Plan Review Details - Permit 21121225
Plan Review Stops For Permit 21121225
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-05-16 Cont ID  
Sent By jgomez Date 2022-05-16 Time 14:06 Rev Time 0.00
Received By jgomez Date 2022-05-16 Time 13:41 Sent To  
Notes
2022-05-16 14:07:02BUILDING REVIEW APPROVED WITH PROVISO:
 (NOTE: SUBMIT INFORMATION PRIOR TO
 INSTALLATION/INSPECTION TO AVOID CONFLICTS/DELAYS):
  
 1- PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR THE
 CONSTRUCTION OF ALL HANDRAILS AND GUARDRAILS SHOWING
 COMPLIANCE WITH TABLE R301.5, SEC. R311.7.8 AND SEC.
 R312.1 FBC-RESIDENTIAL.
  
 2- WINDOW FALL PROTECTION IS REQUIRED ON SECOND FLOOR
 OPERABLE WINDOWS WHERE WINDOW SILL IS LESS THAN 24"
 ABOVE FINISHED FLOOR. SEC. R312.2 FBC RESIDENTIAL.
 NOTE: CLEARLY INDICATE THE WINDOW SILL HEIGHT AND
 SPECIFY TYPE OF WINDOW FALL PROTECTION IF REQUIRED.
  
 3- PRODUCT APPROVALS:
 PROVIDE PRODUCT APPROVAL FOR FIXED WINDOW SIZE 74"X180"
 AS SHOWN ON PLANS.
  
 4-ENGINEER OF RECORD TO REVIEW/APPROVE ABOVE PRODUCT
 APPROVALS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-04-25 Cont ID  
Sent By jgomez Date 2022-04-25 Time 10:14 Rev Time 0.00
Received By jgomez Date 2022-04-25 Time 09:48 Sent To  
Notes
2022-04-25 10:15:20BUILDING APPROVED WITH PROVISO:
 (NOTE: PROVIDE INFORMATION FOR REVIEW BEFORE
 INSTALLATION TO AVOID CONFLICTS/DELAYS):
 1- PROVIDE COMPLETE DETAILS/SPECS FOR THE CONSTRUCTION
 HANDRAILS AND GUARDRAILS, INCLUDING TERRACE GUARDRAIL
 SHOWING COMPLIANCE WITH TABLE R301.5, SEC. R311.7.8 AND
 SEC. R312.1 FBC-RESIDENTIAL.
  
 2-WINDOW FALL PROTECTION SHALL BE PROVIDED ON SECOND
 FLOOR WINDOWS WHERE THE TOP OF THE WINDOW SILL OF AN
 OPERABLE WINDOW IS LOCATED LESS THAN 24" ABOVE THE
 FINISHED FLOOR . SEC. R312.2 FBC RESIDENTIAL.
 NOTE: CLEARLY INDICATE THE WINDOW SILL HEIGHT OF SECOND
 FLOOR WINDOWS AND SPECIFY TYPE OF WINDOW FALL
 PROTECTION IF REQUIRED.
  
 3-PROVIDE PRODUCT APPROVAL FOR:
 A)FIXED WINDOW SIZE 74"X180" AS SHOWN ON PLANS.
 B)TERRACE FLOORING UNDERLAYMENT DESIGNED TO RECEIVE
 PAVERS.
  
 4-ENGINEER OF RECORD TO REVIEW/APPROVE PRODUCT
 APPROVALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-04-20 Cont ID  
Sent By jgomez Date 2022-04-20 Time 13:26 Rev Time 0.00
Received By jgomez Date 2022-04-20 Time 09:15 Sent To  
Notes
2022-04-20 13:26:50RESIDENTIAL (R3) ALTERATION SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21121225
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
 1- OK.
 2- OK.
 3- OK.
 4- OK.
  
