Plan Review Details - Permit 21120914
Plan Review Stops For Permit 21120914
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-03-31 Cont ID  
Sent By cpuell Date 2022-03-31 Time 14:54 Rev Time 0.00
Received By cpuell Date 2022-03-31 Time 14:54 Sent To  
Notes
2022-03-31 14:55:00PARCEL MERGED INTO A NEW PARCEL 74434328060200010 WITH
 THE NEW ADDRESS OF 475 CLAREMORE DR, UPDATED PERMIT
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2022-05-18 Cont ID  
Sent By pvalenti Date 2022-05-18 Time 11:23 Rev Time 0.00
Received By pvalenti Date 2022-05-18 Time 11:22 Sent To  
Notes
2022-05-18 11:28:31PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW NOT REQUIRED:
  
 THE DRINKING FOUNTAINS ARE NOT TO BE INSTALLED UNDER
 THIS PERMIT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-10 Cont ID  
Sent By ccole Date 2022-05-10 Time 17:52 Rev Time 0.00
Received By ccole Date 2022-05-10 Time 17:52 Sent To  
Notes
2022-05-10 17:54:271ST REVIEW FBC-2020 BUILDING.
 PERMIT- 21120914
 5/10/22
  
 CODES IN EFFECT:
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P1 & P2: DRINKING FOUNTAIN DETAIL NOTES
 INDICATE THE DETAILS ARE FOR PLANNING ONLY AND NOT FOR
 CONSTRUCTION. BASED ON THE NOTES IT APPEARS A FL.
 LICENSED DESIGN PROFESSIONAL WILL HAVE TO PROVIDE
 INSTALLATION AND ANCHORING DETAILS- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2022-05-13 Cont ID  
Sent By jleahy Date 2022-05-13 Time 10:36 Rev Time 0.00
Received By jleahy Date 2022-05-13 Time 10:33 Sent To  
Notes
2022-05-13 10:37:25NON-ELECTRIC DRINKING FOUNTAINS JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-12-22 Cont ID  
Sent By jleahy Date 2021-12-22 Time 16:11 Rev Time 0.00
Received By jleahy Date 2021-12-22 Time 16:11 Sent To  
Notes
2021-12-22 16:11:41ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRICAL WORK FOUND.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-13 Cont ID  
Sent By jleahy Date 2022-05-13 Time 10:37 Rev Time 0.00
Received By jleahy Date 2022-05-07 Time 11:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-12-22 Cont ID  
Sent By jleahy Date 2021-12-22 Time 16:11 Rev Time 0.00
Received By jleahy Date 2021-12-20 Time 09:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-05-18 Cont ID  
Sent By rwbrown Date 2022-05-18 Time 11:20 Rev Time 0.00
Received By rwbrown Date 2022-05-18 Time 11:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-05-10 Cont ID  
Sent By ccole Date 2022-05-10 Time 17:50 Rev Time 0.00
Received By ccole Date 2022-05-10 Time 07:51 Sent To  
Notes
2022-05-10 17:52:232ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21120914
 5/10/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. NEW PLANS SUBMITTED.
 FLAMINGO PLUMBING HAS SUBMITTED PLANS WHICH CANNOT BE
 ACCEPTED FOR FINAL REVIEW WITHOUT SUBMITTAL OF A PERMIT
 APPLICATION AS CONTRACTOR OF RECORD- SEC.105.1 WPB, AND
 FL. STATUTE 471.025.
  
 1) PROVIDE A CIVIL PLAN SHOWING THE WATER SERVICE AND
 SANITARY POINTS OF CONNECTION TO MAINS, AND THE
 LOCATIONS OF THE WATER METER AND BACKFLOW PREVENTER-
 SEC. 107.2.1 WPB. AS NOTED ON THE PLAN A SEPARATE
 PERMIT IS REQUIRED FOR THE BACKFLOW PREVENTER- SEC.
 105.1 & 107.2.1 WPB.
  
 A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A
 SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW
 PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC.
 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE
 TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 2) P1, P2, P3, P4: THE DRINKING FOUNTAIN DETAIL ON P1
 SHOWS AN OPEN HUB DRAIN WITH A P-TRAP BUT THE ISOMETRIC
 SHOWS A DIRECT DRAIN CONNECTION. BASED ON THE CONFLICTS
 ON THE PLAN PLEASE PROVIDE PLUMBING PIPING CONNECTION
 DETAILS FOR THE DRINKING FOUNTAINS INCLUDING LOCATIONS
 OF SHUT OFF VALVES, P-TRAPS AND STUDOR VENTS- SECS.
 606.2, 918.4, 918.5, & 1002.1 FBC P.
  
 3) SHEETS P3: PROVIDE A HOSE BIB INSTALLATION DETAIL
 SHOWING HOW THE FIXTURES AND THE WATER RISER LINES WILL
 BE MOUNTED AND SUPPORTED - SEC. 308.1 FBC P.
  
