Plan Review Details - Permit 21120271
Plan Review Stops For Permit 21120271
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-12-07 Cont ID  
Sent By cpuell Date 2021-12-07 Time 16:45 Rev Time 0.00
Received By cpuell Date 2021-12-07 Time 16:45 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2023-04-05 Cont ID  
Sent By sberglun Date 2023-04-05 Time 13:55 Rev Time 0.00
Received By sberglun Date 2023-04-05 Time 13:54 Sent To  
Notes
2023-04-05 13:55:06PLANS SUBMITTED IN JANUARY 2023 ARE APPROVED BY
 ENGINEERING.
 SUZANNE BERGLUND
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2022-06-23 Cont ID  
Sent By gpatrie Date 2022-05-17 Time 07:03 Rev Time 0.00
Received By sberglun Date 2022-06-23 Time 16:12 Sent To  
Notes
2022-06-23 16:14:531) CITY UTILITIES ARE SHOWN INCORRECTLY ON PLANS.
 INCLUDE CITY UNDERGROUND UTILITIY PIPE SIZE, PIPE
 MATERIAL, AND DESCRIPTION ON THE SITE PLAN. CONTACT
 JANICE TARBILL, [email protected] FOR AS-BUILT
 INFORMATION. INCLUDE AS-BUILT INFORMATION IN YOUR
 RESUBMITTAL.
 2) PROVIDE PROFILE FOR PROPOSED UNDERGROUND ELECTRIC
 SHOWING ALL CROSSING DATA FOR OTHER UTILITIES.
 3) ALL ROADWAY, SIDEWALK, AND SWALE RESTORATIONS ARE
 REQUIRED PER CITY STANDARD.
  
 SUZANNE BERGLUND
 [email protected]
 561-494-1075
  
2022-05-17 07:03:40THE POLE IS LOCATED ON THE CORNER OF THE HOUSE AND
 FOWARD OF EXISTING LIGHT POLE, THIS LOCATION IS
 ACCETABLE.
 RESPOND TO ZONEING NOTES.
  
 CONTACT: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-14 Cont ID  
Sent By aoliver Date 2023-04-14 Time 14:09 Rev Time 0.00
Received By aoliver Date 2023-01-18 Time 09:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-18 Cont ID  
Sent By aoliver Date 2022-05-18 Time 06:54 Rev Time 0.00
Received By aoliver Date 2021-12-07 Time 09:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-12-17 Cont ID  
Sent By shill Date 2021-12-17 Time 17:28 Rev Time 0.00
Received By shill Date 2021-12-17 Time 17:28 Sent To  
Notes
2021-12-17 17:28:51SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 COMMUNICATIONS APPLICATIONS - NEW PROCESS EFFECTIVE
 12/6/2021
  
 1. FOR ALL FUTURE SUBMITTALS, PRIOR TO SUBMISSION,
 CONTACT [email protected] TO OBTAIN THE CORRECT ADDRESS
 FOR YOUR APPLICATION. SHE WILL ASSIGN AN ADDRESS VIA
 EMAIL. WHEN YOU SUBMIT THE APPLICATION, INCLUDE THE
 EMAIL AS AN ATTACHMENT.
  
 2. FOR ALL FUTURE SUBMITTALS, TO SUBMIT THE
 COMMUNICATIONS APPLICATION, EMAIL THE COMPLETED
 APPLICATION TO [email protected]. THEY WILL
 GENERATE YOUR APPLICATION AND SEND YOU INSTRUCTIONS TO
 UPLOAD YOUR PLANS.
  
 3. FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS. IT APPEARS THAT THE
 DOCUMENTS SUBMITTED PAPER TO THE BUILDING DIVISION WERE
 DIGITALLY SIGNED PLANS THAT WERE PRINTED.
  
 IF THIS APPLICATION FAILS REVIEW - WHEN RESUBMITTING,
 UPLOAD INDIVIDUALLY SIGNED AND SEALED DRAWINGS IF
 POSSIBLE. IF YOU CANNOT OBTAIN PLANS IN THAT FORMAT,
 UPLOAD THE SINGLE MULTIPAGE DIGITALY SIGNED PDF TO THE
 SIGNATURE FOLDER.
  