 ORIGINAL COMMENT:
 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF ALL NEW HANDRAILS AND GUARDRAILS,
 INCLUDING TERRACE GUARDRAIL SHOWING COMPLIANCE WITH
 TABLE R301.5, SEC. R311.7.8 AND SEC. R312.1
 FBC-RESIDENTIAL.
 NOTE: IF THIS IS A DEFERRED SUBMITTAL, THEN SPECIFY THE
 DESIGN GUIDELINES REQUIRED BY TABLE R301.5, SEC.
 R311.7.8 AND SEC. R312.1 AND CLEARLY SPECIFY ON PLANS
 THAT SHOP DRAWINGS NEED TO BE SUBMITTED FOR REVIEW
 PRIOR TO CONSTRUCTION. ALL SHOP DRAWINGS TO BE REVIEWED
 BY THE DESIGN PROFESSIONAL OF RECORD PRIOR TO SUBMITTAL
 TO THIS OFFICE.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. ENGINEER'S NOTE ON PLANS
 STATING "GRASPABLE ALUMINUM GUARDRAIL INSTALLED AS PER
 MANUFACTURER'S INSTRUCTIONS & AS PER CODE" IS NOT
 ACCEPTABLE. IF ENGINEER IS NOT DESIGNING THE GUARDRAIL,
 THEN HE NEEDS TO SPECIFY ALL THE DESIGN GUIDELINES AS
 REQUESTED ABOVE NOT CITING THE CODE AS A WHOLE OR IN
 PART. SEC. 107.2.1 CITY AMENDMENTS.
  
 6- OK.
 7- OK.
 8- OK.
  
 ORIGINAL COMMENT:
 9- WINDOW FALL PROTECTION SHALL BE PROVIDED ON SECOND
 FLOOR WINDOWS WHERE THE TOP OF THE WINDOW SILL OF AN
 OPERABLE WINDOW IS LOCATED LESS THAN 24" ABOVE THE
 FINISHED FLOOR . SEC. R312.2 FBC RESIDENTIAL.
 NOTE: CLEARLY INDICATE THE WINDOW SILL HEIGHT OF SECOND
 FLOOR WINDOWS AND SPECIFY TYPE OF WINDOW FALL
 PROTECTION IF REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. RESPONSE LETTER STATES THAT "IMPACT
 RATED WINDOWS MEET ALL WINDOW FALL PROTECTION
 REQUIREMENTS". THIS STATEMENT IS INCORRECT. IMPACT
 RATED WINDOWS AND WINDOW FALL PROTECTION ARE TWO
 DIFFERENT THINGS. ENGINEER OF RECORD TO READ SEC.
 R312.2 FBC RESIDENTIAL AND COMPLY AS REQUESTED.
  
 10- PRODUCT APPROVALS:
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 ORIGINAL COMMENT:
 A)FIXED WINDOW SIZE 74"X180" AS SHOWN ON PLANS.
  
 RESPONSE:
 REPEAT COMMENT. NOA 20-1223.01 SUBMITTED DOESN'T COVER
 THIS WINDOW SIZE.
  
 B)OK. IF ALL DOORS AND WINDOWS HAVE IMPACT GLAZING.
  
 C) TERRACE FLOORING UNDERLAYMENT DESIGNED TO RECEIVE
 PAVERS A SPECIFIED ON DETAIL 1/S-0 ON SHEET S100.
  
 11-ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
 ORIGINAL COMMENT:
 12-VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW BASED ON ALL SCOPE OF WORK TO BE DONE. VALUATION TO
 INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND
 PROFIT AND DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC.
 109.3 CITY AMENDMENTS. REVISE VALUATION TO INCLUDE
 COMPLETE SCOPE OF WORK OR PROVIDE COMPLETE BREAKDOWN
 INCLUDING DESIGN PROFESSIONAL FEES FOR BUILDING
 OFFICIAL APPROVAL.
  
 RESPONSE:
 REPEAT COMMENT. VALUE OF $47,300 STILL WAY TOO LOW FOR
 ALL THE SCOPE OF WORK SHOWN ON PLANS AND FOR DESIGN
 PROFESSIONAL FEES.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-03-11 Cont ID  
Sent By jgomez Date 2022-03-11 Time 18:35 Rev Time 0.00
Received By jgomez Date 2022-03-10 Time 16:53 Sent To  
Notes
2022-03-11 14:15:00RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21121225
  
 NOTE:
 LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING.
 SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 1-ALTERATION LEVEL FOR THIS PROJECT IS LEVEL 3 NOT
 LEVEL 2. REVISE INFORMATION ON PLANS AS REQUIRED. SEC.
 604 FBC-EXISTING BUILDING.
  
