HAVE BUILT-IN TIME SWITCHES SHALL BE IN
 COMPLIANCE WITH THIS SECTION.
 EXCEPTIONS:
 1. WHERE PUBLIC HEALTH STANDARDS REQUIRE 24-HOUR PUMP
 OPERATION.
 2. PUMPS THAT OPERATE SOLAR- AND WASTE-HEAT-RECOVERY
 POOL HEATING SYSTEMS.
 C404.9.3 COVERS. OUTDOOR HEATED SWIMMING POOLS AND
 OUTDOOR PERMANENT SPAS SHALL BE EQUIPPED WITH A
 VAPOR-RETARDANT COVER ON OR AT THE WATER SURFACE OR A
 LIQUID COVER OR OTHER MEANS PROVEN TO REDUCE HEAT LOSS.
  
 24) SUMMARY OF SEPARATELY PERMITTED ITEMS.
 A) SANITARY FACILITIES.
 B) POOL SHOWER AND HOSE BIBS.
 C) GAS WATER HEATER AND GAS PIPING.
 D) EQUIPMENT ENCLOSURE BUILDING INCLUDING THE
 MECHANICAL AND ELECTRICAL WORK.
 E) PLUMBING FIXTURES IN THE EQUIPMENT ENCLOSURE
 INCLUDING THE HOSE BIB AND SUMP PUMP
 F) POOL FENCE AND GATES.
 G) POOL DECK.
 H) CIVIL ENGINEERING.
  
 25) SUMMARY OF SUBMITTALS OR DEFERRED SUBMITTALS:
 A) POOL LIFT.
 B) MAIN DRAIN ASSEMBLIES AND COVERS.
 C) POOL PUMP.
 D) COLLECTOR TANK.
 E) FILTERS.
 F) SKIMMERS
 G) CHLORINATION EQUIPMENT
  
 NEW COMMENTS.
  
 1) SHEET PL0.20: PLEASE ADD THESE REQUIRED ITEMS ON THE
 PLAN FOR THE POOL BATHROOMS.
 A) DIAPER CHANGING STATIONS- SEC. 454.1.6.1.1 FBC B.
 B) HOSE BIBS IN OR WITHIN 25 FT. OF THE BATHROOMS- SEC.
 454.1.6.1.4
 C) FLOOR DRAINS IN THE BATHROOMS- SEC. 454.1.6.1.3.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-02-04 Cont ID  
Sent By ccole Date 2022-02-04 Time 13:55 Rev Time 0.00
Received By ccole Date 2022-02-01 Time 15:01 Sent To  
Notes
2022-02-04 13:59:151ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22010238
 2/5/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 PLAN REVIEW RESULTS: DENIED.
  
 BEACHSIDE POOL
  
 1) SHEETS PL0.20 & PL6.00: PROVIDE PLUMBING FIXTURE
 CALCULATIONS FOR THE POOL AND SHOW THE LOCATIONS OF THE
 SANITARY FACILITIES- TABLE 454.1.6.1 AND SECS.
 454.1.6.1- 454.6.1.2 FBC B. IF CLAIMING THE EXCEPTION
 UNDER SEC. 454.1.6.1 PLEASE PROVIDE NOTES AND DETAILS
 ON THE PLAN TO VERIFY COMPLIANCE. THE SUBMITTED PLANS
 DO NOT CLEARLY INDICATE THE LOCATIONS OF THE POOL
 BATHROOMS AND WHICH BATHROOMS ARE DESIGNATED FOR USERS
 OF THE POOL, SPAS, AND DECK AREAS. PROVIDE COMPLIANCE
 DETAILS AND INFORMATION AS REQUIRED BY SECS.
 454.1.6.1.1- 454.1.6.1.4 FBC B. PLEASE NOTE THE
 REQUIRED SANITARY FACILITIES AND PLUMBING FIXTURES
 REQUIRED FOR THE POOL AREA (BATHROOM FIXTURES, HOSE
 BIBS, POOL SHOWERS) AND IN THE EQUIPMENT ROOM (HOSE
 BIB, SUMP PUMP AND DRAIN) SHALL BE INSTALLED UNDER
 SEPARATE PERMITS- SECS. 105.1 & 107.2.1 WPB.
  
