Plan Review Details - Permit 21120272
Plan Review Stops For Permit 21120272
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-03-10 Cont ID  
Sent By cpuell Date 2022-03-10 Time 16:00 Rev Time 0.00
Received By cpuell Date 2022-03-10 Time 16:00 Sent To  
Notes
2022-03-10 16:01:13ADDRESS APPROPRIATE FOR PROJECT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-12-21 Cont ID  
Sent By mpeterso Date 2021-12-21 Time 15:12 Rev Time 0.00
Received By mpeterso Date 2021-12-21 Time 15:12 Sent To  
Notes
2021-12-21 15:22:53ELECTRIC REVIEW FAILED
 1) INCORRECT SIZED OVERCURENT PROTECTION FOR SERVICE
 CONDUCTORS FROM METER TO PANELNEC 230.90 (A)
 2) PROVIDE AVAILABLE FAULT CURRENT FIELD MARKING AS
 REQUIRED AS PER NEC110.24
 3) PROVIDE ARC-FLASH HAZARD WARNING AS PROVIDED PER NEC
 110.16
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2022-03-10 Cont ID  
Sent By eschneid Date 2022-03-10 Time 15:17 Rev Time 0.00
Received By eschneid Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-17 Cont ID  
Sent By mpeterso Date 2022-03-17 Time 11:09 Rev Time 0.00
Received By mpeterso Date 2021-12-08 Time 06:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-03-17 Cont ID  
Sent By mpeterso Date 2022-03-17 Time 11:07 Rev Time 0.00
Received By mpeterso Date 2022-03-17 Time 11:07 Sent To  
Notes
2022-03-17 11:09:20IT APPEARS ALL DRAWINGS ARE COPIES/SCANS OF ENGINEERED,
 DIGITALLY SIGNED AND SEALED DRAWINGS, COPIES OR SCANS
 OF DOCUMENTS WITH ENGINEERS DIGITAL SIGNATURES CANNOT
 BE CERTIFIED USING SIGNATURE, CERTIFYING, SOFTWARE.
 PLANS SUBMITTED ELECTRONICALLY MUST BE DIGITALLY SIGNED
 AND SEALED BY THE ENGINEER OF RECORD. PLEASE FOLLOW THE
 DIRECTIONS OUTLINED BELOW TO CORRECT THIS ISSUE.
  
 FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND
 SIGNED.
  
 EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF
 APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX,
 OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER
 ORIGINAL WITH A WET SIGNATURE TO THE BUILDING
 DEPARTMENT.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO
 BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED
 DOCUMENTS ARE PREFERRED.
 PLEASE EMAIL [email protected] AND CC TO
 [email protected] WITH ANY QUESTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-03-16 Cont ID  
Sent By eschneid Date 2022-03-16 Time 11:36 Rev Time 0.25
Received By eschneid Date 2022-03-10 Time 15:17 Sent To  
Notes
2022-03-16 11:37:01FAILED
  
 1) A COMMUNICATION FACILITY PLACEMENT PERMIT - CITY
 RIGHTS-OF-WAY MUST BE APPROVED PRIOR TO THIS ELECTRIC
 PERMIT BEING APPROVED. THE PLANS INCLUDED WITH THIS
 ELECTRICAL PERMIT MUST MATCH THE PLANS APPROVED WITH
 THE COMMUNICATION FACILITY PLACEMENT PERMIT - CITY
 RIGHTS-OF-WAY PERMIT. PLEASE NOTE THAT A COMMUNICATION
 FACILITY PLACEMENT PERMIT - CITY RIGHTS-OF-WAY PERMIT
 APPLICATION WAS SUBMITTED TO THE CITY (21120654);
 HOWEVER, ON JANUARY 7, 2022, THE APPLICANT REQUESTED TO
 CANCEL THE PERMIT. WHILE NO ZONING REVIEW WAS DONE FOR
 THE COMMUNICATION FACILITY PLACEMENT PERMIT - CITY
 RIGHTS-OF-WAY PERMIT, THE COMMENTS BELOW WILL APPLY IF
 THE PERMIT IS REINSTATED.
  
 2) PROVIDE A SURVEY, PREPARED BY A FLORIDA LICENSED
 SURVEYOR, WHICH SHOWS THE POLE LOCATION, THE
 RIGHT-OF-WAY LINE, THE SIDEWALK, THE EDGE OF PAVEMENT,
 SURROUNDING FEATURES AND THE UNDERGROUND ELECTRIC,
 INCLUDING DIMENSIONS, SO THAT STAFF CAN VERIFY THAT THE
 WIRELESS COMMUNICATION FACILITY IS WITHIN THE
 RIGHT-OF-WAY, NOT ON PRIVATE PROPERTY AND DOES NOT
 IMPEDE THE SIDEWALK. THE SURVEY ALSO NEEDS TO INCLUDE
 THE HEIGHT OF THE EXISTING UTILITY POLE BEING USED TO
 ESTABLISH THE HEIGHT OF THE PROPOSED WIRELESS FACILITY,
 WHICH ALSO NEEDS TO BE PROVIDED.
  
 3) SHEET E201 SHOWS THAT THE PROPOSED WIRELESS FACILITY
 (POLE) DOES NOT MEET THE CITY OF WEST PALM BEACH
 CONCEALMENT (STEALTH) STYLE REQUIRED BY SECTIONS
 78-411(E) AND 78-411(F) OF THE CITY CODE. NOTE: THE
 COVER SHEET CALLS OUT THE USE OF A RAYCAP STEALTH POLE.
 ALL PLANS NEED TO SHOW THE STEALTH FACILITIES.
  
 4) PROVIDE A CROSS SECTION OF THE UNDERGROUND ELECTRIC
 WHICH VERIFIES THAT THERE ARE NO CONFLICTS WITH
 EXISTING UTILITIES.
  
 5) ADDITIONAL COMMENTS MAY BE ISSUED BASED ON PROVIDING
 THE INFORMATION REQUIRED BY THE PREVIOUS COMMENTS.
  
 6) THE POLE COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP
 7022 TRAFFIC GREY A.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446