Plan Review Details - Permit 22010173
Plan Review Stops For Permit 22010173
Review Stop AD ADDRESSING
Rev No 4 Status P Date 2022-03-31 Cont ID  
Sent By cpuell Date 2022-03-31 Time 14:38 Rev Time 0.00
Received By cpuell Date 2022-03-31 Time 14:38 Sent To  
Notes
2022-03-31 14:38:59PARCEL MERGED INTO A NEW PARCEL 74434328060200010 WITH
 THE NEW ADDRESS OF 475 CLAREMORE DR, UPDATED PERMIT

Review Stop AD ADDRESSING
Rev No 3 Status F Date 2022-03-05 Cont ID  
Sent By cpuell Date 2022-03-05 Time 14:07 Rev Time 0.00
Received By cpuell Date 2022-03-05 Time 14:06 Sent To  
Notes
2022-03-05 14:07:10PREVIOUS COMMENTS NOT ADDRESSED

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2022-01-26 Cont ID  
Sent By cpuell Date 2022-01-26 Time 14:12 Rev Time 0.00
Received By cpuell Date 2022-01-26 Time 14:12 Sent To  
Notes
2022-01-26 14:13:00PREVIOUS COMMENTS NOT ADDRESSED

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-01-07 Cont ID  
Sent By cpuell Date 2022-01-07 Time 10:13 Rev Time 0.00
Received By cpuell Date 2022-01-07 Time 10:13 Sent To  
Notes
2022-01-07 10:14:45WILL THE WORK BE ON PARCEL 74434328060200011 AND
 74434328060200012? PLEASE RESPOND TO [email protected] OR
 CALL 561-805-6659

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-04-21 Cont ID  
Sent By rmcphers Date 2022-04-21 Time 13:52 Rev Time 0.00
Received By rmcphers Date 2022-04-21 Time 13:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-03-15 Cont ID  
Sent By rmcphers Date 2022-03-15 Time 10:48 Rev Time 0.00
Received By rmcphers Date 2022-03-15 Time 10:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-02-14 Cont ID  
Sent By rmcphers Date 2022-02-14 Time 08:49 Rev Time 0.00
Received By rmcphers Date 2022-02-14 Time 08:45 Sent To  
Notes
2022-02-14 08:49:54TENNIS COURT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) NEW PLANS SHOW PARKING - PLEASE SHOW THE ACCESSIBLE
 PARKING, ACCESS AISLE AND ACCESSIBLE PATH TO THE TENNIS
 COURT FBC A 502
  
 2) SITE LIGHTING WILL NEED TO BE ON A SEPARATE PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-01-11 Cont ID  
Sent By rmcphers Date 2022-01-11 Time 11:52 Rev Time 0.00
Received By rmcphers Date 2022-01-11 Time 11:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2022-04-26 Cont ID  
Sent By mpeterso Date 2022-04-26 Time 16:14 Rev Time 0.00
Received By mpeterso Date 2022-04-26 Time 16:14 Sent To  
Notes
2022-04-26 16:14:49ELECTRIC IS ON ANOTHER PERMIT. MP

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-03-29 Cont ID  
Sent By mpeterso Date 2022-03-29 Time 09:52 Rev Time 0.00
Received By mpeterso Date 2022-03-29 Time 09:52 Sent To  
Notes
2022-03-29 09:54:42FBC 107 LOCATION OF PROPOSED WORK IS NOT CLEAR. PLEASE
 CLARIFY
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2022-03-07 Cont ID  
Sent By rrossano Date 2022-03-07 Time   Rev Time 0.00
Received By rrossano Date 2022-03-07 Time   Sent To  
Notes
2022-03-07 09:02:28RECEIVED ENGINEERING PLANS FOR FORMAL ENGINEERING
 SUBMITTAL E22030017. ENGINEERING PLANS TO BE UPLOADED
 FOR BUILDING PERMIT UPON FINAL REVISION.
  