 2-PROPOSED FIRST FLOOR PLAN ON SHEET A100 SHOWS WHAT
 SEEMS TO BE A BREEZEWAY CONNECTION BETWEEN THE MAIN
 HOUSE AND THE GARAGE. INFORMATION IS INCOMPLETE.
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THIS STRUCTURE. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 3-PROPOSED FIRST FLOOR PLAN ON SHEET A100 SHOWS NEW
 PRIVACY WALL BETWEEN THEE MAIN HOUSE AND THE GARAGE.
 WHERE IS DETAIL 4/S-2? SEC. R301.2.1 FBC-RESIDENTIAL.
  
 4- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR ALL NEW EXTERIOR DOORS AND WINDOWS. NOTE: SPECIFY
 ALL FRAMING MEMBERS AND CONNECTORS. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF ALL NEW HANDRAILS AND GUARDRAILS,
 INCLUDING TERRACE GUARDRAIL SHOWING COMPLIANCE WITH
 TABLE R301.5, SEC. R311.7.8 AND SEC. R312.1
 FBC-RESIDENTIAL.
 NOTE: IF THIS IS A DEFERRED SUBMITTAL, THEN SPECIFY THE
 DESIGN GUIDELINES REQUIRED BY TABLE R301.5, SEC.
 R311.7.8 AND SEC. R312.1 AND CLEARLY SPECIFY ON PLANS
 THAT SHOP DRAWINGS NEED TO BE SUBMITTED FOR REVIEW
 PRIOR TO CONSTRUCTION. ALL SHOP DRAWINGS TO BE REVIEWED
 BY THE DESIGN PROFESSIONAL OF RECORD PRIOR TO SUBMITTAL
 TO THIS OFFICE.
  
 6- ACCORDING TO NOTE A OF FIGURE R301.2(7)
 FBC-RESIDENTIAL ALL OPENINGS WITHIN 4'-0" OF THE EDGE
 OF THE BUILDING ARE CONSIDERED END ZONE. REVISE
 INFORMATION ON ALL DOORS/WINDOWS ON ALL PROPOSED
 ELEVATIONS AS REQUIRED TO REFLECT END ZONE. NOTE: ALSO,
 REVISE SQUARE FOOTAGE OF FIXED WINDOWS. THEY SHOULD BE
 KEYED AS 1 NOT 2.
  
 7- SHEET S100:
 A)NEED TO PROVIDE STRUCTURAL DETAIL/SPECIFICATIONS FOR
 ATTACHMENT AT EACH END OF NEW FLOOR JOIST AT NEW
 LOGGIA. SEC. R301.1 FBC-RESIDENTIAL.
  
 B)NEED TO SPECIFY NAIL TYPE, SIZE AND SPACING FOR THE
 SPECIFIED 5/8" ZIP SYSTEM SHEATHING ON DETAIL 1/S-0.
 SEC. R301.2.1 FBC-RESIDENTIAL.
 SEC. R803.2.3.1 AND TABLE R803.2.3.1 FBC-RESIDENTIAL.
  
 8- NEED TO SPECIFY CARBON MONOXIDE ALARM WITHIN ALL
 SLEEPING ROOMS, INCLUDING EXISTING BEDROOMS AS REQUIRED
 BY SEC. R315.1 FBC-RESIDENTIAL.
  
 9- WINDOW FALL PROTECTION SHALL BE PROVIDED ON SECOND
 FLOOR WINDOWS WHERE THE TOP OF THE WINDOW SILL OF AN
 OPERABLE WINDOW IS LOCATED LESS THAN 24" ABOVE THE
 FINISHED FLOOR . SEC. R312.2 FBC RESIDENTIAL.
 NOTE: CLEARLY INDICATE THE WINDOW SILL HEIGHT OF SECOND
 FLOOR WINDOWS AND SPECIFY TYPE OF WINDOW FALL
 PROTECTION IF REQUIRED.
  
