Plan Review Details - Permit 22010129
Plan Review Stops For Permit 22010129
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2022-02-04 Cont ID  
Sent By rmcphers Date 2022-02-04 Time 09:45 Rev Time 0.00
Received By rmcphers Date 2022-02-04 Time 09:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-05-02 Cont ID  
Sent By rmcphers Date 2022-05-02 Time 11:11 Rev Time 0.00
Received By rmcphers Date 2022-05-02 Time 11:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-03-23 Cont ID  
Sent By rmcphers Date 2022-03-23 Time 11:28 Rev Time 0.00
Received By rmcphers Date 2022-03-23 Time 11:13 Sent To  
Notes
2022-03-23 11:28:49RESTAURANT BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
  
 1) ALL PRODUCT APPROVALS PROVIDED NEED TO BE REVIEWED
 AND MARKED APPROVED BY THE ARCHITECT OR ENGINEER OF
 RECORD - FBC WPB 107.3.4
  
 2) PRODUCT APPROVAL PROVIDED FOR CASEMENT WINDOWS -
 PLEASE SHOW THE LOCATION AND LABEL AS SUCH ON THE
 DRAWINGS FOR THE CASEMENT WINDOWS.
  
 3) PRODUCT APPROVAL PROVIDED FOR HORIZONTAL SLIDING
 WINDOWS - PLEASE SHOW THE LOCATION AND LABEL AS SUCH ON
 THE DRAWINGS FOR THE HORIZONTAL SLIDING WINDOWS.
  
 4) PLEASE PROVIDE A COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE BI FOLD DOORS/ WINDOWS SHOWN
 ON THE DRAWINGS. FBC 1609.1.2
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-02-04 Cont ID  
Sent By rmcphers Date 2022-02-04 Time 10:14 Rev Time 0.00
Received By rmcphers Date 2022-02-04 Time 09:55 Sent To  
Notes
2022-02-04 10:14:06RESTAURANT BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
  
 1) DRAWING 1.0A SHOWS ASCE 7-10 USED FOR WIND DESIGN -
 SHOULD BE ASCE 7-16 - PLEASE CORRECT FBC CHAPTER 35
  
 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR DOORS - ALL PRODUCT
 APPROVALS NEED TO BE REVIEWED AND MARKED APPROVED BY
 THE DESIGNER OF RECORD FBC WPB 107.3.4
  
 3) PLEASE SHOW THE RAMP HANDRAIL EXTENSIONS FBC A
 505.10.1TOP AND BOTTOM EXTENSION AT RAMPS.
 RAMP HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE
 LANDING FOR 12 INCHES (305 MM) MINIMUM BEYOND THE TOP
 AND BOTTOM OF RAMP RUNS. EXTENSIONS SHALL RETURN TO A
 WALL, GUARD, OR THE LANDING SURFACE, OR SHALL BE
 CONTINUOUS TO THE HANDRAIL OF AN ADJACENT RAMP RUN.
  
 4) PLEASE SHOW THE RAMP EDGE PROTECTION PER FBC A 405.9
 EDGE PROTECTION.
 EDGE PROTECTION COMPLYING WITH 405.9.1 OR 405.9.2 SHALL
 BE PROVIDED ON EACH SIDE OF RAMP RUNS AND AT EACH SIDE
 OF RAMP LANDINGS.
  
 5) ACCESSIBLE RESTROOMS - PLEASE SHOW ALL LOCATION
 DIMENSIONS FOR THE GRAB BARS, MIRROR, TOILET PAPER
 HOLDER, PAPER TOWEL REACH RANGES, ETC PER FBC
 ACCESSIBILITY
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-05-10 Cont ID  
Sent By fgiaquin Date 2022-05-10 Time 22:42 Rev Time 0.00
Received By fgiaquin Date 2022-05-10 Time 22:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-04-04 Cont ID  
Sent By fgiaquin Date 2022-04-04 Time 22:42 Rev Time 0.00
Received By fgiaquin Date 2022-04-04 Time 21:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-01-28 Cont ID  
Sent By fgiaquin Date 2022-01-28 Time 21:59 Rev Time 0.00
Received By fgiaquin Date 2022-01-28 Time 21:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-04-22 Cont ID  
Sent By pleduc Date 2022-04-22 Time   Rev Time 0.00
Received By pleduc Date 2022-04-22 Time 10:38 Sent To  
Notes
2022-04-22 10:46:54FIRE PROVISO:
  
 1) INSTALL EXIT SIGN AT BOTTOM OF STAIRWAY DOOR.
  
