Plan Review Stops For Permit 21120568 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2023-03-29 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-03-29 |
Time |
10:07 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-03-29 |
Time |
10:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2022-03-24 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2022-03-24 |
Time |
13:15 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2022-03-24 |
Time |
12:44 |
Sent To |
|
|
Notes |
2022-03-24 12:47:03 | PETER E VALENTI | | BUILDING PLANS EXAMINER II | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | BUILDING REVIEW DENIED: | | | | FBC R 4501.17.1, PLEASE SHOW ON PLANS THE POOL BARRIER | | DETAILS INCLUDING WINDOW/DOOR ALARMS IF APPLICABLE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2022-01-13 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2022-01-13 |
Time |
13:57 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2022-01-13 |
Time |
13:09 |
Sent To |
|
|
Notes |
2022-01-13 14:14:44 | PETER E VALENTI | | BUILDING PLANS EXAMINER II | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | BUILDING REVIEW DENIED: | | | | FBC R 4501.17.1, PLEASE SHOW ON PLANS THE POOL BARRIER | | DETAILS INCLUDING WINDOW/DOOR ALARMS IF APPLICABLE. | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2023-03-17 |
|
|
Cont ID |
|
Sent By |
ppetty |
Date |
2023-03-17 |
Time |
10:34 |
Rev Time |
0.00 |
Received By |
ppetty |
Date |
2023-03-17 |
Time |
09:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2022-03-24 |
|
|
Cont ID |
|
Sent By |
ppetty |
Date |
2022-03-24 |
Time |
08:53 |
Rev Time |
0.00 |
Received By |
ppetty |
Date |
2022-03-24 |
Time |
08:45 |
Sent To |
|
|
Notes |
2022-03-24 08:54:06 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 | | 7TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1.PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | SINCERELY, | | | | PHIL PETTY | | CHIEF ELECTRICAL INSPECTOR , ELECTRICAL PLANS EXAMINER | | | | 561-805-6742 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2022-01-04 |
|
|
Cont ID |
|
Sent By |
ppetty |
Date |
2022-01-04 |
Time |
08:48 |
Rev Time |
0.00 |
Received By |
ppetty |
Date |
2022-01-04 |
Time |
08:36 |
Sent To |
|
|
Notes |
2022-01-04 08:49:58 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 | | 7TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1.PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | SINCERELY, | | | | PHIL PETTY | | CHIEF ELECTRICAL INSPECTOR , ELECTRICAL PLANS EXAMINER | | | | 561-805-6742 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2023-03-31 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2023-03-31 |
Time |
11:22 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2023-03-30 |
Time |
11:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2023-03-29 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-03-29 |
Time |
10:08 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-03-14 |
Time |
16:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2022-03-24 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2022-03-24 |
Time |
13:16 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2022-03-10 |
Time |
08:56 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-01-13 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2022-01-13 |
Time |
14:15 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2021-12-14 |
Time |
07:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2023-03-31 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2023-03-31 |
Time |
11:22 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2023-03-31 |
Time |
11:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2023-03-17 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2023-03-17 |
Time |
12:32 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2023-03-17 |
Time |
11:10 |
Sent To |
|
|
Notes |
2023-03-17 12:33:00 | 1ST REVIEW FBC-2020 RES. PLUMBING | | PERMIT- 21120568 | | 3/17/23 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE CORRECT POOL PLAN SHEET 3 SPECIFYING THE PUMP | | TO BE CS-150 0.85 HP. THE ENGINEER???S SIGNED AND | | SEALED TDH AND FLOW RATE CALCULATIONS ARE BASED ON A | | 1HP PUMP TO BE INSTALLED- SEC. R4501.6 FBC RES. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2022-03-11 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2022-03-11 |
Time |
15:23 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2022-03-11 |
Time |
15:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2021-12-17 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-12-17 |
Time |
13:13 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-12-17 |
Time |
13:13 |
Sent To |
|
|
Notes |
2021-12-17 13:14:07 | 12/17/21 1ST POOL PLUMBING REVIEW**DENIED** WITH | | COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. WOULD YOU PLEASE SUBMIT TOTAL DYNAMIC HEAD | | CALCULATIONS FOR THE MAXIMUM SYSTEM FLOW? THE PUMP'S | | MAXIMUM FLOW FROM ITS PUMP CURVE IS NO LONGER ALLOWED | | TO BE USED IN DETERMINING THE MAXIMUM SYSTEM FLOW RATE | | PER ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE | | 2013 EDITION ADDRESSES THE FLOW RATE IN GALLONS PER | | MINUTE (GPM). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW | | RATE DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF | | THE SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE | | TDH CALCULATIONS MUST INCLUDE ALL THE SYSTEM | | COMPONENTS, INCLUDING SUCTION AND RETURN PIPING, | | FITTINGS, VALVES, AND FILTER. ALL SYSTEM COMPONENTS | | EXCEPT THE PUMP. | | | | 2. WOULD YOU PLEASE SUBMIT THE POOL PUMP CURVE AND | | IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC | | TO THE PUMP BEING INSTALLED ON THIS POOL. THIS IS | | NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH | | CALCULATIONS PER THE ANSI/APSP/ICC 7 - 2015 SECS. | | 4.4.9, 4.4.9.1. | | | | 3. THERE IS A POOL CHLORINATOR ON POOL SPECIFICATIONS | | AND NO SPECIFICATION FOR IT. WOULD YOU PLEASE PROVIDE | | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | 4. THESE ARE MULTI-FAMILY DWELLINGS, AND WATER USERS | | WILL BE REQUIRED TO INSTALL A BACKFLOW PREVENTION | | ASSEMBLY AT THE POINT OF DELIVERY. THE TYPE OF BACKFLOW | | ASSEMBLY REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF | | HAZARD POSED BY THE WATER USER. A REDUCED PRESSURE ZONE | | BACKFLOW DEVICE WILL BE REQUIRED AT THE WATER METER PER | | THE CITY OF WEST PALM CROSS UTILITIES DEPARTMENT AND | | THEIR CONNECTION CONTROL PROGRAM. | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
4 |
Status |
P |
Date |
2023-03-31 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2023-03-31 |
Time |
11:22 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2023-03-31 |
Time |
11:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2023-03-29 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-03-29 |
Time |
10:07 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-03-29 |
Time |
10:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2022-03-24 |
|
|
Cont ID |
|
Sent By |
ppetty |
Date |
2022-03-24 |
Time |
08:54 |
Rev Time |
0.00 |
Received By |
ppetty |
Date |
2022-03-24 |
Time |
08:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2022-01-13 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2022-01-13 |
Time |
14:15 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2022-01-13 |
Time |
13:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2023-03-21 |
|
|
Cont ID |
|
Sent By |
vbroglia |
Date |
2023-03-21 |
Time |
12:51 |
Rev Time |
0.00 |
Received By |
vbroglia |
Date |
2023-03-21 |
Time |
12:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2022-03-14 |
|
|
Cont ID |
|
Sent By |
vbroglia |
Date |
2022-03-14 |
Time |
16:21 |
Rev Time |
0.00 |
Received By |
vbroglia |
Date |
2022-03-14 |
Time |
16:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2021-12-23 |
|
|
Cont ID |
|
Sent By |
vbroglia |
Date |
2021-12-23 |
Time |
12:55 |
Rev Time |
0.00 |
Received By |
vbroglia |
Date |
2021-12-23 |
Time |
12:55 |
Sent To |
|
|
Notes |
|
|