 IF THIS APPLICATION PASSES REVIEW - UPLOAD THE
 DIGITALLY SIGNED DOCUMENTS (SHOULD BE IDENTICAL TO THE
 DOCUMENTS REVIEWED) TO THE SIGNATURE FOLDER.
  
 IF THE ENGINEER DOES NOT HAVE A DIGITAL SIGNATURE,
 PLEASE CONTACT ME DIRECTLY TO DISCUSS OPTIONS.
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2023-04-14 Cont ID  
Sent By eschneid Date 2023-04-14 Time 14:04 Rev Time 0.25
Received By eschneid Date 2023-04-13 Time 13:43 Sent To  
Notes
2023-04-13 15:01:00THE POLE COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP
 7042 TRAFFIC GREY A.

Review Stop Z ZONING
Rev No 1 Status F Date 2022-01-31 Cont ID  
Sent By eshneide Date 2022-01-31 Time 17:00 Rev Time 0.50
Received By eschneid Date 2022-01-31 Time 17:00 Sent To  
Notes
2022-01-31 17:00:42FAILED
  
 1) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS.
  
 2) THE CITY CODE REQUIRES THAT WIRELESS FACILITIES IN
 THE RIGHT-OF-WAY MAY WITHIN RESIDENTIAL DISTRICTS MAY
 NOT BE PLACED DIRECTLY IN FRONT OF A RESIDENTIAL
 STRUCTURE. PLEASE SHIFT THE POLE TO THE NORTH SO THAT
 IT IS IN LINE WITH OR SLIGHTLY PAST THE FRONT FACADE OF
 THE HOUSES ON EITHER SIDE OF EITHER SIDE OF MANNING
 AVENUE.
  
 3) THE POLE HEIGHT SHOWN ON SHEET C-3 LISTS THE HEIGHT
 TO THE TOP OF THE ANTENNA AS 28 FEET ABOVE GRADE;
 HOWEVER, THE SITE PLAN AND SURVEY CALL OUT A POLE 32
 FEET ABOVE GRADE LEVEL. ALL SHEETS MUST SHOW
 CONSISTENT, ACCURATE INFORMATION. NOTE: THE 32-FOOT
 HEIGHT IS CONSISTENT WITH ONE OF THE NEARBY POWER
 POLES.
  
 4) THE HANDHOLE AND BORE PIT NOTES ON SHEET P-1 STATE
 THAT THE SIDEWALK WILL BE RESTORED; HOWEVER, THESE ARE
 IN LANDSCAPED AREAS AND NOT OVERLAPPING WITH A
 SIDEWALK. PLEASE UPDATE THE NOTATIONS ACCORDINGLY.
  
 5) THE PLANS SHOW THE BORE PITS BEING DUG ADJACENT TO
 AN UNDERGROUND ELECTRIC LINE. IN ORDER TO VERIFY THAT
 THE INSTALLATION WILL NOT INTERFERE WITH THE EXISTING
 FACILITIES, PROVIDE A PUBLIC UTILITY LETTER OF NO
 OBJECTION FROM FPL REGARDING THE INSTALLATION.
  
 6) THE EDGE OF THE BORE PIT EXCAVATION ON THE EAST SIDE
 OF MANNING AVENUE, WEST OF THE HANDHOLE BY THE POWER
 POLE MUST BE RELOCATED AT LEAST FIVE FEET FROM THE
 TRUNK OF THE EXISTING PALM TREE. THE CURRENT LOCATION
 WILL DAMAGE THE ROOT SYSTEM OF THE EXISTING PALM TREE
 AND IS NOT PERMITTED.
  
 7) THE UNDERGROUND ELECTRIC BORE ON THE BORING PROFILE
 MUST BE CLEARLY SHOWN AVOIDING THE UNDERGROUND
 INFRASTRUCTURE IN THE RIGHT-OF-WAY (EX: WATER AND
 SANITARY LINES). PROVIDED THE SEPARATION IS MET IN
 COMMENT #6, THE 36-INCH DEPTH WILL AVOID THE PALM TREE
 ROOT SYSTEMS THAT IT CROSSES.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  