  
 2) DOOR # 5 DEADBOLT - PER NFPA 101
  
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY,
 A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION
 FROM THE EGRESS SIDE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-03-21 Cont ID  
Sent By pleduc Date 2022-03-21 Time   Rev Time 0.00
Received By pleduc Date 2022-03-21 Time 11:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-01-10 Cont ID  
Sent By pleduc Date 2022-01-10 Time   Rev Time 0.00
Received By pleduc Date 2022-01-10 Time 09:23 Sent To  
Notes
2022-01-10 10:13:10FIRE PROVISO:
  
 1) INSTALL EXIT SIGN AT BOTTOM OF STAIRWAY DOOR.
  
  
 2) DOOR # 5 DEADBOLT - PER NFPA 101
  
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY,
 A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION
 FROM THE EGRESS SIDE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2022-04-29 Cont ID  
Sent By ccole Date 2022-04-29 Time 16:13 Rev Time 0.00
Received By ccole Date 2022-04-28 Time 08:47 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2022-03-21 Cont ID  
Sent By ccole Date 2022-03-21 Time 17:08 Rev Time 0.00
Received By ccole Date 2022-03-21 Time 17:08 Sent To  
Notes
2022-03-21 17:10:502ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 22010129
 3/21/2022
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. REMAINING COMMENTS FROM
 THE 1ST REVIEW ARE LISTED BELOW.
  
 1) FAILED. SHEET 3.0P GAS RISER: INCREASE THE 1-INCH
 PIPE SHOWN AT THE 33 FT. RUN TO 1-1/2-INCH BASED ON
 TABLE 402.4(2) FBC FG. CORRECTED SHEET 3.0P NOT
 UPLOADED.
  
 2) FAILED. SHEET 3.0P GAS RISER: SHOW THE BRANCH PIPE
 SIZES FOR THE APPLIANCES ON THE COOKING LINE- TABLE
 402.4(2) FBC FG. SHEET 3.1P SHOWS INDIVIDUAL COMBUSTION
 AIR INTAKE AND EXHAUST DUCTS. ALL OTHER PLANS INDICATE
 A CONCENTRIC VENT- WHICH IS IT?
  
 4) FAILED. SHEET 3.0P: PROVIDE A VENTING DIAGRAM FOR
 THE TANKLESS WATER HEATER SHOWING THE TYPE AND SIZE OF
 CONCENTRIC, VENT RUN LENGTH FROM THE APPLIANCE TO THE
 TERMINATION ABOVE THE ROOF, CLEARANCE HEIGHT ABOVE THE
 ROOF, AND CLEARANCES TO AIR EXHAUST OUTLET AND AIR
 INTAKES ON THE ROOF- SECS. 503.2.3, 503.8 & 624.1. A)
 SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE CONCENTRIC
 VENT DUCT- SECS. 503.4.1 & 624.1 FBC FG. PLEASE NOTE
 THE VENT DUCT SHALL BE LISTED AND LABELED PER SEC.
 503.3.6:
  
 WHERE A VENTING SYSTEM PASSES THROUGH AN ABOVE-CEILING
 AIR-HANDLING SPACE OR OTHER NON-DUCTED PORTION OF AN
 AIR-HANDLING SYSTEM, THE VENTING SYSTEM SHALL CONFORM
 TO ONE OF THE FOLLOWING REQUIREMENTS:
  