 10- PRODUCT APPROVALS:
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)FIXED WINDOW SIZE 74"X180" AS SHOWN ON PLANS.
 B)HURRICANE SHUTTERS IF ABOVE WINDOW DOESN'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 C)NEW BREEZEWAY FINISH ROOFING AND UNDERLAYMENT.
 COORDINATE WITH PLANS.
 D)TERRACE FLOORING UNDERLAYMENT DESIGNED TO RECEIVE
 PAVERS A SPECIFIED ON DETAIL 1/S-0 ON SHEET S100.
  
 11-ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
 12-VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW BASED ON ALL SCOPE OF WORK TO BE DONE. VALUATION TO
 INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND
 PROFIT AND DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC.
 109.3 CITY AMENDMENTS. REVISE VALUATION TO INCLUDE
 COMPLETE SCOPE OF WORK OR PROVIDE COMPLETE BREAKDOWN
 INCLUDING DESIGN PROFESSIONAL FEES FOR BUILDING
 OFFICIAL APPROVAL.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-05-19 Cont ID  
Sent By fgiaquin Date 2022-05-19 Time 22:17 Rev Time 0.00
Received By fgiaquin Date 2022-05-19 Time 19:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-04-18 Cont ID  
Sent By fgiaquin Date 2022-04-18 Time 22:13 Rev Time 0.00
Received By fgiaquin Date 2022-04-18 Time 20:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-01-25 Cont ID  
Sent By fgiaquin Date 2022-01-25 Time 12:51 Rev Time 0.00
Received By fgiaquin Date 2022-01-25 Time 10:53 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2022-05-09 Cont ID  
Sent By rwbrown Date 2022-05-09 Time 09:08 Rev Time 0.00
Received By rwbrown Date 2022-05-09 Time 09:08 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2022-04-07 Cont ID  
Sent By lcrespo Date 2022-04-07 Time 08:30 Rev Time 0.00
Received By lcrespo Date 2022-04-06 Time 07:30 Sent To  
Notes
2022-04-07 08:31:0404/07/22 2ND GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 1. ON SHEET P101;
  
 A. THE ARE TWO DIFFERENT SETS OF SYSTEMS ON THIS PAGE,
 ONE SHOWS AN LP TANK, AND IT ALSO INDICATES A GAS
 METER. WOULD YOU PLEASE CLARIFY BY SHOWING THE SYSTEM
 LP OR GAS PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. THERE SEEMS TO BE A NEW LINE FOR THE DRYER AND THE
 GENERATOR THAT IS NOT SHOWN IN THE ISOMETRIC GAS RISER.
 WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS.
  
 C. THERE IS A GAS POOL HEATER, AND IT DOES NOT SHOW ANY
 GAS LINE TO IT. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 D. THIS TANK-LESS UNIT CALL FOR A 10.5" WATER COLUMN,
 AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN
 REQUIRING A REGULATOR FOR THIS UNIT AS PER THE
 MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER?S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES.
 SEC. G2421.1 OR 410.1.
  
 E. WOULD YOU PLEASE SUBMIT THE MANUFACTURER'S
 SPECIFICATION SHEETS/INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH 2020 FBC FG SEC.
 305.1 OR 2020 FBC RES. SEC. G2408.1. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES/EQUIPMENT SHALL BE ONSITE AT THE
 TIME OF INSPECTION PER THE 2020 FBC RES. SEC. G2413.2
 AND G2404.3
 .
 F. THERE IS A GAS TANKLESS SHOWN ON THE ISOMETRIC BUT
 NOT SHOWN IN THE FLAT DRAWING. WOULD YOU PLEASE CORRECT
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 G. WOULD YOU PLEASE SHOW ON THE HOUSE PLAN THE LOCATION
 OF THE TANK-LESS WATER HEATER AND THE LOCATION AND
 DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN RELATION
 TO THE WATER HEATER. THE LOCATION OF THE WATER HEATER
 SHALL COMPLY WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND-DRAWN PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 H. WOULD YOU PLEASE SUBMIT COMBUSTION AIR CALCULATIONS
 FOR THE ADDED GAS DRYER APPLIANCES. WHERE DOES THE
 BUILDING'S MECHANICAL VENTILATION SYSTEM PROVIDE
 COMBUSTION AIR? THE SYSTEM SHALL PROVIDE THE SPECIFIED
 COMBUSTION AIR RATE IN ADDITION TO THE REQUIRED
 VENTILATION AIR PER THE FBC RES. SEC. G2407.9.3.
 COMBINED COMBUSTION AIR AND VENTILATION AIR SYSTEM.
  
