Plan Review Details - Permit 22010237
Plan Review Stops For Permit 22010237
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-04-05 Cont ID  
Sent By rmcdouga Date 2023-04-05 Time 11:10 Rev Time 0.00
Received By rmcdouga Date 2023-04-05 Time 11:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-12-16 Cont ID  
Sent By rmcdouga Date 2022-12-16 Time 10:24 Rev Time 0.00
Received By rmcdouga Date 2022-12-16 Time 10:08 Sent To  
Notes
2022-12-16 10:15:29PLAN
 REVIEW COMMENTS FOR COURTYARD POOL AND NORTH & SOUTH
 SPAS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) RESOLVED.
  
 2) RESOLVED.
  
 3) THE POOL IS LOCATED IN A SPECIAL FLOOD HAZARD AREA.
 SHOW HOW THE POOL AND POOL EQUIPMENT WILL COMPLY WITH
 FBC 1612.4.2.
  
 4) RESOLVED.
  
 5) RESOLVED.
  
 6) SHOW HOW THE POOL EQUIPMENT IS ANCHORED TO RESIST
 WIND LOADS. FBC 1601.1 AND 1603.1.4
  
 7) PROVIDE STRUCTURAL DETAILS FOR THE COURTYARD POOL
 AND THE TWO SPA POOLS. FBC AMENDMENTS 107.2.1
  
 8) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-03-31 Cont ID  
Sent By rmcdouga Date 2022-03-31 Time 14:12 Rev Time 0.00
Received By rmcdouga Date 2022-03-31 Time 14:12 Sent To  
Notes
2022-03-31 08:42:56PLAN
 REVIEW COMMENTS FOR COURTYARD POOL AND NORTH & SOUTH
 SPAS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHOW THAT THE SANITARY FACILITIES FOR THE POOL MEET
 THE REQUIREMENTS OF FBC 454.1.6.1.
  
 2) REVISE THE POOL RULES SIGN ON SHEET 011-PL0.22 TO
 REFLECT THE 2020 FBC 454.1.2.3.5 REQUIREMENTS FOR
 MAXIMUM POOL DEPTH AND ALLOWING COMMERCIALLY BOTTLED
 WATER ON THE WET DECK.
  
 3) THE POOL IS LOCATED IN A SPECIAL FLOOD HAZARD AREA.
 SHOW HOW THE POOL AND POOL EQUIPMENT WILL COMPLY WITH
 FBC 1612.4.2.
  
 4) THE LOCATION MAP AND SITE ADDRESS ON THE COVER SHEET
 IS NOT FOR THIS PROJECT. PLEASE CORRECT. FBC 107.2.1
  
 5) THIS IS AN AREA OF QUESTIONABLE SOILS. SUBMIT A
 GEOTECHNICAL REPORT FOR THE POOL. FBC 1603.1 AND
 1603.1.6
  
 6) SHOW HOW THE POOL EQUIPMENT IS ANCHORED TO RESIST
 WIND LOADS. FBC 1601.1 AND 1603.1.4
  
 7) PROVIDE STRUCTURAL DETAILS FOR THE COURTYARD POOL
 AND THE TWO SPA POOLS. FBC AMENDMENTS 107.2.1
  
 8) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
 9) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2023-03-31 Cont ID  
Sent By jleahy Date 2023-03-30 Time 06:21 Rev Time 0.00
Received By mpeterso Date 2023-03-31 Time 16:18 Sent To  
Notes
2023-03-31 16:19:33CUSTOMER EMAILED DIRECTIONS TO APPROPRIATE PLANS. MP

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2023-03-22 Cont ID  
Sent By jleahy Date 2023-03-22 Time 12:37 Rev Time 0.00
Received By jleahy Date 2023-03-22 Time 12:37 Sent To  
Notes
2023-03-22 12:38:15SAME AS BEFORE. JLEAHY

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-12-07 Cont ID  
Sent By jleahy Date 2022-12-07 Time 11:47 Rev Time 0.00
Received By jleahy Date 2022-12-07 Time 11:47 Sent To  
Notes
2022-12-07 11:47:52SEE COMMENTS FROM 2/9/22 JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-02-09 Cont ID  
Sent By jleahy Date 2022-02-09 Time 16:18 Rev Time 0.00
Received By jleahy Date 2022-02-09 Time 15:47 Sent To  
Notes
2022-02-10 08:04:00ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLEASE SUBMIT A COST BREAKDOWN OF THE MATERIALS AND
 LABOR FOR THESE WATER FEATURES. (320K)
  
 4 POOLS, 2 SPAS, 1 WATER WALL, AND 1 FOUNTAIN
  
 PLEASE SHOW THE LOCATION WHERE POWER FOR EQUIPMENT
 COMES FROM FOR EACH FEATURE.
  