 1.THE VENTING SYSTEM SHALL BE A LISTED SPECIAL GAS
 VENT; OTHER VENTING SYSTEM SERVING A CATEGORY III OR
 CATEGORY IV APPLIANCE; OR OTHER POSITIVE PRESSURE VENT,
 WITH JOINTS SEALED IN ACCORDANCE WITH THE APPLIANCE OR
 VENT MANUFACTURER?S INSTRUCTIONS.
 2.THE VENTING SYSTEM SHALL BE INSTALLED SUCH THAT
 FITTINGS AND JOINTS BETWEEN SECTIONS ARE NOT INSTALLED
 IN THE ABOVE-CEILING SPACE.
 3.THE VENTING SYSTEM SHALL BE INSTALLED IN A CONDUIT OR
 ENCLOSURE WITH SEALED JOINTS SEPARATING THE INTERIOR OF
 THE CONDUIT OR ENCLOSURE FROM THE CEILING SPACE. VENT
 SPECS NOT SUBMITTED
  
 6) FAILED. SHEET 3.0P: THE PLAN SHOWS A GAS-FIRED
 TANKLESS WATER HEATER ON THE EXTERIOR WALL. IS THIS
 HEATER IN USE OR TO BE REMOVED- SEC. 107.2.1 WPB.
 CORRECTED SHEET 3.0P NOT UPLOADED.
  
 7) FAILED. SHEET 3.0P: PROVIDE A CONDENSATE DISPOSAL
 PLAN FOR THE NEW INTERIOR GAS-FIRED WATER HEATER- SECS.
 307.2, 307.4, & 307.5 FBC FG. SHOW THE TYPE AND SIZE OF
 CONDENSATE PIPING, PIPING RUN, REQUIRED PAN, PAN DRAIN
 LINE AND DISPOSAL LOCATION. PLEASE NOTE A NEUTRALIZING
 DEVICE WILL BE REQUIRED PER SEC. 803.1 FBC P. CORRECTED
 SHEET 3.0P NOT UPLOADED. PLEASE NOTE THAT CONDESNATE
 SHALL NOT DRAIN INTO THE SANITARY SYSTEM- SEC. 90-126
 WPB CODE OF ORDINANCES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB.
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-01-20 Cont ID  
Sent By ccole Date 2022-01-20 Time 17:36 Rev Time 0.00
Received By ccole Date 2022-01-20 Time 17:36 Sent To  
Notes
2022-01-20 17:38:181ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 22010129
 1/20/2022
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 3.0P GAS RISER: INCREASE THE 1-INCH PIPE SHOWN
 AT THE 33 FT. RUN TO 1-1/2-INCH BASED ON TABLE 402.4(2)
 FBC FG.
  
 2) SHEET 3.0P GAS RISER: SHOW THE BRANCH PIPE SIZES FOR
 THE APPLIANCES ON THE COOKING LINE- TABLE 402.4(2) FBC
 FG.
  
 3) SHEET 3.0P: CORRECT THE COMBUSTION AIR CALCULATION
 TO INDICATE .35 X473 KBTUH- SEC. 304.9 FBC P. CLARIFY
 HOW THE 165 CFMS OF COMBUSTION AIR IS BEING PROVIDED
 MECHANICALLY. THE O/A CALCULATIONS ON SHEET 4.0M
 INDICATE A TOTAL OF 190 CFMS FOR THE OCCUPANTS- SEC.
 304.9.3 FBC FG.
  
 4) SHEET 3.0P: PROVIDE A VENTING DIAGRAM FOR THE
 TANKLESS WATER HEATER SHOWING THE TYPE AND SIZE OF
 CONCENTRIC, VENT RUN LENGTH FROM THE APPLIANCE TO THE
 TERMINATION ABOVE THE ROOF, CLEARANCE HEIGHT ABOVE THE
 ROOF, AND CLEARANCES TO AIR EXHAUST OUTLET AND AIR
 INTAKES ON THE ROOF- SECS. 503.2.3, 503.8 & 624.1. A)
 SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE CONCENTRIC
 VENT DUCT- SECS. 503.4.1 & 624.1 FBC FG. PLEASE NOTE
 THE VENT DUCT SHALL BE LISTED AND LABELED PER SEC.
 503.3.6:
  
