Plan Review Details - Permit 21120573
Plan Review Stops For Permit 21120573 |
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
P |
Date |
2022-03-11 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2022-03-11 |
Time |
16:10 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2022-03-11 |
Time |
16:10 |
Sent To |
|
|
Notes |
2022-03-11 16:11:05 | ADDRESS APPROPRIATE FOR PROJECT. |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
F |
Date |
2023-04-18 |
|
|
Cont ID |
|
Sent By |
sberglun |
Date |
2023-04-18 |
Time |
11:15 |
Rev Time |
0.00 |
Received By |
sberglun |
Date |
2023-04-18 |
Time |
11:15 |
Sent To |
|
|
Notes |
2023-04-18 11:15:50 | 1) RELOCATE THE POLE A MIN. OF 5' AWAY FROM THE | | EXISTING WM. | | SUZANNE BERGLUND | | [email protected] |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
F |
Date |
2022-06-23 |
|
|
Cont ID |
|
Sent By |
sberglun |
Date |
2022-06-23 |
Time |
15:39 |
Rev Time |
0.00 |
Received By |
sberglun |
Date |
2022-06-23 |
Time |
15:36 |
Sent To |
|
|
Notes |
2022-06-23 15:39:38 | 1) WHILE ZONING STAFF REQUESTS THE POLE TO BE SHIFTED, | | THE FOLLOWING COMMENTS WILL NEED TO BE TAKEN INTO | | ACCOUNT NO MATTER WHERE THE NEW POLE AND UNDERGROUND | | ELECTRIC ARE PLACED | | A) INCLUDE CITY UNDERGROUND UTILITIY PIPE SIZE, PIPE | | MATERIAL, AND DESCRIPTION ON THE SITE PLAN. CONTACT | | JANICE TARBILL, [email protected] FOR AS-BUILT | | INFORMATION. INCLUDE AS-BUILT INFORMATION IN YOUR | | RESUBMITTAL. | | B) PROVIDE PROFILE FOR PROPOSED UNDERGROUND ELECTRIC | | SHOWING ALL CROSSING DATA FOR OTHER UTILITIES. | | C) ALL ROADWAY, SIDEWALK, AND SWALE RESTORATIONS ARE | | REQUIRED PER CITY STANDARD. | | 2) PLAN WILL BE RE-REVIEWED ONCE RESUBMITTED. | | | | SUZANNE BERGLUND | | [email protected] | | 561-494-1075 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2023-05-02 |
|
|
Cont ID |
|
Sent By |
avolcy |
Date |
2023-05-02 |
Time |
15:37 |
Rev Time |
0.00 |
Received By |
avolcy |
Date |
2023-01-30 |
Time |
07:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-06-27 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2022-06-27 |
Time |
08:28 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2021-12-13 |
Time |
12:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
N |
Date |
2021-12-17 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2021-12-17 |
Time |
12:31 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2021-12-17 |
Time |
08:01 |
Sent To |
|
|
Notes |
2021-12-17 12:31:51 | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | COMMUNICATIONS APPLICATIONS - NEW PROCESS EFFECTIVE | | 12/6/2021 | | | | 1. FOR ALL FUTURE SUBMITTALS, PRIOR TO SUBMISSION, | | CONTACT [email protected] TO OBTAIN THE CORRECT ADDRESS | | FOR YOUR APPLICATION. SHE WILL ASSIGN AN ADDRESS VIA | | EMAIL. WHEN YOU SUBMIT THE APPLICATION, INCLUDE THE | | EMAIL AS AN ATTACHMENT. | | | | 2. FOR ALL FUTURE SUBMITTALS, TO SUBMIT THE | | COMMUNICATIONS APPLICATION, EMAIL THE COMPLETED | | APPLICATION TO [email protected]. THEY WILL | | GENERATE YOUR APPLICATION AND SEND YOU INSTRUCTIONS TO | | UPLOAD YOUR PLANS. | | | | 3. FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR | | ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | SIGNED, SEALED, DATED ORIGINALS. IT APPEARS THAT THE | | DOCUMENTS