 SHOW WIRE SIZES FOR THE EQUIPMENT ON A SINGLE LINE
 RISER FOR POOL EQUIPMENT.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By rmcdouga Date 2023-04-05 Time 11:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-16 Cont ID  
Sent By rmcdouga Date 2022-12-16 Time 10:24 Rev Time 0.00
Received By rmcdouga Date 2022-11-18 Time 12:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-19 Cont ID  
Sent By cpuell Date 2022-05-19 Time 13:11 Rev Time 0.00
Received By cpuell Date 2022-01-25 Time 10:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2022-02-07 Cont ID  
Sent By medwards Date 2022-02-07 Time 08:02 Rev Time 0.00
Received By medwards Date 2022-02-07 Time 08:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-03-20 Cont ID  
Sent By ccole Date 2023-03-20 Time 14:00 Rev Time 0.00
Received By ccole Date 2023-03-20 Time 12:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-12-01 Cont ID  
Sent By ccole Date 2022-12-01 Time 15:57 Rev Time 0.00
Received By ccole Date 2022-11-30 Time 07:58 Sent To  
Notes
2022-12-01 15:58:382ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22010237
 12/1/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 PLAN REVIEW RESULTS: DENIED.
  
 COURTYARD POOL REVIEW COMMENTS.
  
 1) SHEET PL0.20 COURTYARD POOL, NORTH & SOUTH SPA
 BATHROOMS.
  
 A) REFER TO SEC. 403.6.1 FBC P: POOL BATHROOMS FOR
 FEMALE USE SHALL HAVE A RATIO OF THREE TO TWO WATER
 CLOSETS PROVIDED AS THE COMBINED TOTAL OF WATER CLOSETS
 AND URINALS PROVIDED FOR MALE USE.
  
 B) PROVIDE A DETAIL OR NOTE TO CONFIRM EACH BATHROOM
 SHALL CONTAIN A DIAPER CHANGING STATION- SEC.
 454.1.6.1.1.
  
 C) PROVIDE A DETAIL OR NOTE TO CONFIRM EACH BATHROOM
 SHALL CONTAIN A FLOOR DRAIN- SEC. 454.1.6.1.3.
  
 D) SHOW THE LOCATIONS OF REQUIRED HOSE BIBS WITHIN 25
 FT. OF EACH BATHROOM AND NOTE THAT EACH WILL BE
 EQUIPPED WITH A VACUUM BREAKER- SEC. 454.1.6.1.4.
  
 E) CONFIRM WITH DETAILS AND/OR NOTES THAT THE FLOOR
 INSIDE THE HALLWAY LEADING TO THE POOL BATHROOMS AND
 THE POOL BATHROOM FLOORS ARE CONSTRUCTED OF CONCRETE OR
 OTHER NON-ABSORBENT MATERIALS AND HAVE A SMOOTH, SLIP
 RESISTANT FINISH. INDICATE THE FLOORS SLOPE TO THE
 FLOOR DRAINS IN THE BATHROOMS.
  
 2) 2ND REQUEST. PL0.20: SHOW THE LOCATION OF THE
 REQUIRE HOSE BIB OR BIBS WITH VACUUM BREAKERS FOR THE
 POOL DECK- SEC. 454.1.3.1.5 FBC B.
  
 3) 2ND REQUEST. PL0.24 &PL0.26: SHOW THE POTABLE WATER
 RUNS FROM THE WATER SOURCE TO THE COLLECTOR TANKS AND
 LOCATIONS OF POTABLE WATER BACKFLOW PREVENTERS- SEC.
 107.2.1 WPB AND SEC. 454.1.6.3 FBC B
  
 4) 2ND REQUEST. PL0.24 &PL0.26: SHOW THE GAS PIPING
 RUNS FROM THE GAS SOURCE TO THE POOL HEATERS AND ALL
 OTHER GAS FIRED EQUIPMENT OR APPLIANCES. PLEASE PLACE A
 NOTE TO INDICATE THE GAS POOL HEATERS AND GAS PIPING
 SHALL BE INSTALLED UNDER A SEPARATE PERMIT.
  
 5) PL3.21: THE REQUIRED HYDROSTATIC RELIEF VALVE (ITEM
 #7) IS NOT SHOWN IN THE DETAIL- SEC. 454.1.6.5.10.4 FBC
 B.
  
 6) 2ND REQUEST- PL3.11: SHOW GUTTER DRAIN SPACING
 DIMENSIONS- SEC. 454.1.6.5.3.1 FBC B. PLEASE NOTE THE
 DEPTH MARKING OF 3'0" AT THE SUNSHELF ON PL3.11 &
 PL3.10 NEEDS TO BE CHANGED TO SHOW 8".
  