 WHERE A VENTING SYSTEM PASSES THROUGH AN ABOVE-CEILING
 AIR-HANDLING SPACE OR OTHER NON-DUCTED PORTION OF AN
 AIR-HANDLING SYSTEM, THE VENTING SYSTEM SHALL CONFORM
 TO ONE OF THE FOLLOWING REQUIREMENTS:
  
 1.THE VENTING SYSTEM SHALL BE A LISTED SPECIAL GAS
 VENT; OTHER VENTING SYSTEM SERVING A CATEGORY III OR
 CATEGORY IV APPLIANCE; OR OTHER POSITIVE PRESSURE VENT,
 WITH JOINTS SEALED IN ACCORDANCE WITH THE APPLIANCE OR
 VENT MANUFACTURER?S INSTRUCTIONS.
 2.THE VENTING SYSTEM SHALL BE INSTALLED SUCH THAT
 FITTINGS AND JOINTS BETWEEN SECTIONS ARE NOT INSTALLED
 IN THE ABOVE-CEILING SPACE.
 3.THE VENTING SYSTEM SHALL BE INSTALLED IN A CONDUIT OR
 ENCLOSURE WITH SEALED JOINTS SEPARATING THE INTERIOR OF
 THE CONDUIT OR ENCLOSURE FROM THE CEILING SPACE.
  
 5) SHEET 3.0P: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE COOKING APPLIANCES- SEC. 623.1 FBC FG.
  
 6) SHEET 3.0P: THE PLAN SHOWS A GAS-FIRED TANKLESS
 WATER HEATER ON THE EXTERIOR WALL. IS THIS HEATER IN
 USE OR TO BE REMOVED- SEC. 107.2.1 WPB.
  
 7) SHEET 3.0P: PROVIDE A CONDENSATE DISPOSAL PLAN FOR
 THE NEW INTERIOR GAS-FIRED WATER HEATER- SECS. 307.2,
 307.4, & 307.5 FBC FG. SHOW THE TYPE AND SIZE OF
 CONDENSATE PIPING, PIPING RUN, REQUIRED PAN, PAN DRAIN
 LINE AND DISPOSAL LOCATION. PLEASE NOTE A NEUTRALIZING
 DEVICE WILL BE REQUIRED PER SEC. 803.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-05-10 Cont ID  
Sent By fgiaquin Date 2022-05-10 Time 22:42 Rev Time 0.00
Received By fgiaquin Date 2022-04-21 Time 07:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-04-14 Cont ID  
Sent By aoliver Date 2022-04-14 Time 10:02 Rev Time 0.00
Received By aoliver Date 2022-03-18 Time 09:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-02-04 Cont ID  
Sent By rmcphers Date 2022-02-04 Time 10:33 Rev Time 0.00
Received By rmcphers Date 2022-01-10 Time 08:11 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-05-19 Cont ID  
Sent By aoliver Date 2022-05-19 Time 12:03 Rev Time 0.00
Received By aoliver Date 2022-05-11 Time 07:53 Sent To  
Notes
2022-05-19 12:03:575/19/22 NO IMPACT FEES DUE, SEE UPLOADED EMAIL AO
2022-05-11 07:53:215/11/22 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-02-04 Cont ID  
Sent By rmcphers Date 2022-02-04 Time 10:21 Rev Time 0.00
Received By rmcphers Date 2022-02-04 Time 10:21 Sent To  
Notes
2022-02-04 10:22:44PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-05-04 Cont ID  
Sent By medwards Date 2022-05-04 Time 13:11 Rev Time 0.00
Received By medwards Date 2022-05-04 Time 13:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-03-29 Cont ID  
Sent By medwards Date 2022-03-29 Time 13:20 Rev Time 0.00
Received By medwards Date 2022-03-29 Time 13:20 Sent To  
Notes
2022-03-29 13:21:272ND REVIEW FBC-2020 MECHANICAL
 PERMIT-22010129
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW THE OUTDOOR AIR REQUIRED FOR THE BAR.
 FMC TABLE 403.3.1.1
  