 THANKS,
 RICK ROSSANO, SENIOR PROJECT COORDINATOR,
 CITY OF WPB ENGINEERING SERVICES DEPARTMENT
 DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE:
 (561) 246-9525
 EMAIL: [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2022-01-27 Cont ID  
Sent By rrossano Date 2022-01-27 Time   Rev Time 0.00
Received By rrossano Date 2022-01-27 Time   Sent To  
Notes
2022-01-27 12:29:16PLEASE PROVIDE CIVIL ENGINEERING DRAWINGS AND PROJECT
 SPECIFIC SURVEY (TENNIS COURTS AREA) FOR THE SUBMITTAL.
  
 THANKS,
 RICK ROSSANO, SENIOR PROJECT COORDINATOR,
 CITY OF WPB ENGINEERING SERVICES DEPARTMENT
 DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE:
 (561) 246-9525
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-04-26 Cont ID  
Sent By mpeterso Date 2022-04-26 Time 16:14 Rev Time 0.00
Received By mpeterso Date 2022-04-15 Time 07:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-03-29 Cont ID  
Sent By mpeterso Date 2022-03-29 Time 09:54 Rev Time 0.00
Received By mpeterso Date 2022-03-03 Time 07:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-02-14 Cont ID  
Sent By rmcphers Date 2022-02-14 Time 09:06 Rev Time 0.00
Received By rmcphers Date 2022-01-26 Time 08:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-20 Cont ID  
Sent By lmarchan Date 2022-01-20 Time 15:21 Rev Time 0.00
Received By lmarchan Date 2022-01-06 Time 11:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2022-04-26 Cont ID  
Sent By mpeterso Date 2022-04-26 Time 16:12 Rev Time 0.00
Received By mpeterso Date 2022-04-26 Time 16:12 Sent To  
Notes
2022-04-26 16:14:074/26/22 SIGNATURE PASSED ON 1 UNLOCKED DRAWINGS FP-1
 AND 1 SURVEY. ALL OTHER DRAWINGS LOCKED OUT. MP

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2022-04-21 Cont ID  
Sent By rmcphers Date 2022-04-21 Time 13:52 Rev Time 0.00
Received By rmcphers Date 2022-04-21 Time 13:51 Sent To  
Notes
2022-04-21 13:52:17SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS BY - WILLIAM E. PINO P.E. - DO NOT SHOW AS
 DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-03-15 Cont ID  
Sent By rmcphers Date 2022-03-15 Time 10:48 Rev Time 0.00
Received By rmcphers Date 2022-03-15 Time 10:48 Sent To  
Notes
2022-03-15 10:49:51SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) PHOTOMETRIC DRAWINGS PROVIDED DO NOT SHOW AS
 DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-02-14 Cont ID  
Sent By rmcphers Date 2022-02-14 Time 09:03 Rev Time 0.00
Received By rmcphers Date 2022-02-14 Time 09:03 Sent To  
Notes
2022-02-14 09:05:18SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) THE SURVEY PROVIDED DOES NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-01-11 Cont ID  
Sent By rmcphers Date 2022-01-11 Time 11:52 Rev Time 0.00
Received By rmcphers Date 2022-01-11 Time 11:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2022-04-21 Cont ID  
Sent By llouie Date 2022-04-21 Time   Rev Time 0.00
Received By llouie Date 2022-04-21 Time   Sent To  
Notes
2022-04-21 15:34:43SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, WALL/FENCE,
 LIGHTING, PARKING LOT, ETC.

Review Stop Z ZONING
Rev No 3 Status F Date 2022-03-22 Cont ID  
Sent By llouie Date 2022-03-22 Time   Rev Time 0.00
Received By llouie Date 2022-03-22 Time   Sent To  
Notes
2022-03-22 15:01:19** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) A PHOTOMETRIC PLAN IS REQUIRED.
  
 [1/20/2022 AND 2/2/2022 REPEAT COMMENT: NOT ADDRESSED.
 A NOTE WILL NOT SUFFICE. THE PHOTOMETRIC PLAN MUST SHOW
 THE PHOTOMETRIC SPILLOVER BEYOND THE PROPERTY LINES OF
 THE PROPERTY. PER SEC. 94-207(D)(8) OF THE ZLDRS, ANY
 SOURCE OF ILLUMINATION SHALL NOT EXCEED ONE FOOTCANDLE
 AT OR BEYOND THE BOUNDARIES OF THE PROPERTY. PLEASE
 SHOW ILLUMINATION SPILLOVER TO DEMONSTRATE COMPLIANCE
 WITH THE ZONING CODE.]
  