 I. IF LOUVERS ARE USED, LOUVERS THAT ARE BEING
 INSTALLED FOR THE COMBUSTION AIR SHOW THE LOUVERS'
 LOCATION. THE LOUVERS CANNOT BE LOCATED ON AN EXTERIOR
 WALL THAT IS FIRE RATED AS THE FIRE RATING OF THE WALL
 MUST BE MAINTAINED PER THE WPB AMENDMENTS TO FBC
 SEC.107.2.1.
  
 J. WOULD YOU PLEASE SHOW THE TYPE OF PIPE MATERIAL
 BEING INSTALLED, LABEL ALL PIPE SIZES, AND THE
 CORRESPONDING EHD NUMBER OF THE CORRUGATED
 STAINLESS-STEEL TUBING (IF APPLICABLE) FOR EACH PIPE
 SIZE PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 K. WOULD YOU PLEASE SHOW THE LOCATION OF ALL MP
 (STEP-DOWN) REGULATORS. A LISTED SHUTOFF VALVE SHALL BE
 INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR PER
 THE 2020 FBC RES. SEC. G2420.4.
  
 L. THE BTU'S LOAD IS INCORRECT. WOULD YOU PLEASE SHOW
 THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD
 ON THE SYSTEM? REFER TO THE 2020 FBC RES. SEC. G2413.
  
 M. WOULD YOU PLEASE CORRECT THE DISTANCE FROM THE POINT
 OF DELIVERY (GAS METER / MP REGULATOR / LP TANK) TO THE
 MOST REMOTE OUTLET IN THE BUILDING AND/OR SYSTEM PER
 THE 2020 FBC RES. SEC. G2413.4.1.
  
 N. ON THE GAS NOTES, IT REFERS TO THE 2014 FUEL GAS
 CODE, AND THE CURRENT IS 2020 FBC 7 EDITION FUEL GAS.
 WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 O. WOULD YOU PLEASE SHOW ALL UNIONS IN FRONT OF
 REGULATOR 1' OF EITHER SIDE PER THE FBC RES. SEC
 G2421.2.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2022-01-10 Cont ID  
Sent By lcrespo Date 2022-01-10 Time 09:38 Rev Time 0.00
Received By lcrespo Date 2022-01-10 Time 09:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-06-21 Cont ID  
Sent By mpeterso Date 2022-06-21 Time 08:29 Rev Time 0.00
Received By mpeterso Date 2022-06-13 Time 15:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-05-19 Cont ID  
Sent By fgiaquin Date 2022-05-19 Time 22:18 Rev Time 0.00
Received By fgiaquin Date 2022-05-06 Time 08:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-04-25 Cont ID  
Sent By jgomez Date 2022-04-25 Time 10:25 Rev Time 0.00
Received By jgomez Date 2022-04-21 Time 14:27 Sent To I
Notes
2022-04-21 14:29:0604/21/22 RECEIVED EMAIL FROM JULIAN GUTIERREZ. OK TO
 PROVISO BUILDING REVIEW. JG.
  