 2) PL0.20: REFER TO FAC 64 E-9.004 PRINTED BELOW AND
 VERIFY THE IRRIGATION SYSTEM WILL BE INSTALLED IN
 COMPLIANCE-
 64E-9.004: LANDSCAPE IRRIGATION WATER THAT WETS THE WET
 DECK AREA OF THE POOL, THE POOL ITSELF, ENTERS THE
 COLLECTOR TANK, OR WETS AN INTERACTIVE WATER FEATURE
 MUST BE POTABLE WATER FROM A PUBLIC WATER SYSTEM OR
 SHALL MEET THE BACTERIOLOGICAL QUALITY OF POTABLE WATER
 AS EVIDENCED BY ANNUAL LABORATORY ANALYSIS SUBMITTED TO
 THE DEPARTMENT. RECLAIMED WATER MAY NOT BE USED IN
 THESE AREAS. IF RECLAIMED WATER IS USED IN THE VICINITY
 OF THE POOL (INSIDE OF THE POOL FENCE OR WITHIN 100
 FEET OF THE POOL WATER'S EDGE) IT MUST EMPLOY DRIP
 IRRIGATION OR SOAKER HOSES. SIGNS SHALL BE POSTED
 NOTIFYING POOL PATRONS THAT RECLAIMED WATER IS IN USE
 AND IS NOT TO BE CONSUMED.
  
 3) PL0.20, PL0.24: SHOW THE WASTEWATER RECEPTORS AND
 THE PIPING RUNS TO PLACES OF DISPOSAL, OR CONNECTION
 POINTS AT STORM MAINS. PLEASE NOTE THE FOLLOWING
 CONCERNING POOL WASTEWATER:
 WASTEWATER FROM THE POOL AND THE EQUIPMENT SHALL BE
 DECHLORINATED AND DISCHARGED THROUGH AN AIR GAP IN THE
 INTO THE STORM DRAINAGE SYSTEM- SEC. 454.1.6.5.15 &
 SEC. 90-126(5) WPB CODE OF ORDINANCES. THE WASTEWATER
 SHALL NOT DISCHARGE INTO THE SANITARY SYSTEM. PLEASE
 REVIEW WPB BUILDING DEPT. GUIDELINES FOR POOL WATER
 DISPOSAL. THE ENGINEER OF RECORD SHALL SHOW THE
 DECHLORINATION SYSTEM ON THE PLAN AND PROVIDE
 SPECIFICATIONS FOR ALL EQUIPMENT. PLEASE SEE GUIDELINES
 BELOW-
  
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S
 SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 A) THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH
 TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 B) NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 C) WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE
 ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL
 OWNER'S PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 D) DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 E) FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT
 STEPHON HARRIS AT [email protected] OR 561-822-2168.
 F) FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS,
 PLEASE CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 4) PL0.24: SHOW THE POTABLE WATER RUNS FROM THE WATER
 SOURCE TO THE COLLECTOR TANKS AND LOCATIONS OF POTABLE
 WATER BACKFLOW PREVENTERS- SEC. 107.2.1 WPB AND SEC.
 454.1.6.3 FBC B. PLEASE NOTE THAT SEPARATE PERMITS ARE
 REQUIRED FOR THE BACKFLOW PREVENTERS- SEC. 105.1 WPB.
 FL. LICENSED PLUMBING CONTRACTORS SHALL OBTAIN SEPARATE
 PERMITS FOR INSTALLATION OF THE BACKFLOW PREVENTERS IN
 ACCORDANCE WITH SECTION 105.1WPB AND SEC. 90-33 WPB
 CODE OF ORDINANCES. THE DEVICE SHALL BE TESTED AND
 CERTIFIED BY THE WPB UTILITIES DEPARTMENT PRIOR TO
 FINAL INSPECTION BY THE BUILDING DEPARTMENT. PLEASE
 CONTACT THE WPB UTILITIES CENTRAL OPERATIONS DEPT.AT
 561-822-2210 FOR FURTHER INFORMATION.
  
 5) PL0.20: PLEASE PROVIDE AN ENLARGED POOL DECK DRAWING
 SHOWING COMPLIANCE WITH SECS. 454.1.3.1.2- 454.1.3.1.5
 FBC B- DECK SLOPES, UNOBSTRUCTED WIDTHS, SLIP-RESISTANT
 SURFACES FOR THE DECK AND WALKWAYS.
  
 6) PL0.20: SHOW THE LOCATION OF THE REQUIRE HOSE BIB OR
 BIBS WITH VACUUM BREAKERS FOR THE POOL DECK- SEC.
 454.1.3.1.5 FBC B.
  
 7) PL0.24: SHOW THE GAS PIPING RUNS FROM THE GAS SOURCE
 TO THE POOL HEATERS AND ALL OTHER GAS FIRED EQUIPMENT
 OR APPLIANCES. PLEASE PLACE A NOTE TO INDICATE THE GAS
 POOL HEATERS AND GAS PIPING SHALL BE INSTALLED UNDER A
 SEPARATE PERMIT.
  
 8) PL6.00 & PL6.20: SHOW THE POOL DEPTH AT THE POOL
 LIFT LOCATION- SEC. 1009.2.1 WPB, AND AT ALL LEVELS OF
 THE POOL- SEC. 454.1.2.2.4 FBC B.
  
 9) PL0.22 & PL6.00: PLEASE PROVIDE ENLARGED DIMENSIONED
 DETAILS ON THE PLANS AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE POOL LIFT INSTALLATION IN
 COMPLIANCE WITH THE FOLLOWING FBC ACC CODE SECTIONS:
 A) 1009.2.2 SEAT LOCATION.
 IN THE RAISED POSITION, THE CENTERLINE OF THE SEAT
 SHALL BE LOCATED OVER THE DECK AND 16 INCHES MINIMUM
 FROM THE EDGE OF THE POOL. THE DECK SURFACE BETWEEN THE
 CENTERLINE OF THE SEAT AND THE POOL EDGE SHALL HAVE A
 SLOPE NOT STEEPER THAN 1:48.
 B) 1009.2.3 CLEAR DECK SPACE.
 ON THE SIDE OF THE SEAT OPPOSITE THE WATER, A CLEAR
 DECK SPACE SHALL BE PROVIDED PARALLEL WITH THE SEAT.
 THE SPACE SHALL BE 36 INCHES WIDE MINIMUM AND SHALL
 EXTEND FORWARD 48 INCHES MINIMUM FROM A LINE LOCATED 12
 INCHES BEHIND THE REAR EDGE OF THE SEAT. THE CLEAR DECK
 SPACE SHALL HAVE A SLOPE NOT STEEPER THAN 1:48.
 C) 1009.2.4 SEAT HEIGHT.
 THE HEIGHT OF THE LIFT SEAT SHALL BE DESIGNED TO ALLOW
 A STOP AT 16 INCHES (405 MM) MINIMUM TO 19 INCHES
 MAXIMUM MEASURED FROM THE DECK TO THE TOP OF THE SEAT
 SURFACE WHEN IN THE RAISED (LOAD) POSITION.
 D) 1009.2.6 FOOTRESTS AND ARMRESTS.
 FOOTRESTS SHALL BE PROVIDED AND SHALL MOVE WITH THE
 SEAT. IF PROVIDED, THE ARMREST POSITIONED OPPOSITE THE
 WATER SHALL BE REMOVABLE OR SHALL FOLD CLEAR OF THE
 SEAT WHEN THE SEAT IS IN THE RAISED (LOAD) POS
 E) 1009.2.7 OPERATION.
 THE LIFT SHALL BE CAPABLE OF UNASSISTED OPERATION FROM
 BOTH THE DECK AND WATER LEVELS. CONTROLS AND OPERATING
 MECHANISMS SHALL BE UNOBSTRUCTED WHEN THE LIFT IS IN
 USE AND SHALL COMPLY WITH 309.4.
 F) 1009.2.8 SUBMERGED DEPTH.
 THE LIFT SHALL BE DESIGNED SO THAT THE SEAT WILL
 SUBMERGE TO A WATER DEPTH OF 18 INCHES MINIMUM BELOW
 THE STATIONARY WATER LEVEL.
 G) 1009.2.9 LIFTING CAPACITY.
 SINGLE PERSON POOL LIFTS SHALL HAVE A WEIGHT CAPACITY
 OF 300 POUNDS MINIMUM AND BE CAPABLE OF SUSTAINING A
 STATIC LOAD OF AT LEAST ONE AND A HALF TIMES THE RATED
 LOAD.
  
 10) PL6.00 DATA BLOCK: REFER TO SEC. 454.1.1.1 FBC B.
 AND CLARIFY IF THE POOLS FOR THE FACILITY HAVE BEEN
 SIZED TO ACCOMMODATE A TRANSIENT OR NON-TRANSIENT
 BATHING LOAD. PROVIDE NOTES AND CALCULATIONS BASED ON
 THE TOTAL LIVING UNITS OF THE FACILITY.
  
 11) PL6.10: SUBMIT SPECS FOR THE MAIN DRAIN ASSEMBLIES
 AND DRAIN COVERS- SEC. 454.1.6.5.10.2 FBC B.
  
 12) PL6.10: A) PROVIDE A SECTION VIEW OF THE POOL
 GUTTERS SHOWING COMPLIANCE WITH SECS. 454.1.6.5.3.1 &
 454.1.6.5.3.1.1 FBC. THE GUTTERS SHALL BE IDENTIFIED AS
 EITHER RECESSED OR OPEN TYPE. B) SHOW THE DRAIN
 SPACINGS ON THE PLAN OR PROVIDE A NOTE TO INDICATE
 SPACING NOT TO EXCEED 10FT. C) CONCERNING PERIMETER
 OVERFLOW GUTTERS: THE LIP OF THE GUTTER SHALL BE
 UNIFORMLY LEVEL WITH A MAXIMUM TOLERANCE OF 1/4 INCH
 BETWEEN THE HIGH AND LOW AREAS. THE BOTTOM OF THE
 GUTTER SHALL BE LEVEL OR SLOPE TO THE DRAINS.
  
 13) PL6.10: SHOW THE SPACING MEASUREMENTS BETWEEN THE
 WALL INLETS IN COMPLIANCE WITH SEC. 454.1.6.5.9.1 FBC
 B. A) PROVIDE A POOL INLET DETAIL- SEC. 454.1.6.5.9 FBC
 P.
  
 14) PL6.11, PL6.15, PL6.21, & PL6.30: CLARIFY IF A
 GUTTER DRAIN OR INFINITY DRAIN WILL BE INSTALLED. IT
 APPEARS THAT THE INFINITY DESIGNATION IS AN ERROR.
 PLEASE CLARIFY- SEC. 107.2.1 WPB
  
 15) PL6.11: CLARIFY IF PREVAILING WIND DIRECTION WAS
 CONSIDERED BY THE DESIGNER OF RECORD IN THE SELECTION
 OF THE SKIMMER LOCATIONS- SEC. 454.1.6.5.3.2.2 FBC B.
  
 16) PL6.00 & PL6.30: SUBMIT MANUFACTURER'S SPECS FOR
 THE PUMP AND PROVIDE THE PUMP CURVE IN COMPLIANCE WITH
 SEC. 454.1.6.5.4 FBC B.
  
 17) PL6.30: SHOW THE LOCATION OF THE REQUIRED HOSE BIB
 WITH VACUUM BEAKER IN THE EQUIPMENT ROOM- SEC.
 454.1.5.9 FBC B.
  
 18) PL6.30 PLEASE SHOW THE LOCATIONS OF ITEMS- 4, 5, 6,
 7, 11, 13 & 14 IN THE LAYOUT PLAN- SEC. 107.2.1 WPB.
  
 19) PL6.30: PROVIDE AN ENLARGED INSTALLATION AND PIPING
 DETAIL FOR THE WASTEWATER SUMP PUMP AND PIT. PLEASE
 INCLUDE AN EQUIPMENT SCHEDULE FOR THE PUMP- SECS.
 1113.1- 1113.1.2 FBC P. REFER TO COMMENT #3 CONCERNING
 WASTEWATER DISPOSAL AND SHOW COMPLIANCE.
  
 20) PL6.30: SHOW THE EQUIPMENT ROOM DOOR IS EQUIPPED
 WITH A LOCKABLE DOOR OR OTHERWISE PROTECTED FROM
 UNAUTHORIZED ACCESS- 454.1.5.9 FBC B.
  
 21) PL6.00 & PL6.30: PROVIDE A CLEANING SYSTEM FOR THE
 POOL IN ACCORDANCE WITH SEC. 454.1.6.5.12 FBC B. PLEASE
 NOTE A PORTABLE, ROBOTIC OR PLUMBED-IN VACUUM CLEANING
 SYSTEM SHALL BE PROVIDED.
  
 22) PL6.30: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 RECIRCULATION AND TREATMENT EQUIPMENT INCLUDING THE
 FILTERS, CHLORINATOR, SKIMMERS AND FEEDERS SHOWING THE
 EQUIPMENT CONFORMS WITH REQUIRED STANDARDS NSF/ANSI
 STANDARD 50, CIRCULATION SYSTEM COMPONENTS AND RELATED
 MATERIALS FOR SWIMMING POOL, SPAS/HOT TUBS, DATED APRIL
 2007- SECTION 454.1.6.5.1 FBC B.
  
 23) PL6.30: PLEASE SHOW COMPLIANCE WITH THE FOLLOWING
 CODE SECTIONS FROM THE FBC EC:
 C404.9.1 HEATERS. THE ELECTRIC POWER TO ALL HEATERS
 SHALL BE CONTROLLED BY A READILY ACCESSIBLE ON-OFF
 SWITCH THAT IS AN INTEGRAL PART OF THE HEATER, MOUNTED
 ON THE EXTERIOR OF THE HEATER, OR EXTERNAL TO AND
 WITHIN 3 FEET (914 MM) OF THE HEATER. OPERATION OF SUCH
 SWITCH SHALL NOT CHANGE THE SETTING OF THE HEATER
 THERMOSTAT. SUCH SWITCHES SHALL BE IN ADDITION TO A
 CIRCUIT BREAKER FOR THE POWER TO THE HEATER. GAS-FIRED
 HEATERS SHALL NOT BE EQUIPPED WITH CONTINUOUSLY BURNING
 IGNITION PILOTS.
 C404.9.2 TIME SWITCHES. TIME SWITCHES OR OTHER CONTROL
 METHODS THAT CAN AUTOMATICALLY TURN OFF AND ON HEATERS
 AND PUMP MOTORS ACCORDING TO A PRESET SCHEDULE SHALL BE
 INSTALLED FOR HEATERS AND PUMP MOTORS. HEATERS AND PUMP
 MOTORS THAT HAVE BUILT-IN TIME SWITCHES SHALL BE IN
 COMPLIANCE WITH THIS SECTION.
 EXCEPTIONS:
 1. WHERE PUBLIC HEALTH STANDARDS REQUIRE 24-HOUR PUMP
 OPERATION.
 2. PUMPS THAT OPERATE SOLAR- AND WASTE-HEAT-RECOVERY
 POOL HEATING SYSTEMS.
 C404.9.3 COVERS. OUTDOOR HEATED SWIMMING POOLS AND
 OUTDOOR PERMANENT SPAS SHALL BE EQUIPPED WITH A
 VAPOR-RETARDANT COVER ON OR AT THE WATER SURFACE OR A
 LIQUID COVER OR OTHER MEANS PROVEN TO REDUCE HEAT LOSS.
  
 24) SUMMARY OF SEPARATE PERMITS REQUIRED:
 A) POTABLE WATER BACKFLOW PREVENTERS.
 B) SANITARY FACILITIES.
 C) POOL SHOWER AND HOSE BIBS.
 D) GAS WATER HEATER AND GAS PIPING.
 E) EQUIPMENT ENCLOSURE BUILDING INCLUDING THE
 MECHANICAL AND ELECTRICAL WORK.
 F) PLUMBING FIXTURES IN THE EQUIPMENT ENCLOSURE
 INCLUDING THE HOSE BIB AND SUMP PUMP
 G) POOL FENCE AND GATES.
 H) POOL DECK.
 I) CIVIL ENGINEERING.
  
 25) SUMMARY OF SUBMITTALS OR DEFERRED SUBMITTALS:
 A) POOL LIFT.
 B) MAIN DRAIN ASSEMBLIES AND COVERS.
 C) POOL PUMP.
 D) COLLECTOR TANK.
 E) FILTERS.
 F) SKIMMERS
 G) CHLORINATION EQUIPMENT
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2022-02-23 Cont ID  
Sent By shill Date 2022-02-23 Time 16:59 Rev Time 0.00
Received By shill Date 2022-02-23 Time 16:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-06-09 Cont ID  
Sent By rmcphers Date 2023-06-09 Time 11:49 Rev Time 0.00
Received By rmcphers Date 2023-06-09 Time 11:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-04-05 Cont ID  
Sent By rmcdouga Date 2023-04-05 Time 08:53 Rev Time 0.00
Received By rmcdouga Date 2023-04-05 Time 08:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-11-21 Cont ID  
Sent By ccole Date 2022-11-21 Time 12:16 Rev Time 0.00
Received By ccole Date 2022-11-21 Time 12:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-03-24 Cont ID  
Sent By rmcdouga Date 2022-03-24 Time 17:14 Rev Time 0.00
Received By rmcdouga Date 2022-03-24 Time 17:14 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-05-19 Cont ID  
Sent By eschneid Date 2022-05-19 Time 11:17 Rev Time 0.00
Received By jroach Date 2022-05-19 Time 11:16 Sent To  
Notes
2022-05-19 11:18:56THIS REVIEW IS FOR THE BEACH CLUB POOL ONLY AND HAS
 BEEN PASSED SUBJECT TO THE FOLLOWING PROVISOS:
  
 1. ALL DEVELOPMENT WITHIN THE MARINA COMMERCIAL MARINE
 PLANNED DEVELOPMENT (CMPD) SHALL BE SUBJECT TO ALL
 DEVELOPMENT ORDER CONDITIONS, DESIGN GUIDELINES, ETC.,
 AS OUTLINED IN RESOLUTION NO. 66-22, AND AS MAY BE
 AMENDED. ALL CONDITIONS OF APPROVAL IMPOSED BY THE
 DEVELOPMENT ORDER SHALL BE ADDRESSED WITHIN THE
 APPROPRIATE SPECIFIED TIMEFRAMES.
 _______________________________________________________
 _____________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 _______________________________________________________
 _____________
  