  
 2.) NORTHEAST TERMINAL ISLAND LOCATED WITHIN THE
 ON-SITE PARKING AREA SHALL BE DIMENSIONED FOR
 CONSISTENCY WITH THE ZLDRS.
  
 [2/2/2022 REPEAT COMMENT: NOT ADDRESSED. NO DIMENSION
 PROVIDED IN THE PERMIT RESUBMITTAL.]
  
  
 3.) ENGINEERING PLANS SHALL BE SUBMITTED, REVIEWED AND
 APPROVED BY THE ENGINEERING SERVICES DEPARTMENT PRIOR
 TO ZONING SIGN-OFF OF THIS PERMIT. APPROVED ENGINEERING
 PLANS MUST BE CONSISTENT WITH THE SITE PLAN WITH THIS
 PERMIT APPLICATION.
  
 [2/2/2022 REPEAT COMMENT: PASS FROM ENGINEERING
 REQUIRED PRIOR TO ZONING SIGN OFF OF THIS PERMIT.]
  
  
 4.) ALL PERMIT PLANS FOR THE PROPOSED TENNIS COURTS
 SHALL MATCH. PLANS ARE INCONSISTENT WITH THE SUBMITTED
 LANDSCAPE PERMIT (REFERENCE: #22020765).
  
  
 NOTES:
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: GC/PROPOSED GREENE SCHOOL CPD.
  
 * UNITY OF TITLE REQUIREMENT SATSIFIED - ORB BK 33267
 PG 0153 (RECORDED ON 1/31/2022).
  
 CHECK WITH ENGINEERING ON STATUS OF BOND (EPIRES
 4/1/2022?].
  

Review Stop Z ZONING
Rev No 2 Status F Date 2022-02-02 Cont ID  
Sent By llouie Date 2022-02-02 Time   Rev Time 0.00
Received By llouie Date 2022-02-02 Time   Sent To  
Notes
2022-02-02 14:55:06** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SIGNED AND SEALED UPDATED SURVEY OF THE PROPERTY IS
 REQUIRED. A SURVEY WAS NOT PROVIDED WITH THE PERMIT
 APPLICATION. [1/20/2022 MODIFIED COMMENT: THE SURVEY
 SHALL ONLY CONSIST OF THE PARCELS FOR THE OUTDOOR
 TENNIS COURTS.]
  
 2.) HOW TALL ARE THE POLE FIXTURES? FIXTURE DETAILS
 REQUIRED. [1/20/2022 REPEAT COMMENT: NO
 INFORMATION/DETAIL PROVIDED ON THE POLE FIXTURES.]
  
 3.) THE FOLLOWING NOTE SHALL BE PROVIDED IN THE PLANS
 FOR CONSISTENCY WITH THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDRS): ALL OUTDOOR LIGHTING SHALL BE
 SHIELDED TO REDUCE GLARE AND SHALL BE ARRANGED TO
 REFLECT LIGHT OR GLARE AWAY FROM ALL ADJACENT
 RESIDENTIAL DISTRICTS, ADJACENT RESIDENCES, OR PUBLIC
 THROUGHFARES. [ZLDR S.94-309.A.] [1/20/2022 REPEAT
 COMMENT: NOTE NOT PROVIDED IN THE REVISED PLANS.]
  
 4.) A PHOTOMETRIC PLAN IS REQUIRED. [1/20/2022 MODIFIED
 COMMENT: THE PHOTOMETRIC PLAN MUST SHOW THE PHOTOMETRIC
 SPILLOVER BEYOND THE PROPERTY LINES OF THE PROPERTY.
 PER SEC. 94-207(D)(8) OF THE ZLDRS, ANY SOURCE OF
 ILLUMINATION SHALL NOT EXCEED ONE FOOTCANDLE AT OR
 BEYOND THE BOUNDARIES OF THE PROPERTY. PLEASE SHOW
 ILLUMINATION SPILLOVER TO DEMONSTRATE COMPLIANCE WITH
 THE ZONING CODE.]
  