 HELLO MR. GOMEZ,
 AS PER OUR CONVERSATION, PLEASE SEE ATTACHED DOCUMENTS
 REQUESTED. WE WOULD LIKE TO DO THE REVIEW WITH A
 PROVISO AND PROVIDE THE PENDING CORRECTIONS AFTER THE
 PERMIT IS ISSUED. THE NEW VALUATION FOR THE JOB WILL BE
 $79.500. PLEASE LET US KNOW IF YOU HAVE ANY QUESTIONS.
 THANK YOU,
 JULIAN GUTIERREZ
 DIVERSIFIED CONTRACTORS LLC
 PH (919) 244-0871
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-04-20 Cont ID  
Sent By jgomez Date 2022-04-20 Time 13:36 Rev Time 0.00
Received By jgomez Date 2022-04-05 Time 07:59 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-11 Cont ID  
Sent By jgomez Date 2022-03-11 Time 14:22 Rev Time 0.00
Received By jgomez Date 2022-01-04 Time 06:25 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-06-08 Cont ID  
Sent By lmarchan Date 2022-06-08 Time 16:00 Rev Time 0.00
Received By lmarchan Date 2022-04-21 Time 14:51 Sent To  
Notes
2022-06-08 13:51:23RECEIPT MU-2022-18417 - $546.52 PAID
2022-04-21 14:51:304/21/22 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-03-11 Cont ID  
Sent By jgomez Date 2022-03-11 Time 14:21 Rev Time 0.00
Received By jgomez Date 2022-03-11 Time 14:19 Sent To  
Notes
2022-03-11 14:22:03IMPACT FEES
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2022-06-14 Cont ID  
Sent By medwards Date 2022-06-14 Time 06:17 Rev Time 0.00
Received By medwards Date 2022-06-14 Time 06:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-05-11 Cont ID  
Sent By medwards Date 2022-05-11 Time 11:09 Rev Time 0.00
Received By medwards Date 2022-05-11 Time 11:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-04-15 Cont ID  
Sent By medwards Date 2022-04-11 Time 10:54 Rev Time 0.00
Received By medwards Date 2022-04-11 Time 10:54 Sent To  
Notes
2022-04-11 10:55:09 
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-01-05 Cont ID  
Sent By medwards Date 2022-01-05 Time 13:20 Rev Time 0.00
Received By medwards Date 2022-01-05 Time 13:16 Sent To  
Notes
2022-01-05 13:20:50THE PLANS SUBMITTED HAVE 2 SEPERATE AND DIFFERENT
 DESIGNS, ONE IS FROM ON TARGET DESIGNS AND THE OTHER IS
 FROM K.O. ENERGY DESIGN. PLEASE REMOVE ONE AND SUBMIT
 FOR REVIEW. I CANNOT DO A MECHANICAL REVIEW AS THERE
 ARE DIFERENCES BETWEEN THE DRAWINGS. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-05-09 Cont ID  
Sent By rwbrown Date 2022-05-09 Time 09:07 Rev Time 0.00
Received By rwbrown Date 2022-05-09 Time 09:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2022-04-08 Cont ID  
Sent By lcrespo Date 2022-04-08 Time 13:14 Rev Time 0.00
Received By lcrespo Date 2022-04-06 Time 07:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-01-10 Cont ID  
Sent By lcrespo Date 2022-01-10 Time 09:38 Rev Time 0.00
Received By lcrespo Date 2022-01-10 Time 09:17 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2022-04-25 Cont ID  
Sent By jgomez Date 2022-04-25 Time 10:21 Rev Time 0.00
Received By jgomez Date 2022-04-25 Time 10:21 Sent To  
Notes
2022-04-25 10:21:51NO ROOFING ON THIS PROJECT.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2022-04-25 Cont ID  
Sent By jgomez Date 2022-04-20 Time 13:30 Rev Time 0.00
Received By jgomez Date 2022-04-20 Time 13:30 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2022-03-11 Cont ID  
Sent By jgomez Date 2022-03-11 Time 14:15 Rev Time 0.00
Received By jgomez Date 2022-03-11 Time 14:15 Sent To  
Notes
2022-03-10 17:54:35ROOFING REVIEW:
  
 1- PRODUCT APPROVALS:
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)NEW BREEZEWAY FINISH ROOFING AND UNDERLAYMENT.
 COORDINATE WITH PLANS.
  
 B)TERRACE FLOORING UNDERLAYMENT DESIGNED TO RECEIVE
 PAVERS A SPECIFIED ON DETAIL 1/S-0 ON SHEET S100.
  
 2--ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2022-06-21 Cont ID  
Sent By mpeterso Date 2022-06-21 Time 08:26 Rev Time 0.00
Received By mpeterso Date 2022-06-21 Time 08:26 Sent To  
Notes
2022-06-21 08:29:34IT APPEARS THER WERE MORE THAN ONE SUBMISSION OF PAPER
 DOCUMENTS THAT DID NOT CONTAIN ALL DRAWINGS. IT APPEARS
 SOME DRAWINGS PASSED SIGNATURE REVIEW AT DIFFERENT
 TIMES. IT NOW APPEARS THAT ALL DRAWINGS ARE SIGNED AND
 SEALED.MP

