Plan Review Details - Permit 21120568
Plan Review Stops For Permit 21120568
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-03-29 Cont ID  
Sent By pvalenti Date 2023-03-29 Time 10:07 Rev Time 0.00
Received By pvalenti Date 2023-03-29 Time 10:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-03-24 Cont ID  
Sent By pvalenti Date 2022-03-24 Time 13:15 Rev Time 0.00
Received By pvalenti Date 2022-03-24 Time 12:44 Sent To  
Notes
2022-03-24 12:47:03PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC R 4501.17.1, PLEASE SHOW ON PLANS THE POOL BARRIER
 DETAILS INCLUDING WINDOW/DOOR ALARMS IF APPLICABLE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-01-13 Cont ID  
Sent By pvalenti Date 2022-01-13 Time 13:57 Rev Time 0.00
Received By pvalenti Date 2022-01-13 Time 13:09 Sent To  
Notes
2022-01-13 14:14:44PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC R 4501.17.1, PLEASE SHOW ON PLANS THE POOL BARRIER
 DETAILS INCLUDING WINDOW/DOOR ALARMS IF APPLICABLE.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-03-17 Cont ID  
Sent By ppetty Date 2023-03-17 Time 10:34 Rev Time 0.00
Received By ppetty Date 2023-03-17 Time 09:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-03-24 Cont ID  
Sent By ppetty Date 2022-03-24 Time 08:53 Rev Time 0.00
Received By ppetty Date 2022-03-24 Time 08:45 Sent To  
Notes
2022-03-24 08:54:06CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 PHIL PETTY
 CHIEF ELECTRICAL INSPECTOR , ELECTRICAL PLANS EXAMINER
  
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-01-04 Cont ID  
Sent By ppetty Date 2022-01-04 Time 08:48 Rev Time 0.00
Received By ppetty Date 2022-01-04 Time 08:36 Sent To  
Notes
2022-01-04 08:49:58CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 PHIL PETTY
 CHIEF ELECTRICAL INSPECTOR , ELECTRICAL PLANS EXAMINER
  
 561-805-6742
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-03-31 Cont ID  
Sent By rwbrown Date 2023-03-31 Time 11:22 Rev Time 0.00
Received By rwbrown Date 2023-03-30 Time 11:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-03-29 Cont ID  
Sent By pvalenti Date 2023-03-29 Time 10:08 Rev Time 0.00
Received By pvalenti Date 2023-03-14 Time 16:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-24 Cont ID  
Sent By pvalenti Date 2022-03-24 Time 13:16 Rev Time 0.00
Received By pvalenti Date 2022-03-10 Time 08:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-13 Cont ID  
Sent By pvalenti Date 2022-01-13 Time 14:15 Rev Time 0.00
Received By pvalenti Date 2021-12-14 Time 07:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2023-03-31 Cont ID  
Sent By rwbrown Date 2023-03-31 Time 11:22 Rev Time 0.00
Received By rwbrown Date 2023-03-31 Time 11:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2023-03-17 Cont ID  
Sent By ccole Date 2023-03-17 Time 12:32 Rev Time 0.00
Received By ccole Date 2023-03-17 Time 11:10 Sent To  
Notes
2023-03-17 12:33:001ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 21120568
 3/17/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE CORRECT POOL PLAN SHEET 3 SPECIFYING THE PUMP
 TO BE CS-150 0.85 HP. THE ENGINEER???S SIGNED AND
 SEALED TDH AND FLOW RATE CALCULATIONS ARE BASED ON A
 1HP PUMP TO BE INSTALLED- SEC. R4501.6 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-03-11 Cont ID  
Sent By lcrespo Date 2022-03-11 Time 15:23 Rev Time 0.00
Received By lcrespo Date 2022-03-11 Time 15:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-12-17 Cont ID  
Sent By lcrespo Date 2021-12-17 Time 13:13 Rev Time 0.00
Received By lcrespo Date 2021-12-17 Time 13:13 Sent To  
Notes
2021-12-17 13:14:0712/17/21 1ST POOL PLUMBING REVIEW**DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. WOULD YOU PLEASE SUBMIT TOTAL DYNAMIC HEAD
 CALCULATIONS FOR THE MAXIMUM SYSTEM FLOW? THE PUMP'S
 MAXIMUM FLOW FROM ITS PUMP CURVE IS NO LONGER ALLOWED
 TO BE USED IN DETERMINING THE MAXIMUM SYSTEM FLOW RATE
 PER ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE
 2013 EDITION ADDRESSES THE FLOW RATE IN GALLONS PER
 MINUTE (GPM). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW
 RATE DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF
 THE SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE
 TDH CALCULATIONS MUST INCLUDE ALL THE SYSTEM
 COMPONENTS, INCLUDING SUCTION AND RETURN PIPING,
 FITTINGS, VALVES, AND FILTER. ALL SYSTEM COMPONENTS
 EXCEPT THE PUMP.
  
 2. WOULD YOU PLEASE SUBMIT THE POOL PUMP CURVE AND
 IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC
 TO THE PUMP BEING INSTALLED ON THIS POOL. THIS IS
 NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH
 CALCULATIONS PER THE ANSI/APSP/ICC 7 - 2015 SECS.
 4.4.9, 4.4.9.1.
  
 3. THERE IS A POOL CHLORINATOR ON POOL SPECIFICATIONS
 AND NO SPECIFICATION FOR IT. WOULD YOU PLEASE PROVIDE
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. THESE ARE MULTI-FAMILY DWELLINGS, AND WATER USERS
 WILL BE REQUIRED TO INSTALL A BACKFLOW PREVENTION
 ASSEMBLY AT THE POINT OF DELIVERY. THE TYPE OF BACKFLOW
 ASSEMBLY REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF
 HAZARD POSED BY THE WATER USER. A REDUCED PRESSURE ZONE
 BACKFLOW DEVICE WILL BE REQUIRED AT THE WATER METER PER
 THE CITY OF WEST PALM CROSS UTILITIES DEPARTMENT AND
 THEIR CONNECTION CONTROL PROGRAM.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-03-31 Cont ID  
Sent By rwbrown Date 2023-03-31 Time 11:22 Rev Time 0.00
Received By rwbrown Date 2023-03-31 Time 11:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-03-29 Cont ID  
Sent By pvalenti Date 2023-03-29 Time 10:07 Rev Time 0.00
Received By pvalenti Date 2023-03-29 Time 10:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-03-24 Cont ID  
Sent By ppetty Date 2022-03-24 Time 08:54 Rev Time 0.00
Received By ppetty Date 2022-03-24 Time 08:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-01-13 Cont ID  
Sent By pvalenti Date 2022-01-13 Time 14:15 Rev Time 0.00
Received By pvalenti Date 2022-01-13 Time 13:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2023-03-21 Cont ID  
Sent By vbroglia Date 2023-03-21 Time 12:51 Rev Time 0.00
Received By vbroglia Date 2023-03-21 Time 12:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-03-14 Cont ID  
Sent By vbroglia Date 2022-03-14 Time 16:21 Rev Time 0.00
Received By vbroglia Date 2022-03-14 Time 16:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-12-23 Cont ID  
Sent By vbroglia Date 2021-12-23 Time 12:55 Rev Time 0.00
Received By vbroglia Date 2021-12-23 Time 12:55 Sent To  
Notes
***NONE***