Plan Review Details - Permit 21120392
Plan Review Stops For Permit 21120392
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-07-26 Cont ID  
Sent By jwitmer Date 2022-07-26 Time 15:32 Rev Time 0.00
Received By jwitmer Date 2022-07-26 Time 13:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-07-12 Cont ID  
Sent By pvalenti Date 2022-07-12 Time 16:23 Rev Time 0.00
Received By pvalenti Date 2022-07-12 Time 10:01 Sent To  
Notes
2022-07-12 16:39:28PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, PROVIDE MORE DETAILED INFORMATION.
  
 CONSIDERING SECTIONS 1012.5.2 & 1012.6.2 OF THE FBC EB
 THE EXISTING HEIGHT/AREA & WALL RATINGS HAVE BEEN MET.
 HOWEVER, AS PER FBC EB 1012.4.2, THE MEANS OF EGRESS
 DETAILS FROM FBC B CHAPTER 10 MUST BE IDENTIFIED.
  
 1.) IDENTIFY THE PANIC HARDWARE ON EGRESS DOORS AS PER
 SCTION FBC B 1010.1.10.
 2.) FBC B 107.2.1, INDICATE HOW THE ACCESS TO STAIRS AT
 1ST FLOOR WILL BE CLOSED OFF.
 3.) FBC B 107.2.1, PROVIDE A SIGNED LETTER FROM OWNER
 AND DESIGNER OF RECORD AS TO HOW AND WHY THE TOTAL
 OCCUPANT # IS AT 159 OCCUPANTS. CONSIDERING THE
 EDUCATION OCCUPANCY AND FBC B TABLE 1004.5 WE NEED TO
 BE SURE THAT WE WILL NOT HAVE AN OCCUPANCY ISSUE. FOR
 EXAMPLE, A CONFLICT WITH THE FUTURE NUMBER OF OCCUPANTS
 AND THE BATHROOM CAPACITY.
 4.) FBC B 468.3.5.2, INDICATE THE LOCATION OF STAFF
 BATHROOMS AND SEPARATE STUDENT BATHROOMS.
 5.) FBC B 468.3.7, INDICATE HOW THE LIGHTING IS SET UP
 TO MEET THE CODE REQUIREMENTS. AS THE EXISTING LIGHTING
 FROM THE LATS OCCUPANCY (RESTAURANT) MAY NOT BE
 SUFFICIENT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-03-09 Cont ID  
Sent By jwitmer Date 2022-03-09 Time 13:17 Rev Time 0.00
Received By jwitmer Date 2022-03-09 Time 10:50 Sent To  
Notes
2022-03-09 13:17:14WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT:21120392
 ADD: 2119 S DIXIE HWY.
 CONT: BELACRIS CONSTRUCTION
 TEL: 305-244-0277
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW / CHANGE OF OCCUPANCY
 DATE: WED. MARCH 09TH/ 2022
 ACTION: DENIED
  
  
 1) THE VALUE OF $185.00 DOLLARS WAS GIVEN FOR A CHANGE
 OF OCCUPANCY. THERE ARE SIGNED AND SEALED SHEETS FOR A
 PREVIOUS PERMIT, THEY COULD ONLY BE USED FOR REFERENCE
 ONLY. PLEASE PROVIDE A COMPLETE SET OF PLANS FOR A
 CHANGE OF OCCUPANCY, EDUCATIONAL.
  
 2) 2020 FBC-EXISTING BUILDING CODE SHOW COMPLIANCE FOR
 ALL OF CHAPTER 10 FOR ALL TRADES, CHANGE OF OCCUPANCY,
 1001.2.1- 1013.
  
 3) 2020 FBC-BUILDING 468 PRIVATE SCHOOLS SHOW
 COMPLIANCE WITH 468.1- 468.3.7.5.
  