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2022-06-07 Cont ID  
Sent By pvalenti Date 2022-06-07 Time 15:31 Rev Time 0.00
Received By pvalenti Date 2022-06-07 Time 15:31 Sent To  
Notes
2022-06-07 15:50:09 
  
 SIGNATURE REVIEW DENIED:
  
 PAPER PLAN SHEETS WERE SUBMITTED WITH HAND SIGNATURES
 BY PROFESSIONAL ENGINEER, RONALD W. GUSTAINUS. PLAN
 SHEETS: AC 100, AC 102 & M.1 ARE MISSING. THESE PLAN
 SHEETS ARE NOT LISTED UNDER THE INDEX ON PAPER PLAN
 SHEET A000. HOWEVER, THOSE PLAN SHEETS WERE PART OF THE
 SET THAT WAS SUBMITTED INTO PROJECT DOX AND REVIEWED.
 PLEASE PROVIDE RESPONSE AND SUBMIT HAND SIGNED PAPER
 SHEETS AC 100, AC 102, M.1 & CORRECTED, HAND SIGNED
 PAPER, INDEX PLAN SHEET A000.
 THE SUBMITTED PAPER PLAN SHEETS HAVE BEEN ROUTED TO THE
 MIXED BOX AT THE RECORDS RETENTION SPECIALISTS OFFICE.
  
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
 UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY
 VERIFIED) PLAN OR YOU CAN DELIVER AN ORIGINAL
 SIGNED/SEALED PAPER ORIGINAL TO:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 FEEL FREE TO CONTACT ME AT 561 805 6673.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2022-05-16 Cont ID  
Sent By jgomez Date 2022-05-16 Time 14:19 Rev Time 0.00
Received By jgomez Date 2022-05-16 Time 14:19 Sent To  
Notes
2022-05-16 14:19:38SIGNATURE REVIEW:
  
 1- ALL DRAWINGS HAVE A COPY OF THE ENGINEER'S SEAL AND
 SIGNATURE. ALL DRAWINGS NEED THE ORIGINAL SEAL AND
 SIGNATURE OF THE ENGINEER AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTES WHEN SUBMITTING DOCUMENTS/PLANS FOR
 PUBLIC RECORDS.
  
 NOTE: SUBMIT DRAWINGS ELECTRONICALLY WITH ENGINEER'S
 DIGITAL SIGNATURE OR PROVIDE HARD COPY WITH ENGINEER'S
 ORIGINAL SEAL AND SIGNATURE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
2022-05-11 11:11:38THE MECHANICAL DOCUMENTS HAVE A COPY OF THE ENGINEERS
 WET SEAL. THE ORIGINAL WET SEAL WOULD NEED TO BE
 SUBMITTED TO OUR OFFICE. ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-04-25 Cont ID  
Sent By jgomez Date 2022-04-25 Time 10:23 Rev Time 0.00
Received By jgomez Date 2022-04-25 Time 10:23 Sent To  
Notes
2022-04-25 10:24:02SIGNATURE REVIEW:
  
 1- ALL DRAWINGS HAVE A COPY OF THE ENGINEER'S SEAL AND
 SIGNATURE. ALL DRAWINGS NEED THE ORIGINAL SEAL AND
 SIGNATURE OF THE ENGINEER AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTES WHEN SUBMITTING DOCUMENTS/PLANS FOR
 PUBLIC RECORDS.
 NOTE: SUBMIT DRAWINGS ELECTRONICALLY WITH ENGINEER'S
 DIGITAL SIGNATURE OR PROVIDE HARD COPY WITH ENGINEER'S
 ORIGINAL SEAL AND SIGNATURE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-04-20 Cont ID  
Sent By jgomez Date 2022-04-20 Time 13:32 Rev Time 0.00
Received By jgomez Date 2022-04-20 Time 13:32 Sent To  
Notes
2022-04-20 13:36:32SIGNATURE REVIEW:
  
 1- ALL DRAWINGS HAVE A COPY OF THE ENGINEER'S SEAL AND
 SIGNATURE. ALL DRAWINGS NEED THE ORIGINAL SEAL AND
 SIGNATURE OF THE ENGINEER AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTES WHEN SUBMITTING DOCUMENTS/PLANS FOR
 PUBLIC RECORDS.
 NOTE: SUBMIT DRAWINGS ELECTRONICALLY WITH ENGINEER'S
 DIGITAL SIGNATURE OR PROVIDE HARD COPY WITH ENGINEER'S
 ORIGINAL SEAL AND SIGNATURE.
  
