Plan Review Details - Permit 21120760
Plan Review Stops For Permit 21120760
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-04-28 Cont ID  
Sent By cpuell Date 2022-04-28 Time 16:34 Rev Time 0.00
Received By cpuell Date 2022-04-28 Time 16:26 Sent To  
Notes
2022-04-28 16:35:32WORK TO BE DONE ONT 516 AND 518 32ND ST. HALF ADDRESS
 READDRESSED AS 518 32ND ST (GARAGE BUILDING NOT IN
 SCOPE OF WORK)

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-12-15 Cont ID  
Sent By cpuell Date 2021-12-15 Time 16:22 Rev Time 0.00
Received By cpuell Date 2021-12-15 Time 16:22 Sent To  
Notes
2021-12-15 16:25:01WHICH OF THE 3 BUILDINGS ARE TO BE REROOFED? THEEAST
 BUILDING HAS A HALF ADDRESS WHICH WILL NEED TO BE
 READDRESSED. PLEASE HAVE THE OWNER CONTACT
 [email protected] OR CALL 561-805-6659 TO READDRESS THE
 HALF ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-05-09 Cont ID  
Sent By rmcphers Date 2022-05-09 Time 10:57 Rev Time 0.00
Received By rmcphers Date 2022-05-09 Time 10:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-04-20 Cont ID  
Sent By jbrooks Date 2022-04-20 Time 10:00 Rev Time 0.00
Received By jbrooks Date 2022-04-20 Time 07:41 Sent To  
Notes
2022-04-20 10:00:48JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected].
  
 1. SUBMITTED MIAMI-DADE COUNTY NOA 19-0311.04 COVERS
 MULTIPLE ROOFING SYSTEMS TYPES A(1) THROUGH E(24).
 SELECT SYSTEM TO BE USED. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING. ENGINEERED SIGNED AND SEALED
 CALCULATIONS MAY BE REQUIRED. PLEASE NOTE THIS IS A
 CATEGORY C AREA.
 2. FBC B 107.2.1 SUBMITTED FORM 400 IS A PALM BEACH
 COUNTY BUILDING DEPARTMENT DOCUMENT AND IS NOT APPROVED
 FOR USE AS A SUBSTITUTE FOR SIGNED AND SEALED ENHANCED
 NAILING CALCULATIONS BY THE CITY OF WEST PALM BEACH
 BUILDING DEPARTMENT THE AUTHORITY OF JURISDICTION.
 GENERAL LIMITATION #7 IS SPECIFICALLY REFERRED TO IN
 THIS NOA. SUBMIT FASTENER DENSITY CALCULATIONS
 PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED ARCHITECT, OR
 REGISTERED ROOF CONSULTANT.
 3. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA'S FOR THE PROPOSED ROOF COATING SYSTEM TO
 BE USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
 4. FBC B 107.2.1 PROVIDE A ROOF DRAINAGE PLAN THAT
 COMPLIES WITH SECTION 903.4 OF THE 2020 FBC-RESIDENTIAL
 AND CHAPTER 11 OF THE 2020 FBC-PLUMBING
 5. FBC EB 706.6 PROVIDE A FLASHING DETAIL DRAWING FOR
 THE EXISTING PARAPET WALLS TO INCLUDE PARAPET WALL
 HEIGHT(S).
 6. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND SHOW THE AREAS TO RECEIVE NEW
 ROOFING CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF
 SLOPE(S), MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS
 MUST SHOW POSITIVE DRAINAGE.
 7. FBC EB 706.8.1 PROVIDE A DETAILED COST ESTIMATE OF
 THE EVALUATION AND INSTALLATION OF CONNECTIONS AT THE
 GABLE ENDS OR ALL CORNERS THAT WILL EXCEED 15% OF THE
 COST OF THE ROOF REPLACEMENT WHEN COMPLETED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-04-28 Cont ID  
Sent By amhamilt Date 2022-04-28 Time 09:37 Rev Time 0.00
Received By amhamilt Date 2022-04-28 Time 09:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-09 Cont ID  
Sent By rmcphers Date 2022-05-09 Time 10:57 Rev Time 0.00
Received By rmcphers Date 2022-05-06 Time 10:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-28 Cont ID  
Sent By cpuell Date 2022-04-28 Time 15:13 Rev Time 0.00
Received By cpuell Date 2022-04-19 Time 12:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-05-10 Cont ID  
Sent By mpeterso Date 2022-05-10 Time 16:18 Rev Time 0.00
Received By mpeterso Date 2022-05-10 Time 16:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-05-09 Cont ID  
Sent By rmcphers Date 2022-05-09 Time 10:59 Rev Time 0.00
Received By rmcphers Date 2022-05-09 Time 10:59 Sent To  
Notes
2022-05-09 11:01:12SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) ADDITIONAL ATTACHMENT ENGINEERING FROM LANK
 ENGINEERING LLC - DOES NOT SHOW AS DIGITALLY SIGNED IN
 ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  