Plan Review Details - Permit 22010018
Plan Review Stops For Permit 22010018
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-03-07 Cont ID  
Sent By jgomez Date 2022-03-07 Time 15:34 Rev Time 0.00
Received By jgomez Date 2022-03-07 Time 15:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-03-07 Cont ID  
Sent By jgomez Date 2022-03-07 Time 12:50 Rev Time 0.00
Received By jgomez Date 2022-03-07 Time 10:50 Sent To  
Notes
2022-03-07 12:50:56RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22010018
  
 1- WOOD FRAMED WALLS:
 A) REVISE WALL SHEATHING NAILING SPECIFICATIONS TO SHOW
 COMPLIANCE WITH SEC. R703.3.1 FBC-RESIDENTIAL.
  
 2-OK.
  
 3- PROVIDE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. 107.2.1
 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-03-03 Cont ID  
Sent By jgomez Date 2022-03-03 Time 15:25 Rev Time 0.00
Received By jgomez Date 2022-03-03 Time 15:25 Sent To  
Notes
2022-03-03 16:18:51RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22010018
  
 NOTE:
 LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING.
 SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL
 COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN
 THE FLORIDA BUILDING CODE.
  
 1- WOOD FRAMED WALLS:
 A) REMOVING EXISTING CLAPBOARD. NEED TO SPECIFY WALL
 SHEATHING TO RECEIVE THE NEW STUCCO. SPECIFY WALL
 SHEATHING MATERIAL, THICKNESS AND FASTENING. SEC.
 R703.1.2 FBC-RESIDENTIAL.
  
 B) NEED TO SPECIFY STUCCO BASE (LATH OR ANY OTHER
 STUCCO BASE) AS REQUIRED BY SEC. R703.7 FBC-RESIDENTIAL
 AND TABLE R702.1(1) FBC-RESIDENTIAL.
  
 C) NEED TO SPECIFY THE MIN. STUCCO THICKNESS AS
 REQUIRED BY SEC. R703.7 FBC-RESIDENTIAL AND TABLE
 R702.1(1) FBC-RESIDENTIAL.
  
 D)NEED TO SPECIFY TWO WATER RESISTIVE BARRIERS WHEN
 STUCCO IS APPLIED TO WOOD AS REQUIRED BY SEC. R703.7.3
 FBC-RESIDENTIAL.
  
 2- DRAWINGS SUBMITTED SHOW TWO NORTH ELEVATIONS. IT
 LOOKS LIKE THERE IS A TYPO. ONE OF THEM SHOULD BE THE
 SOUTH ELEVATION. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 3- PROVIDE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. 107.2.1
 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-03-07 Cont ID  
Sent By jgomez Date 2022-03-07 Time 15:34 Rev Time 0.00
Received By jgomez Date 2022-03-07 Time 15:25 Sent To I
Notes
2022-03-07 15:26:05RECEIVED REVISED PLANS FROM RICHARD MCDONALD. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-07 Cont ID  
Sent By jgomez Date 2022-03-07 Time 12:50 Rev Time 0.00
Received By jgomez Date 2022-03-07 Time 10:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-03 Cont ID  
Sent By jgomez Date 2022-03-03 Time 16:22 Rev Time 0.00
Received By jgomez Date 2022-01-04 Time 14:02 Sent To I
Notes
***NONE***