 7) DEFERRED SUBMITTALS: ALL POOL AND SPA RECIRCULATION
 EQUIPMENT SHALL BE DEFERRED SUBMITTALS WHICH SHALL BE
 ONSITE AT TIME OF INSPECTION- SEC. 107.3.4.1 WPB.. EACH
 SUBMITTAL SHALL BEAR THE APPROVAL STAMP OF THE ENGINEER
 OF RECORD. THE SUBMITTALS SHALL INCLUDE BUT NOT BE
 LIMITED TO:
  
 A) PUMPS.
  
 B) MAIN DRAIN ASSEMBLIES INCLUDING FRAMES, COVERS, AND
 SUMPS.
  
 C) COLLECTOR TANKS
  
 D) FILTERS
  
 E) SKIMMERS
  
 F) EQUALIZER FITTINGS
  
 G) HYDROSTATIC RELIEF VALVES
  
 H) CHLORINATION AND DECHLORINATION EQUIPMENT
  
 I) ADA LIFTS
  
 J) EMERGENCY SHOWER AND EYE WASH STATIONS
  
  
 NORTH AND SOUTH SPA REVIEW COMMENTS.
  
 1) SHEET PL0.20 COURTYARD POOL, NORTH & SOUTH SPA
 BATHROOMS: IN RESPONSE TO 1ST REVIEW COMMENT #1, AN
 UPDATED SHEET PL0.20 HAS BEEN PROVIDED WHICH SHOWS THE
 LOCATIONS OF THE POOL AND SPA BATHROOMS IN AN ADJACENT
 BUILDING WITH A TRAVEL DISTANCE EXCEEDING THE ALLOWABLE
 50 FT. PER SEC. 454.1.6.1.2 FBC B. THE LOCATIONS ARE
 LIMITED TO 50 FT. BECAUSE THE RESTROOM DOORS DO NOT
 OPEN DIRECTLY TO THE OUTSIDE. DIRECTIONAL SIGNS WOULD
 ALSO BE REQUIRED TO BE POSTED WITH DIRECTIONS LEGIBLE
 FROM ANY PORTION OF THE POOL DECK.
  
 A) PROVIDE A DETAIL OR NOTE TO CONFIRM EACH BATHROOM
 SHALL CONTAIN A DIAPER CHANGING STATION- SEC.
 454.1.6.1.1.
  
 B) PROVIDE A DETAIL OR NOTE TO CONFIRM EACH BATHROOM
 SHALL CONTAIN A FLOOR DRAIN- SEC. 454.1.6.1.3.
  
 C) SHOW THE LOCATIONS OF REQUIRED HOSE BIBS WITHIN 25
 FT. OF EACH BATHROOM AND NOTE THAT EACH WILL BE
 EQUIPPED WITH A VACUUM BREAKER- SEC. 454.1.6.1.4.
  
 D) CONFIRM WITH DETAILS AND/OR NOTES THAT THE FLOOR
 INSIDE THE HALLWAY LEADING TO THE POOL BATHROOMS AND
 THE POOL BATHROOM FLOORS ARE CONSTRUCTED OF CONCRETE OR
 OTHER NON-ABSORBENT MATERIALS AND HAVE A SMOOTH, SLIP
 RESISTANT FINISH. INDICATE THE FLOORS SLOPE TO THE
 FLOOR DRAINS IN THE BATHROOMS
  
 2) 2ND REQUEST. PL0.20: SHOW THE LOCATION OF THE
 REQUIRE HOSE BIB OR BIBS WITH VACUUM BREAKERS FOR THE
 POOL AND SPA DECK- SEC. 454.1.3.1.5 FBC B.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-02-03 Cont ID  
Sent By ccole Date 2022-02-03 Time 16:49 Rev Time 0.00
Received By ccole Date 2022-02-02 Time 13:49 Sent To  
Notes
2022-02-03 16:49:331ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22010237
 2/3/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 PLAN REVIEW RESULTS: DENIED.
  
 COURTYARD POOL REVIEW COMMENTS.
  
 1) SHEETS PL0.20 & PL3.00: PROVIDE PLUMBING FIXTURE
 CALCULATIONS FOR THE POOL AND SHOW THE LOCATIONS OF THE
 SANITARY FACILITIES- TABLE 454.1.6.1 AND SECS.
 454.1.6.1- 454.6.1.2 FBC B. IF CLAIMING THE EXCEPTION
 UNDER SEC. 454.1.6.1 PLEASE PROVIDE NOTES AND DETAILS
 ON THE PLAN TO VERIFY COMPLIANCE. THE SUBMITTED PLANS
 DO NOT CLEARLY INDICATE THE LOCATIONS OF THE POOL
 BATHROOMS AND WHICH BATHROOMS ARE DESIGNATED FOR USERS
 OF THE POOL, SPAS, AND DECK AREAS. PROVIDE COMPLIANCE
 DETAILS AND INFORMATION AS REQUIRED BY SECS.
 454.1.6.1.1- 454.1.6.1.4 FBC B. PLEASE NOTE THE
 REQUIRED SANITARY FACILITIES AND PLUMBING FIXTURES
 REQUIRED FOR THE POOL AREA (BATHROOM FIXTURES, HOSE
 BIBS, POOL SHOWERS ) AND IN THE EQUIPMENT ROOM- (SUMP
 PUMP AND EMERGENCY SHOWER AND EYEWASH ETC.) SHALL BE
 INSTALLED UNDER SEPARATE PERMITS- SECS. 105.1 & 107.2.1
 WPB.
  