 4) W 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY
 THE BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING
 MINIMUM CRITERIA AND DOCUMENTS: A FLOOR PLAN;
 SITE PLAN; FOUNDATION PLAN; FLOOR/ROOF FRAMING PLAN OR
 TRUSS LAYOUT; ALL FENESTRATION PENETRATIONS;
 FLASHING; AND ROUGH OPENING DIMENSIONS; AND ALL
 EXTERIOR ELEVATIONS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 1. SITE REQUIREMENTS:
 PARKING
 FIRE ACCESS
 VEHICLE LOADING
 DRIVING/TURNING RADIUS
 FIRE HYDRANT/WATER SUPPLY/POST INDICATOR VALVE (PIV)
 SET BACK/SEPARATION (ASSUMED PROPERTY LINES)
 LOCATION OF SPECIFIC TANKS, WATER LINES AND SEWER LINES
 FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD
 ELEVATIONS
 PROPOSED ELEVATION CERTIFICATE FOR STRUCTURES IN A
 SPECIAL FLOOD HAZARD AREA
 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE SECTION 503).
 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 FIRE BLOCKING AND DRAFT STOPPING AND CALCULATED FIRE
 RESISTANCE
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 EARLY WARNING SMOKE EVACUATION SYSTEMS
 SCHEMATIC FIRE SPRINKLERS
 STANDPIPES
 PRE-ENGINEERED SYSTEMS
 RISER DIAGRAM
 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING
 REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 EARLY WARNING
 SMOKE CONTROL
 STAIR PRESSURIZATION
 SYSTEMS SCHEMATIC
 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 SPECIFIC OCCUPANCY REQUIREMENTS
 CONSTRUCTION REQUIREMENTS
 HORIZONTAL EXITS/EXIT PASSAGEWAYS
  
 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 SOIL CONDITIONS/ANALYSIS
 TERMITE PROTECTION
 DESIGN LOADS
 WIND REQUIREMENTS
 BUILDING ENVELOPE/ COMPONENTS & CLADDING
 STRUCTURAL CALCULATIONS (IF REQUIRED)
 FOUNDATION
 FLOOD REQUIREMENTS IN ACCORDANCE WITH SECTION 1612,
 INCLUDING LOWEST FLOOR
 ELEVATIONS, ENCLOSURES, FLOOD DAMAGE-RESISTANT
 MATERIALS
 WALL SYSTEMS
 FLOOR SYSTEMS
 ROOF SYSTEMS
 THRESHOLD INSPECTION PLAN
 STAIR SYSTEMS
  
 9. MATERIALS SHALL BE REVIEWED AND SHALL AT A MINIMUM
 INCLUDE THE FOLLOWING:
 WOOD
 STEEL
 ALUMINUM
 CONCRETE
 PLASTIC
 GLASS
 MASONRY
 GYPSUM BOARD AND PLASTER
 INSULATING (MECHANICAL)
 ROOFING
 INSULATION
  
 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 VERTICAL ACCESSIBILITY
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS
 EQUIPMENT
 SPECIAL OCCUPANCY REQUIREMENTS
  
 11. INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
 LIGHT AND VENTILATION
 SANITATION
 12. SPECIAL SYSTEMS:
 ELEVATORS
 ESCALATORS
 LIFTS
 13. LOCATION AND INSTALLATION DETAILS. THE SPECIFIC
 LOCATION AND INSTALLATION DETAILS OF EACH
 FIRE DOOR, FIRE DAMPER, CEILING DAMPER AND SMOKE DAMPER
 SHALL BE SHOWN AND PROPERLY
 IDENTIFIED ON THE BUILDING PLANS BY THE DESIGNER.
  
 14) THE SURVEY SHOWS 2 BUILDINGS JUST WEST OF THE ALLEY
 WAY, IS THERE ANY WORK TO BE COMPLETED UNDER THIS
 PERMIT.
  
 15) PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 A TRANSMITTAL LETTER / NARRATIVE LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2022-08-01 Cont ID  
Sent By fgiaquin Date 2022-08-01 Time 23:48 Rev Time 0.00
Received By fgiaquin Date 2022-08-01 Time 23:46 Sent To  
Notes
2022-08-01 23:49:08NO ELEC WORK REVIEWED OR APPROVED. PER CONVO WITH MR.
 KEITH SPINA SCHOOL IS CHANGING TO PRIVATE SCHOOL ONLY.
 NO WORK TO BE PERFORMED.

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2022-07-06 Cont ID  
Sent By fgiaquin Date 2022-07-06 Time 20:10 Rev Time 0.00
Received By fgiaquin Date 2022-07-06 Time 18:53 Sent To  
Notes
2022-07-06 20:10:08NO ELEC WORK REVIEWED OR APPROVED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-03-14 Cont ID  
Sent By fgiaquin Date 2022-03-14 Time 22:58 Rev Time  
Received By fgiaquin Date   Time   Sent To  
Notes
2022-03-14 22:58:16ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW THAT COMPLIES
 WITH CHANGE OF OCCUPANCY STANDARDS IN THE FLORIDA
 BUILDING CODE EXISTING BUILDING BOOK.
  