 2) THE WALK-IN COOLER WILL NOT BE REVIEWED AT THIS
 TIME. IT WILL REQUIRE A SEPARATE PERMIT AND PLAN
 REVIEW. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-01-13 Cont ID  
Sent By medwards Date 2022-01-13 Time 12:06 Rev Time 0.00
Received By medwards Date 2022-01-13 Time 12:06 Sent To  
Notes
2022-01-13 12:06:481ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22010129
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE LIFE SAFETY PLAN INDICATES A BREWERY BUT I DO
 NOT SEE ONE ON THE DRAWINGS. PLEASE LABEL EACH USE OF
 SPACE IN THIS CHANGE OF USE TENANT SPACE. FBC 107.2.1
  
 2) THE LIFE SAFETY SHEET INDICATES THE KITCHEN SQUARE
 FOOTAGE AS 1775, SHEET 4.0M INDICATES IN THE OUTDOOR
 AIR CALCULATIONS THAT THE KITCHEN SQUARE FOOTAGE IS
 ONLY 807. PLEASE BE CONSISTENT. FBC 107.2.1
  
 3) THE LIFE SAFETY SHEET INDICATES THE LOUNGE SQUARE
 FOOTAGE AS1583, SHEET 4.0M INDICATES IN THE OUTDOOR AIR
 CALCULATIONS THAT THE DINING ROOM SQUARE FOOTAGE IS
 2695. PLEASE BE CONSISTENT. FBC 107.2.1
  
 4) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH
 USE OF SPACE IN THIS TENANT SPACE ACCORDING TO THE FBC
 M 403.3.1.1 AND TABLE 403.3.1.1 AND NOT THE OCCUPANT
 COUNT FROM THE ARCHITECT.
  
 5) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR EACH UNIT. FBC EC C403.2.1
  
 6) PLEASE SHOW HOW THE OUTDOOR AIR WILL BE DISTRIBUTED
 CONSISTENTLY IN THIS TENANT SPACE. FBC 107.2.1
  
 7) PLEASE IDENTIFY THE UNIT IN THE KITCHEN ON THE
 MECHANICAL DRAWING. FBC 107.2.1
  
 8) SHEET 2.2E INDICATES THERE IS A DISHWASHER, PLEASE
 SHOW THIS DISHWASHER ON THE MECHANICAL DRAWINGS. PLEASE
 ALSO PROVIDE DETAILS FOR THIS DISHWASHER. PLEASE SHOW
 HOW THIS DISHWASHER MEETS THE REQUIREMENTS OF FBC M
 507.3 FOR HAVING A HOOD ABOVE THE DISHWASHER.
  
 9) PLEASE PROVIDE THE CONDENSATE PIPE, SIZE AND
 TERMINATION LOCATION. FBC M 307
  
 10) PLEASE SHOW THAT THE EQUIPMENT ON THE ROOF WILL
 MEET THE GUARDS REQUIREMENT IN FBC M 304.11
  
 11) PLEASE SHOW THAT THE NEW EQUIPMENT ACCESS WILL MEET
 THE REQUIREMENTS FOR ACCESS INCLUDING THE 30 INCH HIGH
 REQUIREMENT FOR CLIMBING OVER OBSTRUCTIONS. FBC M 306.5
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-04-29 Cont ID  
Sent By ccole Date 2022-04-29 Time 16:13 Rev Time 0.00
Received By ccole Date 2022-04-28 Time 08:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-03-21 Cont ID  
Sent By ccole Date 2022-03-21 Time 17:11 Rev Time 0.00
Received By ccole Date 2022-03-21 Time 13:10 Sent To  
Notes
2022-03-21 17:11:542ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22010129
 3/21/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. REMAINING 1ST REVIEW
 COMMENTS LISTED BELOW.
  