 2) PL0.20: REFER TO FAC 64 E-9.004 PRINTED BELOW AND
 VERIFY THE IRRIGATION SYSTEM WILL BE INSTALLED IN
 COMPLIANCE-
 64E-9.004: LANDSCAPE IRRIGATION WATER THAT WETS THE WET
 DECK AREA OF THE POOL, THE POOL ITSELF, ENTERS THE
 COLLECTOR TANK, OR WETS AN INTERACTIVE WATER FEATURE
 MUST BE POTABLE WATER FROM A PUBLIC WATER SYSTEM OR
 SHALL MEET THE BACTERIOLOGICAL QUALITY OF POTABLE WATER
 AS EVIDENCED BY ANNUAL LABORATORY ANALYSIS SUBMITTED TO
 THE DEPARTMENT. RECLAIMED WATER MAY NOT BE USED IN
 THESE AREAS. IF RECLAIMED WATER IS USED IN THE VICINITY
 OF THE POOL (INSIDE OF THE POOL FENCE OR WITHIN 100
 FEET OF THE POOL WATER'S EDGE) IT MUST EMPLOY DRIP
 IRRIGATION OR SOAKER HOSES. SIGNS SHALL BE POSTED
 NOTIFYING POOL PATRONS THAT RECLAIMED WATER IS IN USE
 AND IS NOT TO BE CONSUMED.
  
 3) PL0.20, PL0.24 & PL0.26: SHOW THE WASTEWATER
 RECEPTORS AND THE PIPING RUNS TO PLACES OF DISPOSAL, OR
 CONNECTION POINTS AT STORM MAINS. PLEASE NOTE THE
 FOLLOWING CONCERNING POOL WASTEWATER:
 WASTEWATER FROM THE POOL AND THE POOL EQUIPMENT SHALL
 BE DECHLORINATED AND DISCHARGED THROUGH AN AIR GAP IN
 THE INTO THE STORM DRAINAGE SYSTEM- SEC. 454.1.6.5.15 &
 SEC. 90-126(5) WPB CODE OF ORDINANCES. THE WASTEWATER
 SHALL NOT DISCHARGE INTO THE SANITARY SYSTEM. PLEASE
 REVIEW WPB BUILDING DEPT. GUIDELINES FOR POOL WATER
 DISPOSAL. THE ENGINEER OF RECORD SHALL SHOW THE
 DECHLORINATION SYSTEM ON THE PLAN AND PROVIDE
 SPECIFICATIONS FOR ALL EQUIPMENT. PLEASE SEE GUIDELINES
 BELOW-
  
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S
 SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 A) THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH
 TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 B) NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 C) WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE
 ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL
 OWNER'S PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 D) DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 E) FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT
 STEPHON HARRIS AT [email protected] OR 561-822-2168.
 F) FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS,
 PLEASE CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 4) PL0.24 &PL0.26: SHOW THE POTABLE WATER RUNS FROM THE
 WATER SOURCE TO THE COLLECTOR TANKS AND LOCATIONS OF
 POTABLE WATER BACKFLOW PREVENTERS- SEC. 107.2.1 WPB AND
 SEC. 454.1.6.3 FBC B. PLEASE NOTE THAT SEPARATE PERMITS
 ARE REQUIRED FOR THE BACKFLOW PREVENTERS- SEC. 105.1
 WPB. FL. LICENSED PLUMBING CONTRACTORS SHALL OBTAIN
 SEPARATE PERMITS FOR INSTALLATION OF THE BACKFLOW
 PREVENTERS IN ACCORDANCE WITH SECTION 105.1WPB AND SEC.
 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE
 TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 5) PL0.20: PLEASE PROVIDE AN ENLARGED POOL DECK DRAWING
 SHOWING COMPLIANCE WITH SECS. 454.1.3.1.2- 454.1.3.1.5
 FBC B- DECK SLOPES, UNOBSTRUCTED WIDTHS, SLIP-RESISTANT
 SURFACES FOR THE DECK AND WALKWAYS.
  
 6) PL0.20: SHOW THE LOCATION OF THE REQUIRE HOSE BIB OR
 BIBS WITH VACUUM BREAKERS FOR THE POOL DECK- SEC.
 454.1.3.1.5 FBC B.
  