SUBMITTED PAPER TO THE BUILDING DIVISION WERE | | DIGITALLY SIGNED PLANS THAT WERE PRINTED. | | | | IF THIS APPLICATION FAILS REVIEW - WHEN RESUBMITTING, | | UPLOAD INDIVIDUALLY SIGNED AND SEALED DRAWINGS IF | | POSSIBLE. IF YOU CANNOT OBTAIN PLANS IN THAT FORMAT, | | UPLOAD THE SINGLE MULTIPAGE DIGITALY SIGNED PDF TO THE | | SIGNATURE FOLDER. | | | | IF THIS APPLICATION PASSES REVIEW - UPLOAD THE | | DIGITALLY SIGNED DOCUMENTS (SHOULD BE IDENTICAL TO THE | | DOCUMENTS REVIEWED) TO THE SIGNATURE FOLDER. | | | | IF THE ENGINEER DOES NOT HAVE A DIGITAL SIGNATURE, | | PLEASE CONTACT ME DIRECTLY TO DISCUSS OPTIONS. | | | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2023-05-02 |
|
|
Cont ID |
|
Sent By |
avolcy |
Date |
2023-05-02 |
Time |
15:33 |
Rev Time |
0.00 |
Received By |
avolcy |
Date |
2023-05-02 |
Time |
15:33 |
Sent To |
|
|
Notes |
2023-05-02 15:37:06 | INSUFFICIENT | | | | PREVIOUS ZONING COMMENTS WERE ADDRESSED WITH THIS | | SUBMITTAL, HOWEVER, BASED ON ENGINEERING COMMENTS, POLE | | MUST BE RELOCATED. ZONING WILL NEED TO RE-REVIEW THE | | NEW PROPOSED LOCATION. | | | | PLEASE ENSURE THAT NEW LOCATION OF POLE ALIGNS WITH | | OTHER POLES/TREES IN THE R-O-W AND IS NOT IN FRONT OF | | RESIDENTIAL STRUCTURES. | | | | REVIEWED BY: | | GAISHA VOLCY | | [email protected] | | | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2022-03-10 |
|
|
Cont ID |
|
Sent By |
eshneide |
Date |
2022-03-10 |
Time |
16:57 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2022-03-10 |
Time |
16:57 |
Sent To |
|
|
Notes |
2022-03-10 16:57:47 | INSUFFICIENT | | | | 1) THE PROPOSED POLE IS SHOWN IN FRONT OF THE SINGLE | | FAMILY HOUSED THAT ARE LOCATED ON THE EAST SIDE OF | | POINSETTIA AVENUE. THE SITE PLAN WITH AERIAL SHOWS THAT | | THE POLE IS DIRECTLY IN FRONT OF HOUSE ON THE PROPERTY | | AT 2704 POINSETTIA AVENUE. THE POLE NEEDS TO BE SHIFTED | | TO THE NORTH AT LEAST THREE FEET TO BE LOCATED NORTH OF | | THE NORTH WALL OF THE HOUSE. | | | | 2) THE CITY CODE REQUIRES THAT POLES SHALL BE LOCATED | | SO AS TO ALIGN WITH EXISTING POLES IN THE RIGHT-OF-WAY | | AND HAVE EQUAL SETBACK DISTANCES WITH EXISTING POLES | | FROM THE CURBLINE OF THE RIGHT-OF-WAY. THE PROPOSED | | POLE IS NOT SHOWN IN LINE WITH THE EXISTING LIGHT POLES | | ALONG TAMARIND AVENUE IN THIS LOCATION. THE POLE NEEDS | | TO BE MOVED A COUPLE FEET TO THE WEST. | | | | 3) THE BORE PIT, BY THE POLE, NOTES ON SHEET P-1 STATE | | THAT THE SIDEWALK WILL BE RESTORED; HOWEVER, IT IS | | LOCATED ONLY WITHIN THE PARKWAY WHICH WILL NEED | | RESTORATION. PLEASE UPDATE THE NOTATIONS ACCORDINGLY. | | | | 4) PROVIDE A CROSS SECTION OF THE UNDERGROUND ELECTRIC | | WHICH VERIFIES THAT THERE ARE NO CONFLICTS WITH | | EXISTING UTILITIES. | | | | 5) THE PLANS SHOW GAS AND COM LINES ADJACENT TO THE | | BORE PIT(S). IN ORDER TO VERIFY THAT THE INSTALLATION | | WILL NOT INTERFERE WITH THE EXISTING FACILITIES, | | PROVIDE A PUBLIC UTILITY LETTER OF NO OBJECTION FROM | | FPU FOR THE GAS LINE AND THE COM PROVIDER(S), MOST | | LIKELY AT&T OR COMCAST. | | | | 6) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS. | | THE POLE COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP | | 7042 TRAFFIC GREY A. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | [email protected] | | | | |
|
|
|