Plan Review Details - Permit 21120457
Plan Review Stops For Permit 21120457
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-05 Cont ID  
Sent By rmcdouga Date 2022-01-05 Time 06:52 Rev Time 0.00
Received By rmcdouga Date 2021-12-13 Time 06:59 Sent To  
Notes
***NONE***

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status F Date 2022-01-04 Cont ID  
Sent By shill Date 2022-01-04 Time 16:57 Rev Time 0.00
Received By jesmith Date 2022-02-01 Time 12:42 Sent To  
Notes
2022-01-04 16:57:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 NFPA 99-18 = HEALTH CARE FACILITIES CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21120457 3200 N MILITARY TRL
 MASTER 21010809
  
 1ST REVIEW
 MED GAS COMMENTS: DENIED
 PER WPB FBC 107.2.1, PROVIDE PLAN VIEW AND RISER
 DIAGRAM FOR O2 AND VACUUM PIPING NOTED ON P1.1.7 NOTE 4
 FOR DENTAL ROOM 127.
 PER WPB FBC 107.2.1, SHOW LOCATIONS OF O2 AND VACUUM
 OUTLETS.
 PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR O2 AND
 VACUUM OUTLETS.
 PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR O2 AND
 VACUUM PIPING.
 PER WPB FBC 107.2.1, PROVIDE SPECIFICATION O2 PIPE
 JOINTS.
 PER WPB FBC 107.2.1, NFPA 99-18 SECTION 1.3.1, STATES
 THAT VETERINARY FACILITIES ARE NOT GOVERNED BY THIS
 CODE. HOWEVER, OXYGEN CAN BE HAZARDOUS IF NOT PROPERLY
 ADDRESSED AND IT WOULD BE ADVISABLE TO INSTALL,
 FOLLOWING THE RULES LAID OUT IN NFPA 99-18 INCLUDING
 BRAZING REQUIREMENTS. IF YOU ARE ADHERING TO ANOTHER
 CODE OR REGULATION, PLEASE STATE AS MUCH AND PROVIDE
 THE DOCUMENTS FOR REFERENCE.
 P1.1.7 FOR AREA F; NOTE 4 INDICATES OXYGEN PIPING.
 P1.1.5 FROM MASTER PERMIT INDICATES AIR, NOT OXYGEN.
 PER WPB FBC 107.2.1, CLARIFY. IF THERE IS OXYGEN, THEN
 PER WPB FBC 107.2.1, PROVIDE EQUIPMENT SOURCE AND
 LOCATION OF SOURCE EQUIPMENT.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21120457 3200 N MILITARY TRL
 MASTER 21010809
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-01-04 Cont ID  
Sent By shill Date 2022-01-04 Time 16:56 Rev Time 0.00
Received By jesmith Date 2022-02-01 Time 12:42 Sent To  
Notes
2022-01-04 16:57:01CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21120457 3200 N MILITARY TRL
 MASTER 21010809
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 1. PER FBC PL 1002.4.1, PROVIDE TRAP SEAL PROTECTION
 FOR THE TRENCH DRAIN, COMPLYING WITH ONE OF THE METHODS
 IN SECTIONS 1002.4.1.1 THROUGH 1002.4.1.4.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21120457 3200 N MILITARY TRL
 MASTER 21010809
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2022-01-04 Cont ID  
Sent By shill Date 2022-01-04 Time 09:30 Rev Time 0.00
Received By shill Date 2022-01-04 Time 09:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-01-05 Cont ID  
Sent By rmcdouga Date 2022-01-05 Time 06:52 Rev Time 0.00
Received By rmcdouga Date 2022-01-05 Time 06:52 Sent To  
Notes
2022-01-05 06:54:15THE PLANS ARE NOT DIGITALLY SIGNED AND SEALED.
 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON THEM.
 YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED AND
 SEALED PAPER VERSION OF DRAWINGS. AFTER THE ELECTRONIC
 PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE
 CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT
 TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 481 & 61G1 OR FS 471 &
 61G15