 1) FAILED. SHEETS C-1, 1.3A, 3.0P: PROVIDE PLUMBING
 FIXTURE CALCULATIONS IN COMPLIANCE WITH TABLE 403.1 FBC
 P. PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED NUMBER OF PLUMBING FIXTURES. PLEASE CLARIFY
 WHICH OCCUPANT LOAD IS CORRECT- (161 OCCUPANTS- SHEET
 C-1) OR (178 OCCUPANTS- SHEET 1.3A). PLEASE NOTE THAT
 DRINKING FOUNTAINS ARE REQUIRED FIXTURES FOR ASSEMBLY
 AND BUSINESS OCCUPANCIES. SHOW THE LOCATION OF THE
 REQUIRED DRINKING FOUNTAINS OR PLACE A NOTE TO INDICATE
 DRINKING WATER IN A CONTAINER FREE OF CHARGE WILL BE
 PROVIDED- SEC.- 410.4 FBC P. THE CORRECTED C-1 SHEET
 WAS NOT UPLOADED.
  
 3) FAILED. SHEET 1.0A- MISSING ACCESSIBILITY DETAILS
 PER FBC ACC:
 K) HEIGHT AND DEPTH OF THE ACCESSIBLE URINAL- SEC.
 605.2. NOT PROVIDED.
 L) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 ACCESSIBLE URINAL- SEC. 605.3. NOT PROVIDED.
  
 4) FAILED. SHEET 1.0A: PROVIDE THE DEPTH MEASUREMENTS
 OF THE STANDARD RESTROOM STALLS- SEC. 405.3.1 FBC P.
 NOT PROVIDED.
  
  
 5) FAILED. SHEET 3.0P: PROVIDE GREASE WASTE
 CALCULATIONS IN COMPLIANCE WITH SEC. 1003.3.5 FBC P.
 PLEASE ADD THE GREASE INTERCEPTOR TO THE LIST OF
 SEPARATE PERMITS ON SHEET C-1. NOTE: COMPLETE GREASE
 INTERCEPTOR PLANS, EQUIPMENT SPECIFICATIONS,
 CALCULATIONS AND DETAILS WILL BE REQUIRED UNDER THE
 SEPARATE PERMIT. CORRECTED SHEET 3.0P NOT UPLOADED.
  
 12) FAILED. SHEETS 3.0P & 3.1P: PLEASE NOTE A SEPARATE
 PERMIT IS REQUIRED FOR THE POTABLE WATER SERVICE
 BACKFLOW PREVENTER- SEC. 105.1 & 107.2.1 WPB. PLEASE
 ADD THE DEVICE TO THE LIST OF SEPARATE PERMITS ON SHEET
 C-1. SHEET C-1 WITH MODIFED SEPARATE PERMIT LIST NOT
 UPLOADED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-01-20 Cont ID  
Sent By ccole Date 2022-01-20 Time 17:41 Rev Time 0.00
Received By ccole Date 2022-01-20 Time 11:52 Sent To  
Notes
2022-01-20 17:43:361ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22010129
 1/20/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS C-1, 1.3A, 3.0P: PROVIDE PLUMBING FIXTURE
 CALCULATIONS IN COMPLIANCE WITH TABLE 403.1 FBC P.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED NUMBER OF PLUMBING FIXTURES. PLEASE CLARIFY
 WHICH OCCUPANT LOAD IS CORRECT- (161 OCCUPANTS- SHEET
 C-1) OR (178 OCCUPANTS- SHEET 1.3A). PLEASE NOTE THAT
 DRINKING FOUNTAINS ARE REQUIRED FIXTURES FOR ASSEMBLY
 AND BUSINESS OCCUPANCIES. SHOW THE LOCATION OF THE
 REQUIRED DRINKING FOUNTAINS OR PLACE A NOTE TO INDICATE
 DRINKING WATER IN A CONTAINER FREE OF CHARGE WILL BE
 PROVIDED- SEC.- 410.4 FBC P.
  
 2) SHEETS 1.0A, 1.3A, 3.0P, 3.1P: SHEET 1.3A INDICATES
 A 1390 SQ. FT. BREWERY. SHOW THE LOCATION OF THE
 BREWERY AND PROVIDE AN EQUIPMENT PLAN AND SCHEDULE-
 SEC. 107.2.1 WPB.
  