 5.) A 5 FT. WIDE LANDSCAPE BUFFER SHALL BE PROVIDED
 ALONG THE ENTIRE PERIMETER OF THE PROJECT. THE REVISED
 PLAN SHOWS THAT PERIMETER LANDSCAPE BUFFER REQUIREMENT
 IS NOT MET AROUND THE PERIMETER OF THE ON-SITE PARKING
 AREA. THE INGRESS/EGRESS POINT MAY HAVE TO BE SHIFTED
 TO ACCOMMODATE THE BUFFER REQUIREMENT.
  
 6.) A SEPARATE LANDSCAPE PERMIT SHALL BE SUBMITTED,
 REVIEWED AND APPROVED PRIOR TO ZONING SIGN-OFF. THE
 LANDSCAPE PERMIT MUST BE REVIEWED FOR CONSISTENCY WITH
 THIS PERMIT. THE APPLICANT/PROJECT TEAM WAS INFORMED
 THAT A SEPARATE LANDSCAPE PERMIT WAS REQUIRED DURING A
 ZOOM CALL ON THE 1/11/2022; HOWEVER, THIS HAS YET TO BE
 ADDRESSED AS THERE IS NO RECORD OF A LANDSCAPE PERMIT
 IN THE SYSTEM.]
  
 7.) NORTHEAST TERMINAL ISLAND LOCATED WITHIN THE
 ON-SITE PARKING AREA SHALL BE DIMENSIONED FOR
 CONSISTENCY WITH THE ZLDRS.
  
 8.) ENGINEERING PLANS SHALL BE SUBMITTED, REVIEWED AND
 APPROVED BY THE ENGINEERING SERVICES DEPARTMENT PRIOR
 TO ZONING SIGN-OFF OF THIS PERMIT. APPROVED ENGINEERING
 PLANS MUST BE CONSISTENT WITH THE SITE PLAN WITH THIS
 PERMIT APPLICATION.
  
  
 NOTES:
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: GC/PROPOSED GREENE SCHOOL CPD.
  
 * UNITY OF TITLE REQUIREMENT SATSIFIED - ORB BK 33267
 PG 0153 (RECORDED ON 1/31/2022).
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-01-20 Cont ID  
Sent By ajones Date 2022-01-20 Time   Rev Time  
Received By llouie Date 2022-01-20 Time   Sent To  
Notes
2022-01-20 15:02:33** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SIGNED AND SEALED UPDATED SURVEY OF THE PROPERTY IS
 REQUIRED. A SURVEY WAS NOT PROVIDED WITH THE PERMIT
 APPLICATION.
  
 2.) A UNIT OF TITLE IS REQUIRED TO JOIN THE ADJACENT
 PARCEL, WHICH SEEMS TO BE A PART OF THE PROJECT AREA.
  
 3.) PLANS SHALL BE CONSISTENT WITH THE APPLICATION FOR
 THE PROPOSED CREATION OF THE GREENE SCHOOL COMMERCIAL
 PLANNED DEVELOPMENT (CPD) TO WHICH THE PARCELS IS
 PROPOSED TO BE A PART OF.
  
 4.) A 5 FT WIDE LANDSCAPE BUFFER IS REQUIRED ALONG THE
 BISCAYNE DRIVE PROPERTY LINE. [ZLDR S.94-443]
  
 5.) SHOW SETBACK DISTANCE OF THE LIGHT POLE FIXTURES TO
 THE PROPERTY LINE(S). A MINIMUM 5 FT. IS REQUIRED FROM
 THE PROPERTY LINES.
  
 6.) HOW TALL ARE THE POLE FIXTURES? FIXTURE DETAILS
 REQUIRED.
  
 7.) THE FOLLOWING NOTE SHALL BE PROVIDED IN THE PLANS
 FOR CONSISTENCY WITH THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDRS): ALL OUTDOOR LIGHTING SHALL BE
 SHIELDED TO REDUCE GLARE AND SHALL BE ARRANGED TO
 REFLECT LIGHT OR GLARE AWAY FROM ALL ADJACENT
 RESIDENTIAL DISTRICTS, ADJACENT RESIDENCES, OR PUBLIC
 THROUGHFARES. [ZLDR S.94-309.A.]
  
 8.) A PHOTOMETRIC PLAN IS REQUIRED.
  
  
 NOTES:
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: GC/PROPOSED GREENE SCHOOL CPD
  