 7) PL0.24 &PL0.26: SHOW THE GAS PIPING RUNS FROM THE
 GAS SOURCE TO THE POOL HEATERS AND ALL OTHER GAS FIRED
 EQUIPMENT OR APPLIANCES. PLEASE PLACE A NOTE TO
 INDICATE THE GAS POOL HEATERS AND GAS PIPING SHALL BE
 INSTALLED UNDER A SEPARATE PERMIT.
  
 8) PL0.20 & PL0.24: PLEASE SHOW THE GRAVITY PIPING RUNS
 FROM THE POOL DRAINS TO THE COLLECTOR TANK AND THE
 SUCTION DRAIN LINES FROM THE TANK TO THE PUMP- SEC.
 454.1.6.5.3 & 454.1.6.5.10.5 FBC B. PROVIDE A
 CROSS-SECTION VIEW OF THE PIPE RUNS SHOWING THE SLOPES.
  
 9) PL3.00 & PL3.05: SHOW THE POOL DEPTH AT THE POOL
 LIFT LOCATION- SEC. 1009.2.1 WPB, AND AT ALL LEVELS OF
 THE POOL- SEC. 454.1.2.2.4 FBC B.
  
 10) PL0.22 & PL3.00: PLEASE PROVIDE ENLARGED
 DIMENSIONED DETAILS ON THE PLANS AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE POOL LIFT
 INSTALLATION IN COMPLIANCE WITH THE FOLLOWING FBC ACC
 CODE SECTIONS:
 A) 1009.2.2 SEAT LOCATION.
 IN THE RAISED POSITION, THE CENTERLINE OF THE SEAT
 SHALL BE LOCATED OVER THE DECK AND 16 INCHES MINIMUM
 FROM THE EDGE OF THE POOL. THE DECK SURFACE BETWEEN THE
 CENTERLINE OF THE SEAT AND THE POOL EDGE SHALL HAVE A
 SLOPE NOT STEEPER THAN 1:48.
 B) 1009.2.3 CLEAR DECK SPACE.
 ON THE SIDE OF THE SEAT OPPOSITE THE WATER, A CLEAR
 DECK SPACE SHALL BE PROVIDED PARALLEL WITH THE SEAT.
 THE SPACE SHALL BE 36 INCHES WIDE MINIMUM AND SHALL
 EXTEND FORWARD 48 INCHES MINIMUM FROM A LINE LOCATED 12
 INCHES BEHIND THE REAR EDGE OF THE SEAT. THE CLEAR DECK
 SPACE SHALL HAVE A SLOPE NOT STEEPER THAN 1:48.
 C) 1009.2.4 SEAT HEIGHT.
 THE HEIGHT OF THE LIFT SEAT SHALL BE DESIGNED TO ALLOW
 A STOP AT 16 INCHES (405 MM) MINIMUM TO 19 INCHES
 MAXIMUM MEASURED FROM THE DECK TO THE TOP OF THE SEAT
 SURFACE WHEN IN THE RAISED (LOAD) POSITION.
 D) 1009.2.6 FOOTRESTS AND ARMRESTS.
 FOOTRESTS SHALL BE PROVIDED AND SHALL MOVE WITH THE
 SEAT. IF PROVIDED, THE ARMREST POSITIONED OPPOSITE THE
 WATER SHALL BE REMOVABLE OR SHALL FOLD CLEAR OF THE
 SEAT WHEN THE SEAT IS IN THE RAISED (LOAD) POS
 E) 1009.2.7 OPERATION.
 THE LIFT SHALL BE CAPABLE OF UNASSISTED OPERATION FROM
 BOTH THE DECK AND WATER LEVELS. CONTROLS AND OPERATING
 MECHANISMS SHALL BE UNOBSTRUCTED WHEN THE LIFT IS IN
 USE AND SHALL COMPLY WITH 309.4.
 F) 1009.2.8 SUBMERGED DEPTH.
 THE LIFT SHALL BE DESIGNED SO THAT THE SEAT WILL
 SUBMERGE TO A WATER DEPTH OF 18 INCHES MINIMUM BELOW
 THE STATIONARY WATER LEVEL.
 G) 1009.2.9 LIFTING CAPACITY.
 SINGLE PERSON POOL LIFTS SHALL HAVE A WEIGHT CAPACITY
 OF 300 POUNDS MINIMUM AND BE CAPABLE OF SUSTAINING A
 STATIC LOAD OF AT LEAST ONE AND A HALF TIMES THE RATED
 LOAD.
  
 11) PL3.00 DATA BLOCK: REFER TO SEC. 454.1.1.1 FBC B.
 AND CLARIFY IF THE POOLS FOR THE FACILITY HAVE BEEN
 SIZED TO ACCOMODATE A TRANIENT OR NON-TRANSIENT BATHING
 LOAD. PROVIDE NOTES AND CALCULATIONS BASED ON THE TOTAL
 LIVING UNITS OF THE FACILTIY.
  