 3) SHEET 1.0A- MISSING ACCESSIBILITY DETAILS PER FBC
 ACC:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SEC. 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SEC. 606.2.
 C) TURNING SPACE DIAMETERS- SEC. 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SEC. 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SEC. 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SEC. 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SEC. 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS ? SEC.
 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) HEIGHT AND DEPTH OF THE ACCESSIBLE URINAL- SEC.
 605.2
 L) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 ACCESSIBLE URINAL- SEC. 605.3.
 M) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC.
 606.2
  
 4) SHEET 1.0A: PROVIDE THE DEPTH MEASUREMENTS OF THE
 STANDARD RESTROOM STALLS- SEC. 405.3.1 FBC P.
  
 5) SHEET 3.0P: PROVIDE GREASE WASTE CALCULATIONS IN
 COMPLIANCE WITH SEC. 1003.3.5 FBC P. PLEASE ADD THE
 GREASE INTERCEPTOR TO THE LIST OF SEPARATE PERMITS ON
 SHEET C-1. NOTE: COMPLETE GREASE INTERCEPTOR PLANS,
 EQUIPMENT SPECIFICATIONS, CALCULATIONS AND DETAILS WILL
 BE REQUIRED UNDER THE SEPARATE PERMIT.
  
 6) SHEETS 3.0P & 3.1P: SHOW THE LOCATION OF THE GREASE
 INTERCEPTOR SAMPLING PORT AND INDICATE ACCESS WILL BE
 PROVIDED TO THE INTERCEPTOR COVERS AND CLEANOUTS- SECS.
 708.1.7 & 708.1.10 FBC P.
  
 7) SHEET 3.0P: THE LOCATION OF THE FLOOR SINK IN THE
 DETAIL DOES NOT MATCH THE LOCATION ON THE PLAN. THE
 PLAN SHOWS THE FLOOR SINK BETWEEN THE FOOD HANDLING
 (3-COMPARTMENT) SINK AND THE WARE WASHER- SEC. 802.1.1
 AND 802.3 FBC P. PLEASE INCLUDE THE FLOOR SINKS IN THE
 PLUMBING FIXTURE SCHEDULE- SECS. 414.1 & 802.4 FBC P.
  
 8) SHEETS 3.0P & 3.1P: PROVIDE VENTS FOR THE FLOOR
 SINKS AND FLOOR DRAINS IN THE KITCHEN AREA- SEC. 802.3
 FBC P AND THE FLOOR DRAIN IN THE MEN'S RESTROOM- SECS.
 910 & 911 FBC P.
  
 9) SHEETS 3.0P & 3.1P: THE PLAN SHOWS 3/4-INCH SUPPLY
 LINES TO THE URINALS, AND THE RISER SHOWS 1-INCH- SEC.
 107.2.1 WPB. PLEASE NOTE A COMPLETE REVIEW OF THE
 PLUMBING PLANS CANNOT BE COMPLETED WITH A PLUMBING
 FIXTURE SCHEDULE- TABLE 604.5 FBC P.
  
 10) SHEETS 3.0P & 3.1P: SHOW LOCATIONS OF REQUIRED
 BACKFLOW PREVENTERS FOR SUPPLY LINES CONNECTING TO THE
 WARE WASHER, GLASS WASHER, AND ICE MAKERS- SEC. 608.3
 FBC P.
  
 11) SHEETS 3.0P & 3.1P: A RECIRCULATION PUMP IS SHOWN
 BUT THERE IS A NOTE INDICATING A RECIRCULATING WATER
 HEATER. WHICH RECIRCULATION SYSTEM WILL BE USED?- SEC.
 607.1 FBC P.
  