 2- SURVEY NEEDS ORIGINAL SEAL/SIGNATURE AS REQUIRED BY
 CHAPTER 472 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR
 PUBLIC RECORDS.
 NOTE: PROVIDE HARD COPY WITH ORIGINAL SEAL/SIGNATURE OR
 UPLOAD SURVEY WITH DIGITAL SIGNATURE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-01-04 Cont ID  
Sent By rmcdouga Date 2022-01-04 Time 11:28 Rev Time 0.00
Received By rmcdouga Date 2022-01-04 Time 11:27 Sent To  
Notes
2022-01-04 11:34:52ENGINEER'S SEAL AND SIGNATURE ON THE PLANS ARE OKAY.
 SENT TO STORAGE.

Review Stop Z ZONING
Rev No 4 Status P Date 2022-05-18 Cont ID  
Sent By vbroglia Date 2022-05-18 Time 15:56 Rev Time 0.00
Received By vbroglia Date 2022-05-18 Time 15:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2022-05-16 Cont ID  
Sent By vbroglia Date 2022-05-16 Time 14:18 Rev Time 0.00
Received By vbroglia Date 2022-05-16 Time 14:18 Sent To  
Notes
2022-05-16 14:26:015/16/2022 FAILED
  
 A SEPERATE PERMIT IS NEEDED FOR FENCES/WALLS AND
 GENERATORS
 PLEASE APPLY FOR THESE PERMITS
  
 THE PROPOSED LOGGIA NEEDS TO MEET PRINCIPLE STRUCTURE
 SETBACKS, AS IT IS ATTACHED TO THE MAIN HOUSE. THE SIDE
 SETBACK IS 5 FEET MIN. WITH A 15 FEET TOTAL.
 GIVEN THAT YOU HAVE 5.3 FEET ON THE WEST SIDE, THE EAST
 SIDE SETBACK SHOULD BE 9.7 FEET AWAY FROM THE PROPERTY
 LINE.
  
  
 AS FIRST REVIEW COMMENT MENTIONS TO SHOW THE SETBACKS
 OF THE ASSCESSORY STRUCTURES AND THERE ARE STILL NO
 SETBACKS LISTED ON THE SITE PLANS, I DO NOT KNOW IF THE
 SURVEY DIMENSIONS ARE FROM THE POST OF THE NEW LOGGIA
 OR THE ROOF.
  
  
 VALENTINA BROGLIA
 ASSOCIATE PLANNER
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2022-04-08 Cont ID  
Sent By vbroglia Date 2022-04-08 Time 11:28 Rev Time 0.00
Received By vbroglia Date 2022-04-08 Time 11:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-01-13 Cont ID  
Sent By vbroglia Date 2022-01-13 Time 16:46 Rev Time  
Received By vbroglia Date 2022-01-13 Time   Sent To  
Notes
2022-01-13 16:52:491/13/2022 FAILED. PLEASE UPDATE SITE PLAN OR SURVEY TO
 MATCH, IT IS UNCLEAR IF THE ACCESSORY STRUCTURE WILL
 HAVE PROPOSED WORK DONE OR IF REMAINED UNTOUCHED.
 PLEASE SHOW SETBACK OF BUILDING AND PROPOSED LODGIA
 FROM THE PROPERTY LINE ON SITE PLAN. IF THERE WILL BE A
 BREEZEWWAY CONNECTING THE ACCESSORY STRUCTURE THE GUEST
 HOUSE/GARAGE MUST MEET PRINCIPLE STRUCTURE'S SETBACKS
  
 PLEASE INDICATE IF FENCE AND TILE WILL GO ON TO
 EASEMENT AS NOTED ON SURVEY, IF SO PLEASE PROVIDE
 EASEMENT FORMS. SEPERATE PERMIT IS NEEDED FOR
 FENCE/WALL PROPOSED ON SITE PLAN/SURVEY
  
 VALENTINA BROGLIA
 [email protected]


Account Summary | Usage Policy | Privacy Policy