 12) PL3.00, PL3.05, PL3.10: SHOW THE MAIN DRAINS ARE
 LOCATED AT THE DEEPEST POINT OF THE POOL- SEC.
 454.1.6.5.10 FBC B. PLEASE NOTE IF THE WIDTH OF THE
 DEEPEST PORTION OF THE POOL IS GREATER THAN 30 FT THE
 DRAINS SHALL BE EQUALLY SPACED FROM THE POOL SIDE WALLS
 AND EACH OTHER- SEC. 454.1.6.5.10.3
  
 13) PL3.00 & PL3.2.1: SUBMIT SPECS FOR THE MAIN DRAIN
 ASSEMBLIES AND DRAIN COVERS- SEC. 454.1.6.5.10.2 FBC B.
  
 14) PL3.01: PLEASE CORRECT THE DEPTH MARKINGS TO BE
 CONSISTENT WITH THE DEPTHS OF THE POOL AND THE SUN
 SHELF- SECS. 454.1.2.3 & 454.1.2.8 FBC B. A) SHOW THE
 ACTUAL DEPTH OF THE SUN SHELF MEASURED FROM THE COPING
 AND THE SHELF FLOOR, AND CLARIFY OF AN OPEN-TYPE GUTTER
 SYSTEM WILL BE INSTALLED AND USED AS A STEP- SEC.
 454.1.2.3.8 FBC B.
  
 15) PL3.11: A) PROVIDE A SECTION VIEW OF THE POOL
 GUTTERS AND SUN SHELF GUTTERS SHOWING COMPLIANCE WITH
 SECS. 454.1.6.5.3.1 & 454.1.6.5.3.1.1 FBC. THE GUTTERS
 SHALL BE IDENTIFIED AS EITHER RECESSED OR OPEN TYPE. B)
 SHOW THE DRAIN SPACINGS ON THE PLAN OR PROVIDE A NOTE
 TO INDICATE SPACING NOT TO EXCEED 10FT. C) CONCERNING
 PERIMETER OVERFLOW GUTTERS: THE LIP OF THE GUTTER SHALL
 BE UNIFORMLY LEVEL WITH A MAXIMUM TOLERANCE OF 1/4 INCH
 BETWEEN THE HIGH AND LOW AREAS. THE BOTTOM OF THE
 GUTTER SHALL BE LEVEL OR SLOPE TO THE DRAINS.
  
 16) PL3.11: SHOW THE SPACING MEASUREMENTS BETWEEN THE
 FLOOR INLETS AND FROM ADJACENT WALLS IN COMPLIANCE WITH
 SEC. 454.1.6.5.9.4. A) PROVIDE A POOL INLET DETAIL-
 SEC. 454.1.6.5.9.5 FBC P.
  
 17) PL3.11 & PL3.32: PLEASE MATCH THE COLLECTOR TANK
 DETAIL DRAIN AND SUCTION PIPE SIZES SHOWN ON THE DETAIL
 WITH THE SIZES SHOWN ON THE PLAN- SEC. 107.2.1 WPB. A)
 SHOW THE LOCATION OF THE TANK IS IN A LOCKABLE
 ENCLOSURE OR OTHERWISE PROTECTED FROM UNAUTHORIZED
 ACCESS (LOCKABLE LID?)- SEC. 454.1.5.1 FBC B. SHOW
 MEANS OF ACCESS FOR CLEANING, SERVICE AND INSPECTION-
 454.1.5.5. PLEASE SUBMIT A SPEC SHEET FOR THE TANK.
  
 18) PL3.00, PL3.15, PL3.30: SUBMIT MANUFACTURER'S SPECS
 FOR THE PUMP AND PROVIDE THE PUMP CURVE IN COMPLIANCE
 WITH SEC. 454.1.6.5.4 FBC B.
  
 19) PL3.30: SHOW THE LOCATION OF THE REQUIRED HOSE BIB
 WITH VACUUM BEAKER IN THE EQUIPMENT ROOM- SEC.
 454.1.5.9 FBC B.
  
 20) PL3.30: THE SAND FILTERS ARE IDENTIFIED AS ITEM #2
 IN THE SCHEDULE BUT ARE LABELED AS COLLECTOR TANK ITEM
 #3) IN THE LAYOUT PLAN. PLEASE NOTE SHEET PL0.20 SHOWS
 THE TANK CLOSE TO THE POOL DECK AND NOT IN THE
 ENCLOSURE- SEC. 107.2.1 WPB.
  
 21) PL3.30: SHOW THE LOCATION OF THE EMERGENCY SHOWER
 AND EYEWASH (ITEM #11) IN THE LAYOUT PLAN- SEC. 107.2.1
 WPB.
  
 22) PL3.30: PLEASE SHOW THE LOCATIONS OF ITEMS- 4, 5,
 6, 7, 8 IN THE LAYOUT PLAN- 107.2.1 WPB.
  