 FBC-EB SECTION 1008
 ELECTRICAL
  
 2. PROVIDE ENERGY CONSERVATION CALCULATIONS SHOWING
 COMPLIANCE WITH THE CHANGE OF OCCUPANCY STANDARDS IN
 THE FLORIDA BUILDING CODEL ENERGY CONSERVATION BOOK.
  
 FBC-EC
 SECTIONC505
 CHANGE OF OCCUPANCY OR USE
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2022-08-03 Cont ID  
Sent By   Date 2022-08-03 Time   Rev Time 0.00
Received By bdolan Date 2022-08-03 Time 13:25 Sent To  
Notes
2022-08-03 13:50:01THE FOLLOWING COMMENTS WERE SUBMITTED BY LT. BRIAN
 DOLAN, DIVISION OF FIRE PREVENTION, WEST PALM BEACH
 FIRE RESCUE.
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THE LETTER FROM JEFFREY P. COLLINS, MS, PE HAS BEEN
 RECEIVED AND ACCEPTED BY THE DIVISION OF FIRE
 PREVENTION AS ACCEPTABLE IN ADDRESSING THE LIFE SAFETY
 CONCERNS REGARDING CHANGE OF USE TO AN EDUCATIONAL
 OCCUPANCY, SPECIFICALLY REGARDING THE FOLLOWING ITEMS:
  
 5. PROVIDE FIRE DEPARTMENT ACCESS TO THE AREAS THAT ARE
 BLOCKED OFF. THE WON DOORS CLOSING OFF THE STAIRWELLS
 WILL NEED TO BE ACCESSIBLE FOR MEANS OF EGRESS FROM THE
 STAIRWELL. KEYS FOR ENTRY MUST BE PROVIDED TO THE FIRE
 DEPARTMENT.
 6. FIRE EXTINGUISHER PLACEMENT SHOWN ON REVISED LS2.0.
 8. A DOOR SCHEDULE WITH HARDWARE IS REQUIRED. EXISTING
 DOORS PROVIDED IN SEPARATE DOCUMENT.
  
 TRAVEL DISTANCE COMPLIES WITH THE LIFE SAFETY CODE,
 NFPA 101 (FFPC.) THE SPRINKLER SYSTEM FOR THE ENTIRE
 BUILDING MUST BE FULLY OPERATIONAL. THE FIRE ALARM MUST
 ALSO BE FULLY OPERATIONAL.
 -SPRINKLER AND FIRE ALARM SYSTEMS REQUIRE SERVICE
 TESTING BY APPROPRIATE LICENSED/CERTIFIED
 CONTRACTOR(S).
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION PRIOR TO OCCUPANCY.
 FAILURE TO FOLLOW THESE PROVISO COMMENTS WILL RESULT IN
 A FAILED FIRE INSPECTION.
  
  
 PER CITY CODES, SITE IS SUBJECT TO FIELD INSPECTIONS,
 REQUIRED TESTING AND APPROVAL PRIOR TO OCCUPANCY IN NEW
 CLASSIFICATION.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2022-07-25 Cont ID  
Sent By   Date 2022-07-25 Time   Rev Time 0.00
Received By bdolan Date 2022-07-25 Time 12:00 Sent To  
Notes
2022-07-25 12:12:43THIS PLAN WAS REVIEWED AND FAILED BY LT. BRIAN DOLAN,
 DIVISION OF FIRE PREVENTION, WITH THE FOLLOWING
 COMMENTS:
  
 - FIRE SPRINKLER PERMIT FROM 2013 IS NOT VALID FOR
 CURRENT CHANGE OF USE REQUEST.
  
 - SPRINKLER SYSTEM REQUIRES EVALUATION FOR OPERABILITY
 AND SUITABILITY FOR PROPOSED OCCUPANCY.
  
 - FIRE ALARM PERMIT FROM 2014 IS NOT VALID FOR CURRENT
 CHANGE OF USE REQUEST.
  
 - FIRE ALARM SYSTEM REQUIRES EVALUATION AND TESTING FOR
 OPERABILITY AND SUITABILITY FOR PROPOSED OCCUPANCY.
  