 4) P4: PROVIDE A VENT PIPE RISER DETAIL SHOWING THE
 HEIGHT OF THE RISER AND HOW IT WILL BE SUPPORTED AND
 PROTECTED FROM DAMAGE- SECS. 305.7 & 308.1 FBC P.
  
 NEW COMMENT- 5/12/2022: A PLUMBING REVIEW WAS NOT
 CONDUCTED UNDER THE MASTER PERMIT-20090914 FOR THE
 TENNIS COURTS. PLEASE CONTACT THE ARCHITECT AND/OR
 ENGINEER OF RECORD FOR THE COURTS AND PROVIDE PLUMBING
 FIXTURE CALCULATIONS FOR THE COURTS IN ACCORDANCE WITH
 TABLE 403.1 FBC P. PROVIDE A SCHEDULE THAT INDICATES
 THE REQUIRED AND PROVIDED FIXTURES FOR THE OCCUPANCY.
 THE ARCHITECT SHALL CLARIFY WHETHER THE COURTS ARE
 DESIGNED FOR PUBLIC, PRIVATE, OR BOTH PUBLIC AND
 PRIVATE USE, AND ALSO HOW ACCESS TO FIXTURES IS BEING
 PROVIDED ONSITE FOR OCCUPANTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-12-22 Cont ID  
Sent By ccole Date 2021-12-22 Time 15:49 Rev Time 0.00
Received By ccole Date 2021-12-22 Time 15:49 Sent To  
Notes
2021-12-22 15:50:231ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21120914
 12/22/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P1: THE PLUMBING PLAN, AND THE PLUMBING AND
 ELECTRICAL SPECS FOR THE DRINKING FOUNTAIN APPEAR TO
 HAVE BEEN COPIED AND PASTED ONTO THE LANDSCAPE PLANS.
 PLEASE NOTE THAT LANDSCAPE ARCHITECTS CANNOT DESIGN
 PLUMBING AND ELECTRICAL PLANS- FL. STATUTE- 481.303.
 PLEASE PROVIDE SEPARATE PLUMBING AND ELECTRICAL PLANS-
 SECTION 107.2.1 WPB.
  
 2) P1: THE DRINKING FOUNTAIN SHALL DRAIN INTO THE
 SANITARY SEWER SYSTEM IN COMPLIANCE WITH SEC. 301.3 FBC
 P. PLEASE PROVIDE A SANITARY DRAINAGE LAYOUT PLAN AND
 ISOMETRIC DRAWING SHOWING THE BRANCH DRAIN LINE
 CONNECTION TO THE MAIN- SEC. 107.3.5.1.3 WPB.
  
 3) P1: PLEASE PROVIDE WATER SUPPLY LAYOUT AND ISOMETRIC
 DRAWING SHOWING THE DRINKING FOUNTAIN BRANCH LINE
 CONNECTION TO THE MAIN SERVICE LINE- SEC. 107.2.1 WPB.
  
 4) P1: THE DRINKING FOUNTAIN SHALL BE ACCESSIBLE IN
 COMPLIANCE WITH SEC. 211.1 FBC ACC.
  
 5) P1: NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE
 PROVIDED- ONE COMPLYING WITH 602.1 AND ONE COMPLYING
 WITH 602.7- (HI-LO). REFER TO SECTIONS 306, 307, AND
 602 FBC ACC AND PROVIDE DRINKING FOUNTAIN INSTALLATION
 DETAILS AND ELEVATION VIEWS SHOWING KNEE AND TOE
 CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS. SHOW
 THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE FOR A
 FORWARD WHEELCHAIR APPROACH TO THE FOUNTAIN- SECTION
 602.2 FBC ACC, AND SHOW HOW THE LOCATIONS OF THE
 FOUNTAINS WILL BE IN COMPLIANCE WITH SECTION 307.2
 PROTRUSION LIMITS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2022-05-10 Cont ID  
Sent By ccole Date 2022-05-10 Time 17:54 Rev Time 0.00
Received By ccole Date 2022-05-10 Time 17:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-12-20 Cont ID  
Sent By ccole Date 2021-12-20 Time 14:05 Rev Time 0.00
Received By ccole Date 2021-12-20 Time 14:05 Sent To  
Notes
2021-12-20 14:07:15SIGNATURE REVIEW
 PERMIT- 21120912
 12/22/21
  
 PLAN REVIEW RESULTS- DENIED.
  
 1) THE LANDSCAPE PLAN REQUIRES THE DIGITAL SIGNATURE
 AND SEAL OF THE LANDSCAPE ARCHITECT OF RECORD- FL
 STATUTE 481.221 AND SECTION 61G1-16.005 FLORIDA
 ADMINISTRATIVE CODE.
  
 2) P1: PLEASE NOTE THE PLUMBING PLAN, AND THE PLUMBING
 AND ELECTRICAL SPECS FOR THE DRINKING FOUNTAIN HAVE
 BEEN COPIED AND PASTED ONTO THE LANDSCAPE PLANS.
 LANDSCAPE ARCHITECTS CANNOT DESIGN PLUMBING AND
 ELECTRICAL PLANS- FL. STATUTE 481-303.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  