 23) PL3.30: PROVIDE AN ENLARGED INSTALLATION AND PIPING
 DETAIL FOR THE WASTEWATER SUMP PUMP AND PIT. PLEASE
 INCLUDE AN EQUIPMENT SCHEDULE FOR THE PUMP- SECS.
 1113.1- 1113.1.2 FBC P. REFER TO COMMENT #3 CONCERNING
 WASTEWATER DISPOSAL AND SHOW COMPLIANCE.
  
 24) PL3.30: SHOW THE EQUIPMENT ROOM DOOR IS EQUIPPED
 WITH A LOCKABLE DOOR OR OTHERWISE PROTECTED FROM
 UNAUTHORIZED ACCESS- 454.1.5.9 FBC B.
  
 25) PL3.00 & PL3.30: PROVIDE A CLEANING SYSTEM FOR THE
 POOL IN ACCORDANCE WITH SEC. 454.1.6.5.12 FBC B. PLEASE
 NOTE A PORTABLE, ROBOTIC OR PLUMBED-IN VACUUM CLEANING
 SYSTEM SHALL BE PROVIDED.
  
 26) PL3.30: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 RECIRCULATION AND TREATMENT EQUIPMENT INCLUDING THE
 FILTERS, CHLORINATOR, FEEDERS, AND SPA SKIMMERS SHOWING
 THE EQUIPMENT CONFORMS WITH REQUIRED STANDARDS NSF/ANSI
 STANDARD 50, CIRCULATION SYSTEM COMPONENTS AND RELATED
 MATERIALS FOR SWIMMING POOL, SPAS/HOT TUBS, DATED APRIL
 2007- SECTION 454.1.6.5.1 FBC B.
  
 27) PL3.30: PLEASE SHOW COMPLIANCE WITH THE FOLLOWING
 CODE SECTIONS FROM THE FBC EC:
 C404.9.1 HEATERS. THE ELECTRIC POWER TO ALL HEATERS
 SHALL BE CONTROLLED BY A READILY ACCESSIBLE ON-OFF
 SWITCH THAT IS AN INTEGRAL PART OF THE HEATER, MOUNTED
 ON THE EXTERIOR OF THE HEATER, OR EXTERNAL TO AND
 WITHIN 3 FEET (914 MM) OF THE HEATER. OPERATION OF SUCH
 SWITCH SHALL NOT CHANGE THE SETTING OF THE HEATER
 THERMOSTAT. SUCH SWITCHES SHALL BE IN ADDITION TO A
 CIRCUIT BREAKER FOR THE POWER TO THE HEATER. GAS-FIRED
 HEATERS SHALL NOT BE EQUIPPED WITH CONTINUOUSLY BURNING
 IGNITION PILOTS.
 C404.9.2 TIME SWITCHES. TIME SWITCHES OR OTHER CONTROL
 METHODS THAT CAN AUTOMATICALLY TURN OFF AND ON HEATERS
 AND PUMP MOTORS ACCORDING TO A PRESET SCHEDULE SHALL BE
 INSTALLED FOR HEATERS AND PUMP MOTORS. HEATERS AND PUMP
 MOTORS THAT HAVE BUILT-IN TIME SWITCHES SHALL BE IN
 COMPLIANCE WITH THIS SECTION.
 EXCEPTIONS:
 1. WHERE PUBLIC HEALTH STANDARDS REQUIRE 24-HOUR PUMP
 OPERATION.
 2. PUMPS THAT OPERATE SOLAR- AND WASTE-HEAT-RECOVERY
 POOL HEATING SYSTEMS.
 C404.9.3 COVERS. OUTDOOR HEATED SWIMMING POOLS AND
 OUTDOOR PERMANENT SPAS SHALL BE EQUIPPED WITH A
 VAPOR-RETARDANT COVER ON OR AT THE WATER SURFACE OR A
 LIQUID COVER OR OTHER MEANS PROVEN TO REDUCE HEAT LOSS.
  
 28) SUMMARY OF SEPARATE PERMITS REQUIRED:
  
 A) POTABLE WATER BACKFLOW PREVENTERS.
 B) SANITARY FACILITIES.
 C) POOL SHOWER AND HOSE BIBS.
 D) GAS WATER HEATER AND GAS PIPING.
 E) EQUIPMENT ENCLOSURE BUILDING INCLUDING THE
 MECHANICAL AND ELECTRICAL WORK.
 F) PLUMBING FIXTURES IN THE EQUIPMENT ENCLOSURE
 INCLUDING THE HOSE BIB, EMERGENCY SHOWER, FLOOR DRAIN,
 AND SUMP PUMP
 G) POOL FENCE AND GATES.
 H) POOL DECK.
 I) CIVIL ENGINEERING.
  