 - THE AREA SHOWN IN DRAWING DOES NOT ADDRESS AREA FOR
 PROPOSED OCCUPANCY AREA IN CHANGE OF USE PERMIT REQUEST
  
 - ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 - INSTALLATION OF "LOCKED BARRIERS" FROM STAIRWELLS AS
 PROPOSED REQUIRES REVIEW AND APPROVAL BY A FIRE
 PROTECTION ENGINEER FOR SUITABILITY/POTENTIAL BARRIER
 TO EGRESS OR INGRESS OF EMERGENCY PERSONNEL.
  
 PER EMAIL FROM FIRE MARSHAL CHIEF PETER LEDUC 15 JULY
 2022:
  
  
 "SIR
  
 THANK YOU ONCE AGAIN FOR THE INFORMATION.
  
 YOU HAVE SUBMITTED INFORMATION FROM 2013-2015 AND I DO
 NOT SEE ANY INDICATION THAT THIS INFORMATION HAS BEEN
 REVIEWED/APPROVED BY A FPE MEETING THE CURRENT
 REQUIREMENTS OF AN EDUCATIONAL OCCUPANCY.
  
 RESPECTFULLY SUBMITTED.
  
  
 PETER LEDUC
 DIVISION CHIEF/FIRE MARSHAL
 WEST PALM BEACH FIRE DEPARTMENT"
  
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2022-06-24 Time   Rev Time 0.00
Received By bdolan Date 2022-06-24 Time 09:57 Sent To  
Notes
2022-06-24 10:05:53PER NFPA 1, THE PLAN SET PRESENTED DOES NOT PRESENT
 SUFFIECIENT INFORMATION TO CONSIDER A LIFE SAFETY
 REVIEW REGARDING AN EDUCATIONAL FACILITY. PLEASE CITE
 NFPA 101 REQUIREMENTS AS SPECIFIED IN NFPA 101, CH. 14
 NEW EDUCATIONAL OCCUPANCIES.
  
 WHAT ARE THE PROPOSED CHANGES TO THE DESIGNATED AREAS
 ON THE PLAN SET?
  
 ARE CHANGES TO THE STAIRS PLANNED? ELEVATOR SHAFT?
  
 CHANGE OF OCCUPANCY TYPE TO EDUCATIONAL CAN NOT BE
 GRANTED UNTIL ALL REQUIREMENTS OF A NEW EDUCATIONAL
 OCCUPANCY AS DEFINED IN NFPA 101 CH. 14 ARE MET.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-02-25 Cont ID  
Sent By   Date 2022-02-25 Time   Rev Time 0.00
Received By bdolan Date 2022-02-25 Time 13:39 Sent To  
Notes
2022-02-25 14:19:49THE FIRE DEPARTMENT DOES NOT HAVE ANY OBJECTION TO THE
 PLANNED PROJECT AND NEW USE OF THE OCCUPANCY, HOWEVER
 THE CURRENT PLAN DOES NOT HAVE ENOUGH DETAIL REGARDING
 FIRE CODE REQUIREMENTS TO APPROVE A CHANGE OF
 OCCUPANCY.
  
 PLEASE SUBMIT DETAILS FOR UPGRADING THE
 FACILITY/BUILDING TO MEET THE PROVISIONS OF NFPA 101,
 CHAPTER 14 NEW EDUCATIONAL OCCUPANCIES.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-03-08 Cont ID  
Sent By amhamilt Date 2022-03-08 Time 16:22 Rev Time 0.00
Received By amhamilt Date 2022-03-08 Time 16:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-08-03 Cont ID  
Sent By lmarchan Date 2022-08-03 Time 15:28 Rev Time 0.00
Received By lmarchan Date 2022-08-03 Time 12:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-08-01 Cont ID  
Sent By fgiaquin Date 2022-08-01 Time 23:49 Rev Time 0.00
Received By fgiaquin Date 2022-07-22 Time 07:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-12 Cont ID  
Sent By pvalenti Date 2022-07-12 Time 16:39 Rev Time 0.00
Received By pvalenti Date 2022-06-21 Time 17:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-14 Cont ID  
Sent By fgiaquin Date 2022-03-14 Time 23:09 Rev Time 0.00
Received By fgiaquin Date 2022-02-22 Time 09:32 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-08-12 Cont ID  
Sent By lmarchan Date 2022-08-12 Time 16:06 Rev Time 0.00
Received By lmarchan Date 2022-08-03 Time 15:27 Sent To  
Notes
2022-08-12 16:06:28MU:2022-037083-0000 - $0.00 NO FEES DUE
2022-08-03 15:28:018/3/22 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-03-09 Cont ID  
Sent By jwitmer Date 2022-03-09 Time 12:36 Rev Time 0.00
Received By jwitmer Date 2022-03-09 Time 10:50 Sent To  
Notes
2022-03-09 12:36:17IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected].
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2022-06-24 Cont ID  
Sent By medwards Date 2022-06-24 Time 14:44 Rev Time 0.00
Received By medwards Date 2022-06-24 Time 14:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-03-07 Cont ID  
Sent By medwards Date 2022-03-07 Time 10:43 Rev Time 0.00
Received By medwards Date 2022-03-07 Time 10:43 Sent To  
Notes
2022-03-07 10:46:24PLEASE PROVIDE DRAWINGS FOR THIS CHANGE OF OCCUPANCY
 AND USE OF SPACE SHOWING THIS NEW SCHOOL. THIS SHOULD
 ALSO SHOW THE CORRECTED OUTDOOR AIR CALCULATIONS FROM
 THE 202 FBC M 403.3.1.1 AND TABLE 403.3.1.1.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2022-06-24 Cont ID  
Sent By rwbrown Date 2022-06-24 Time 11:46 Rev Time 0.00
Received By rwbrown Date 2022-06-24 Time 11:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-03-01 Cont ID  
Sent By rwbrown Date 2022-03-01 Time 13:19 Rev Time 0.00
Received By rwbrown Date 2022-03-01 Time 13:14 Sent To  
Notes
2022-03-01 13:22:351ST PLUMBING REVIEW
  
 RESULTS: DENIED
  
 1. PER 1010.1 OF THE 2020 EXISTING BUILDING CODE,
 PLEASE SHOW COMPLIANCE WITH V7 FPC 403.1 - MINIMUM
 FACILITIES. PLEASE SHOW A COMPREHENSIVE TOTAL BUILDING
 OCCUPANT LOAD TO SHOW THIS BUILDING WILL BE IN
 COMPLAINCE WITH THE REQUIRED MINIMUM FACILITIES WITH
 THE NEW OCCUPANCY AND USE OF THIS BUILDING.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-08-01 Cont ID  
Sent By fgiaquin Date 2022-08-01 Time 23:49 Rev Time 0.00
Received By fgiaquin Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-07-12 Cont ID  
Sent By pvalenti Date 2022-07-12 Time 11:04 Rev Time 0.00
Received By pvalenti Date 2022-07-12 Time 10:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-03-14 Cont ID  
Sent By fgiaquin Date 2022-03-14 Time 23:07 Rev Time  
Received By fgiaquin Date   Time   Sent To  
Notes
2022-03-14 23:07:35ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLANS PROVIDED ARE OLD PLANS FROM 2013, ARE PAPER
 PLANS, AND ARE NOT DIGITALLY SIGNED. DIGITALLY
 SUBMITTED PLANS MUST BE DIGITALLY SIGNED BY THE DESIGN
 PROFESSIONAL.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop Z ZONING
Rev No 2 Status P Date 2022-07-07 Cont ID  
Sent By llouie Date 2022-07-07 Time   Rev Time 0.00
Received By llouie Date 2022-07-07 Time   Sent To  
Notes
2022-07-07 16:45:08* INTERIOR WORK TO CHANGE USE FROM RESTAURANT TO
 PRIVATE SCHOOL ONLY. EXTERIOR WORK REQUIRES SEPARATE
 PERMITS.
  
 * PRIVATE SCHOOL USE IS A PERMITTED USE BY-RIGHT IN GC.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-03-04 Cont ID  
Sent By llouie Date 2022-03-04 Time   Rev Time  
Received By llouie Date 2022-03-04 Time   Sent To  
Notes
2022-03-04 16:22:29** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) COORDINATION BETWEEN THE BUILDING PERMIT AND THE
 APPLICATION FOR THE PROPOSED GREENE SCHOOL COMMERCIAL
 PLANNED DEVELOPMENT (CPD), PENDING WITH PLANNING STAFF
 IS REQUIRED.
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: GC
  
 * REFERENCE: PB CASE NO. 1878 (GREENE SCHOOL CPD)
  