 12) SHEETS 3.0P & 3.1P: PLEASE NOTE A SEPARATE PERMIT
 IS REQUIRED FOR THE POTABLE WATER SERVICE BACKFLOW
 PREVENTER- SEC. 105.1 & 107.2.1 WPB. PLEASE ADD THE
 DEVICE TO THE LIST OF SEPARATE PERMITS ON SHEET C-1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status P Date 2022-04-10 Cont ID  
Sent By rgathrig Date 2022-04-10 Time 12:13 Rev Time 0.00
Received By rgathrig Date 2022-04-10 Time 12:13 Sent To  
Notes
2022-04-10 12:14:08PRIVATE PROVIDER INSPECTIONS ONLY APPROVED
  
 RICHARD GATHRIGHT
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2022-03-18 Cont ID  
Sent By rgathrig Date 2022-03-18 Time 12:46 Rev Time 0.00
Received By rgathrig Date 2022-03-18 Time 12:46 Sent To  
Notes
2022-03-18 12:51:18PRIVATE PROVIDER INSPECTIONS ONLY RREVIEW FAILED
 THE NTOB IS ONLY DOCUEMNT PROVIDED
 NEEC COI AND PP RESUMES PER 553.791 (4)(B)
  
 RICHARD GATHRIGHT
 ASSISTANT BUILDING OFFICIAL
 561 805 6679

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-05-02 Cont ID  
Sent By rmcphers Date 2022-05-02 Time 11:15 Rev Time 0.00
Received By rmcphers Date 2022-05-02 Time 11:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-03-23 Cont ID  
Sent By rmcphers Date 2022-03-23 Time 11:34 Rev Time 0.00
Received By rmcphers Date 2022-03-23 Time 11:34 Sent To  
Notes
2022-03-23 11:37:33SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) THE TEMPORARY CONSTRUCTION SERVICE DRAWING SIGNED
 AND SEALED BY THOMAS J. TWOMEY P.E. DOES NOT SHOW AS
 DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-02-04 Cont ID  
Sent By rmcphers Date 2022-02-04 Time 10:33 Rev Time 0.00
Received By rmcphers Date 2022-02-04 Time 10:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2022-05-04 Cont ID  
Sent By aaponte Date 2022-05-04 Time 08:20 Rev Time 0.00
Received By aaponte Date 2022-05-04 Time 08:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2022-04-13 Cont ID  
Sent By aaponte Date 2022-04-13 Time 13:31 Rev Time 0.00
Received By aaponte Date 2022-04-13 Time 13:31 Sent To  
Notes
2022-04-13 13:35:101. SATISFIED - PLEASE PROVIDE A SURVEY OF THE PROPERTY.
 2. NOT SATISFIED- PLEASE PROVIDE DATA TO INDICATE THE
 TOTAL SQUARE FOOTAGE OF THE EXISTING BUILDING AND IF
 ANY ADDITIONAL SQUARE FOOTAGE IS PROPOSED (RELOCATE
 MAIN ENTRANCE)
 3. NOT SATISFIED- CANOPY MINIMUMPROJECTION IS 8 FEET.
 PROPOSED CANOPY IS ONLY 4 FEET.
 4. SATISIFED - PROVIDE DEMOLITION PLANS.
 5. SATISFIED - GARBAGE LOCATION NOT PROVIDED ON SITE. -
 PLEASE PROVIDE INFORMATION REGARDING PROPOSED LOCATION
 FOR GARBAGE COLLECTION.
 6. ANY NEW MECHANICAL EQUIPMENT LOCATED ON ROOF SHALL
 BE SCREEN.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439

Review Stop Z ZONING
Rev No 1 Status F Date 2022-01-27 Cont ID  
Sent By aaponte Date 2022-01-27 Time 16:52 Rev Time 0.00
Received By aaponte Date 2022-01-27 Time 16:51 Sent To  
Notes
2022-01-27 16:56:111. PLEASE PROVIDE A SURVEY OF THE PROPERTY.
 2. PLEASE PROVIDE DATA TO INDICATE THE TOTAL SQUARE
 FOOTAGE OF THE EXISTING BUILDING AND IF ANY ADDITIONAL
 SQUARE FOOTAGE IS PROPOSED (RELOCATE MAIN ENTRANCE)
 3. PROVIDE INFORMATION REGARDING THE PROPOSED CANOPY
 INCLUDING HEIGHT, PROJECTION.
 4. PROVIDE DEMOLITION PLANS.
 5. PLEASE PROVIDE INFORMATION REGARDING PROPOSED
 LOCATION FOR GARBAGE COLLECTION.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439