 29) SUMMARY OF SUBMITTALS OR DEFERRED SUBMITTALS:
  
 A) POOL LIFT.
 B) MAIN DRAIN ASSEMBLIES AND COVERS.
 C) POOL PUMP.
 D) COLLECTOR TANK.
 E) FILTERS.
 F) SKIMMERS
 G) CHLORINATION EQUIPMENT
  
 NORTH AND SOUTH SPA REVIEW COMMENTS.
  
 1) COMMENTS 1-10, 12, 13, 18, 19, 23, 24, 25, 26, 27, &
 28 FROM THE COURTYARD POOL REVIEW ABOVE ARE ALSO
 APPLICABLE TO THE SPA REVIEWS.
  
 2) PL0.20: SHOW THE LOCATIONS OF THE SPA POOL SIGNS AND
 CLOCKS- SECS. 454.1.18.13 & 454.1.18.14 FBC B.
  
 3) PL0.20: CLARIFY IF THE SPAS WILL BE EQUIPPED WITH
 EMERGENCY CUT OFF SWITCHES. REFER TO SEC. 454.1.18.15
 FBC B AND PROVIDE DETAILS IF APPLICABLE.
  
 4) PL4.00 & PL5.00: SHOW DEPTH MARKING LOCATIONS- SEC.
 454.1.2.3.1 FBC B.
  
 5) PL4.11, PL4.15, PL5.10 & PL5.15: IDENTIFY THE
 LOCATIONS OF PROPORTIONAL VALVES ON ALL RECIRCULATION
 LINES- SEC. 454.1.8.8 FBC B.
  
 6) PL4.00: REFER TO SECS. 454.1.1.1 & 454.1.7.9 FBC B
 AND SHOW COMPLIANCE- AUTOMATED OXIDATION REDUCTION
 POTENTIAL (ORP) AND PH CONTROLLERS WITH SENSING PROBES
 SHALL BE PROVIDED TO ASSIST IN MAINTAINING PROPER
 DISINFECTION AND PH LEVELS.
  
 7) PL4.15 & PL5.15: THE DRAWINGS SHOW A FEATURE PUMP
 THAT IS SUPPLYING WATER FROM THE COLLECTOR TANKS TO
 WATER SPOUTS. PLEASE SHOW THE LOCATIONS OF THE WATER
 FEATURE AND SPOUTS ON THE PLANS AND PROVIDE DETAILS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2022-02-02 Cont ID  
Sent By shill Date 2022-02-02 Time 17:42 Rev Time 0.00
Received By shill Date 2022-02-02 Time 17:42 Sent To  
Notes
2022-02-02 17:42:40INSPECTIONS ONLY

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-03-20 Cont ID  
Sent By ccole Date 2023-03-20 Time 12:42 Rev Time 0.00
Received By ccole Date 2023-03-20 Time 12:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-12-01 Cont ID  
Sent By ccole Date 2022-12-01 Time 16:07 Rev Time 0.00
Received By ccole Date 2022-12-01 Time 16:09 Sent To  
Notes
2022-12-01 16:08:56SIGNATURE REVIEW
 12/1/22
  
 SHEETS A1.201G, A7.101, C6.00, E2.01N, E5.06, L1-110,
 L1-160, L4-100, L6-100, P2.01S, S1.00-D, S5.1 ARE NOT
 DIGITALLY SIGNED AND SEALED BY THE DESIGN PROFESSIONALS
 OF RECORD- FL. STATUTE 471.025, 481.221 & 481.321.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-03-31 Cont ID  
Sent By rmcdouga Date 2022-03-31 Time 10:01 Rev Time 0.00
Received By rmcdouga Date 2022-03-31 Time 10:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2023-04-11 Cont ID  
Sent By ESchneid Date 2023-04-11 Time 16:50 Rev Time 0.25
Received By eschneid Date 2023-04-11 Time 16:07 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-05-19 Cont ID  
Sent By jroach Date 2022-05-19 Time 11:22 Rev Time 0.00
Received By jroach Date 2022-05-19 Time 11:22 Sent To  
Notes
2022-05-19 11:22:56THIS REVIEW IS FOR THE COURTYARD POOL/SPAS ONLY AND HAS
 BEEN PASSED SUBJECT TO THE FOLLOWING PROVISOS:
  
 1. ALL DEVELOPMENT WITHIN THE MARINA COMMERCIAL MARINE
 PLANNED DEVELOPMENT (CMPD) SHALL BE SUBJECT TO ALL
 DEVELOPMENT ORDER CONDITIONS, DESIGN GUIDELINES, ETC.,
 AS OUTLINED IN RESOLUTION NO. 66-22, AND AS MAY BE
 AMENDED. ALL CONDITIONS OF APPROVAL IMPOSED BY THE
 DEVELOPMENT ORDER SHALL BE ADDRESSED WITHIN THE
 APPROPRIATE SPECIFIED TIMEFRAMES.
 _______________________________________________________
 _____________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 _______________________________________________________
 _____________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 P: 561.822.1448 | E: [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved