Plan Review Details - Permit 21120558
Plan Review Stops For Permit 21120558
Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2022-08-17 Cont ID  
Sent By sberglun Date 2022-08-17 Time 10:39 Rev Time 0.00
Received By sberglun Date 2022-08-17 Time 10:39 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2022-08-08 Cont ID  
Sent By sberglun Date 2022-08-08 Time 15:23 Rev Time 0.00
Received By sberglun Date 2022-08-08 Time 15:18 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2022-06-27 Cont ID  
Sent By sberglun Date 2022-06-27 Time 14:17 Rev Time 0.00
Received By sberglun Date 2022-06-27 Time 14:17 Sent To  
Notes
2022-06-27 14:17:441) CITY UTILITIES ARE SHOWN INCORRECTLY ON PLANS.
 PLEASE CONTACT JANICE TARBILL, [email protected] FOR
 AS-BUILT INFORMATION. PLEASE INCLUDE AS-BUILT
 INFORMATION IN YOUR RESUBMITTAL.
 2) PLEASE PROVIDE PROFILE FOR PROPOSED UNDERGROUND
 ELECTRIC SHOWING ALL CROSSING DATA FOR OTHER UTILITIES.
 3) ALL ROADWAY, SIDEWALK, AND SWALE RESTORATIONS ARE
 REQUIRED PER CITY STANDARD.
  
 SUZANNE BERGLUND
 [email protected]
 561-494-1075
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2022-03-16 Cont ID  
Sent By gpatrie Date 2022-03-16 Time 10:21 Rev Time  
Received By gpatrie Date   Time   Sent To  
Notes
2022-03-16 10:21:25NO SURVEY WAS PROVIDED PER COMENTS BY CHRIS KIMMERLY.
  
 CONTACT [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By aoliver Date 2022-08-10 Time 15:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-08-08 Cont ID  
Sent By aoliver Date 2022-08-08 Time 15:29 Rev Time 0.00
Received By aoliver Date 2022-07-22 Time 07:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-27 Cont ID  
Sent By lmarchan Date 2022-06-27 Time 15:58 Rev Time 0.00
Received By lmarchan Date 2022-04-11 Time 16:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-16 Cont ID  
Sent By lmarchan Date 2022-03-16 Time 16:52 Rev Time 0.00
Received By lmarchan Date 2021-12-14 Time 14:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2022-11-03 Cont ID  
Sent By ckimmerl Date 2022-11-03 Time 15:15 Rev Time 0.00
Received By ckimmerl Date 2022-11-03 Time 15:15 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2022-07-27 Cont ID  
Sent By ckimmerl Date 2022-07-27 Time 11:43 Rev Time 0.00
Received By ckimmerl Date 2022-07-27 Time 11:34 Sent To  
Notes
2022-07-27 11:35:471. PLEASE PROVIDE THE NECESSARY PUBLIC/PRIVATE UTILITY
 LETTERS GRANTING APPROVAL OF THE POLE LOCATION, BORE
 PITS, HANDHOLES, AND UNDERGROUND ELECTRICAL FOR THE
 PROPOSED WIRELESS COMMUNICATIONS FACILITY.
  
  
  
 GENERALLY MEETS/SATISFIES ZONING REVIEW REQUIREMENTS.
 THE POLE DESIGN, HEIGHT, LOCATION, AND ELECTRIC CONDUIT
 PATH MEET CITY REQUIREMENTS.
 ***** FAIL STATUS IS SO THAT THIS PERMIT IS VERIFIED BY
 ZONING AFTER NEXT ENGINEERING REVIEW *****
  
  
  
 THIS WCF PERMIT SHOULD BE COMBINED/MERGED WITH THE
 CONDUIT PERMIT (21120582)

Review Stop Z ZONING
Rev No 2 Status F Date 2022-06-16 Cont ID  
Sent By ckimmerl Date 2022-06-16 Time 12:16 Rev Time 0.00
Received By ckimmerl Date 2022-06-16 Time 12:15 Sent To  
Notes
2022-06-16 12:16:09ORIGINAL 3/2/22 COMMENTS
  
 1. PROVIDE A SURVEY, PREPARED BY A FLORIDA LICENSED
 SURVEYOR, WHICH SHOWS THE POLE LOCATION AND THE
 RIGHT-OF-WAY LINE SO THAT STAFF CAN VERIFY THAT THE
 WIRELESS COMMUNICATION FACILITY IS WITHIN THE
 RIGHT-OF-WAY AND NOT ON PRIVATE PROPERTY.
 [SATISFIED]
  
 2. PROVIDE A COPY OF THE FDOT APPROVAL IF THE SURVEY
 SHOWS THE PROPOSED WIRELESS COMMUNICATION FACILITY IS
 IN THE FDOT-CONTROLLED RIGHT-OF-WAY.
 [NOT SATISFIED] SECTION OF ROW THE PROPOSED POLE IS IN
 WAS FORMERLY THE ON RAMP FOR THE FLAGLER MEMORIAL
 BRIDGE. OUR RECORDS INDICATE THAT THIS LOCATION IS
 STILL WITHIN THE FDOT ROW, UNLESS APPLICANT CAN PROVIDE
 DOCUMENTATION PROVING OTHERWISE.
  
 PLEASE PROVIDE A COPY OF THE FDOT APPROVAL.
  
 3. POLE HEIGHT SHALL BE ANALOGOUS TO EXISTING
 DECORATIVE LIGHT POLES/FIXTURES ALONG N FLAGLER DR. & N
 QUADRILLE BLVD.
 [NOT SATISFIED] PLEASE PROVIDE HEIGHT DIMENSIONS FOR
 THE REFERENCE POLE (UTILITY POLE, LIGHT POLE, ETC.)
 WITHIN THE ROW THAT THIS WIRELESS COMMUNICATIONS
 FACILITY POLE IS MATCHING/LESS THAN THE HEIGHT OF.
 PROVIDE THIS HEIGHT CALLOUT ON THE SITE PLANS. (SURVEY
 SHOWS 36? HEIGHT REFERENCED POLE)
  
 ADDITIONALLY, PROPOSED POLE HEIGHT IS SHOWN AT 3
 DIFFERENT MEASUREMENTS. HEIGHT SHOWN AS 25? ON OVERALL
 SITE PLAN, CROSS SECTION, AND PLAN VIEW. HEIGHT SHOWN
 AS 24?-6? ON PHOTO SIM. HEIGHT SHOWN AS 30? ON NEW
 EQUIPMENT ELEVATION. PLEASE CLARIFY AND HAVE HEIGHT BE
 LESSER OR EQUAL TO REFERENCED UTILITY POLES IN ROW.
  
 4. POLE COLOR SHALL MATCH THE BLACK DECORATIVE LIGHT
 POLES/FIXTURES ALONG N FLAGLER DR. & N QUADRILLE BLVD.
 COLOR SHALL MATCH RAYCON RAL 7022 (UMBRA GREY), PLEASE
 CONTACT STAFF IF THERE ARE QUESTIONS OR CONCERNS WITH
 MATCHING THE POLE COLORS.
 [SATISFIED]
  
 5. THE POLE STEALTH DESIGN MEETS CITY STANDARDS.
 [SATISFIED]
  
 NEW COMMENT: 6/16/22
 1. PLEASE PROVIDE DETAILS OR SHEETS FOR THE UNDERGROUND
 POWER ROUTE AND CONNECTION FOR THE PROPOSED POLE.
 PROVIDE ELECTRICAL CONNECTION PATH/BORE PITS ON SURVEY,
 PLAN VIEW, AND SITE PLANS SO THAT STAFF CAN VERIFY THAT
 THE WIRELESS COMMUNICATION FACILITY ELECTRICAL
 CONNECTIONS ARE WITHIN THE RIGHT-OF-WAY AND NOT ON
 PRIVATE PROPERTY.
  
 CHRIS KIMMERLY, AICP
 URBAN DESIGN PLANNER
 (561)822-1426
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-03-02 Cont ID  
Sent By ckimmerl Date 2022-03-02 Time 11:46 Rev Time 0.00
Received By ckimmerl Date 2022-03-02 Time 10:53 Sent To  
Notes
2022-03-02 11:02:241. PROVIDE A SURVEY, PREPARED BY A FLORIDA LICENSED
 SURVEYOR, WHICH SHOWS THE POLE LOCATION AND THE
 RIGHT-OF-WAY LINE SO THAT STAFF CAN VERIFY THAT THE
 WIRELESS COMMUNICATION FACILITY IS WITHIN THE
 RIGHT-OF-WAY AND NOT ON PRIVATE PROPERTY.
 2. PROVIDE A COPY OF THE FDOT APPROVAL IF THE SURVEY
 SHOWS THE PROPOSED WIRELESS COMMUNICATION FACILITY IS
 IN THE FDOT-CONTROLLED RIGHT-OF-WAY.
 3. POLE HEIGHT SHALL BE ANALOGOUS TO EXISTING
 DECORATIVE LIGHT POLES/FIXTURES ALONG N FLAGLER DR. & N
 QUADRILLE BLVD.
 4. POLE COLOR SHALL MATCH THE BLACK DECORATIVE LIGHT
 POLES/FIXTURES ALONG N FLAGLER DR. & N QUADRILLE BLVD.
 COLOR SHALL MATCH RAYCON RAL 7022 (UMBRA GREY), PLEASE
 CONTACT STAFF IF THERE ARE QUESTIONS OR CONCERNS WITH
 MATCHING THE POLE COLORS.
 5. THE POLE STEALTH DESIGN MEETS CITY STANDARDS.
  
 PLEASE NOTE IN FUTURE SUBMISSIONS FOR WCF PERMITS, THAT
 THE COMMUNICATIONS FACILITIES PLACEMENT PERMIT SHALL
 INCLUDE ANY WORK WITHIN THE ROW. LOCATION, POLES,
 UNDERGROUND CONDUIT PATHS, BOREPITS, HANDHOLES, ETC.
 ALL OF THESE ELEMENTS CAN BE COMBINED INTO A SINGLE
 PERMIT.
 THE UNDERGROUND ELECTRIC/FIBER/CONNECTIONS WILL BE
 SUBMITTED AS A SEPARATE PERMIT.
  
 CHRIS KIMMERLY @ (561)822-1426
 [email protected]
  