Plan Review Details - Permit 21120107
Plan Review Stops For Permit 21120107
Review Stop AD ADDRESSING
Rev No 4 Status P Date 2022-12-07 Cont ID  
Sent By cpuell Date 2022-12-07 Time 09:28 Rev Time 0.00
Received By cpuell Date 2022-12-07 Time 09:28 Sent To  
Notes
2022-12-07 09:29:35PARCEL 74434327890000022 ASSIGNED THE ADDRESS OF 2565 S
 FLAGLER DR

Review Stop AD ADDRESSING
Rev No 3 Status F Date 2022-09-23 Cont ID  
Sent By cpuell Date 2022-09-23 Time 14:44 Rev Time 0.00
Received By cpuell Date 2022-09-23 Time 14:44 Sent To  
Notes
2022-09-23 14:45:20AN ADDRESS NEEDS TO BE ASSIGNED TO 74434327890000022.
 PLEASE HAVE OWNER CONTACT [email protected] OR CALL
 561-805-6659

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2022-07-12 Cont ID  
Sent By cpuell Date 2022-07-12 Time 15:08 Rev Time 0.00
Received By cpuell Date 2022-07-12 Time 15:08 Sent To  
Notes
2022-07-12 15:10:46WARRENTY DEED DOES NOT ADDRESS MY COMMENTS. PLEASE
 RESPOND TO THE QUESTION, WHICH PARCEL DOES THE DOCK
 CORRESPOND TO 74434327890000032 OR 74434327890000022.
 PARCEL 74434327890000022 HAS YET TO BE GIVEN AN
 ADDRESS. PLEASE RESPOND TO [email protected] OR
 CALL 561-805-6659

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-05-23 Cont ID  
Sent By cpuell Date 2022-05-23 Time 09:20 Rev Time 0.00
Received By cpuell Date 2022-05-23 Time 09:20 Sent To  
Notes
2022-05-23 09:26:24PCN ON APPLICATION OF 74434327220140170 IS NOT LONGER A
 VALID PCN, IT USED TO BE ATTACHED TO 2501 S FLAGLER DR.
 2527 S FLAGLER DR WAS RECENTLY SUBDIVIDED, WHICH PARCEL
 IS THIS DOCK ATTACHED TO. IF IT IS THE EASTERN PARCEL
 WITH THE PCN OF 74434327890000022. PLEASE RESPOND TO
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-12-17 Cont ID  
Sent By cthroop Date 2021-12-17 Time 13:21 Rev Time 0.00
Received By cthroop Date 2021-12-17 Time 10:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2022-07-26 Cont ID  
Sent By jleahy Date 2022-07-26 Time 11:13 Rev Time 0.00
Received By jleahy Date 2022-07-26 Time 11:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-12-17 Cont ID  
Sent By jleahy Date 2021-12-17 Time 13:56 Rev Time 0.00
Received By jleahy Date 2021-12-17 Time 13:45 Sent To  
Notes
2021-12-17 13:57:27ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRICAL WORK SHOWN, PLEASE SHOW LAYOUT OF
 ELECTRICAL WORK AND WHERE IT COMES FROM.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-10-07 Cont ID  
Sent By lmarchan Date 2022-10-07 Time 16:36 Rev Time 0.00
Received By lmarchan Date 2022-09-23 Time 08:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-26 Cont ID  
Sent By jleahy Date 2022-07-26 Time 11:14 Rev Time 0.00
Received By jleahy Date 2022-07-12 Time 09:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-12-30 Cont ID  
Sent By cpuell Date 2021-12-30 Time 10:01 Rev Time 0.00
Received By cpuell Date 2021-12-17 Time 07:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-07-26 Cont ID  
Sent By jleahy Date 2022-07-26 Time 11:15 Rev Time 0.00
Received By jleahy Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-12-17 Cont ID  
Sent By cthroop Date 2021-12-17 Time 13:16 Rev Time 0.00
Received By cthroop Date 2021-12-17 Time 10:08 Sent To  
Notes
2021-12-17 13:19:23DESIGN PROFESSIONALS
  
 SIGNATURE REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC2017
  
 1ST REVIEW
 RESULTS: DENIED
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY
 DIGITAL SIGNATURES AND SEALS PER FS 668.003.
  
 THE DESIGNER OF THE STRUCTURAL SHEETS CANNOT
 SELF-CERTIFY THEIR DIGITAL SIGNATURE. THE SIGNATURE
 MUST BE THIRD PARTY VERIFIED.
 61G15-23.004 F.A.C.
 (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL
 SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL
 HAVE THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION
 AUTHORITY AND SHALL ASSURE THAT THE DIGITAL SIGNATURE
 IS: (A) UNIQUE TO THE PERSON USING IT; (B) CAPABLE OF
 VERIFICATION; AS OF NOVEMBER 16, 2020 63 (C) UNDER THE
 SOLE CONTROL OF THE PERSON USING IT; AND, (D) LINKED TO
 A DOCUMENT IN SUCH A MANNER THAT THE DIGITAL SIGNATURE
 AND CORRESPONDINGLY THE DOCUMENT IS INVALIDATED IF ANY
 DATA IN THE DOCUMENT IS CHANGED.
  
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  

Review Stop Z ZONING
Rev No 3 Status P Date 2022-10-07 Cont ID  
Sent By llouie Date 2022-10-07 Time   Rev Time 0.00
Received By llouie Date 2022-10-07 Time   Sent To  
Notes
2022-10-07 13:22:12ZONING APPROVED WITH THE FOLLOWING PROVISO:
  
 1.) SEPARATE PERMIT REQUIRED FOR BOATLIFTS.

Review Stop Z ZONING
Rev No 2 Status F Date 2022-07-25 Cont ID  
Sent By llouie Date 2022-07-25 Time 13:57 Rev Time 0.00
Received By llouie Date 2022-07-25 Time 13:57 Sent To  
Notes
2022-07-25 13:59:28** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PLEASE PROVIDE PROOF THAT THE PROPERTY OWNER IS THE
 HOLDER OF RIPARIAN RIGHTS. PROOF OF RIPARIAN RIGHTS MAY
 BE INCLUDED IN THE DEED FOR THE LAND, ETC. [ZLDR
 S.94-313.A.2.A.]
  
 [STAFF RESPONSE: NOT ADDRESSED. THE PROVIDED WARRANTY
 DEED AND SURVEY DOES NOT REFLECT THE OWNER ON RECORD
 FOR THE PROPERTY (2527 SOUTH FLAGLER LLC). THE
 INFORMATION MUST BE CONSISTENT.
  
  
 2.) THE SURVEY PROVIDED IS OUTDATED AND DOES NOT
 REFLECT THE CORRECT LOT LINES OR OWNERSHIP OF THE
 PROPERTY. THE SURVEY SHALL BE UPDATED AND SIGNED AND
 SEALED BY A FLORIDA REGISTERED LAND SURVEYOR.
  
 [STAFF RESPONSE: NOT ADDRESSED. ADDITIONALLY, THE
 SURVEY SHOULD ALSO DEPICT THE LOT DIVIDED INTO EQUAL
 THIRDS TO ACCURATELY DETERMINE THE MIDDLE ONE-THIRD OF
 THE LOT.]
  
  
 3.) LOCATION AND SETBACK OF ANY PORTION OF THE DOCK,
 PILINGS, BOATLIFTS, AND OTHER MOORING-RELATED
 FACILITIES SHALL BE CONSTRUCTED IN THE MIDDLE ONE-THIRD
 OF THE LOT ON WHICH A DOCK IS CONSTRUCTED, AS EXTENDED
 INTO THE WATERWAY. THE MIDDLE ONE-THIRD IS NOT DEPICTED
 ACCURATELY IN THE PLANS AND SHALL BE REVISED TO
 ACCURATELY REFLECT THE MIDDLE ONE THIRD OF THE LOT.
 [ZLDR S.94-313.H.]
  
 [STAFF RESPONSE: PARTIALLY ADDRESSED. THE UPDATED
 SIGNED AND SEALED SURVEY, DEPICTING THE MIDDLE
 ONE-THIRD IS NECESSARY TO DETERMINE IF ALL COMPONENTS
 OF THE DOCK IS LOCATED WITHIN THE MIDDLE ONE-THIRD. THE
 INFORMATION FROM THE SURVEY MUST BE TRANSPOSED INTO THE
 SITE PLAN.
  
  
 4.) A DOCK COVENANT IS REQUIRED. THE COVENANT NEEDS TO
 BE RECORDED BEFORE A PERMIT FOR DOCK CONSTRUCTION IS
 ISSUED.
  
 [STAFF RESPONSE: NOT ADDRESSED. THE REVISED COVENANT,
 CONTAINING THE CORRECTED INFORMATION, TO BE EXECUTED BY
 THE PROPERTY OWNER WAS SENT TO THE CONTRACTOR (WILLIAM
 EDRED) AND THE PROPERTY OWNER ON 7/13/22 VIA EMAIL.
 STAFF IS STILL WAITING ON THE RETURN OF THE COMPLETED
 DOCUMENT FOR FINAL REVIEW BY THE LAW DEPARTMENT AND THE
 MAYOR'S SIGNATURE.]
  
  
  
 NOTES:
  
 * PLEASE NOTE THAT IF ANY OF THE DIMENSIONAL
 REQUIREMENTS CANNOT BE MET, WAIVERS MUST BE GRANTED
 THROUGH THE CLASS A SPECIAL USE PERMIT PROCESS. THIS
 REQUIRES A SEPARATE APPLICATION AND FEES TO BE
 PROCESSED AND REVIEWED BY THE DEVELOPMENT SERVICES
 DEPARTMENT- PLANNING DIVISION. THE APPLICATION IS
 REQUIRED TO GO THROUGH THE PUBLIC HEARING PROCESS AND
 THE CLASS A SPECIAL USE PERMIT MUST BE GRANTED APPROVAL
 BY THE CITY COMMISSION.
  
 * SEPARATE PERMIT REQUIRED FOR BOATLIFT(S), SECURITY
 GATE.
  
 * ANY REVISIONS/RESUBMITTAL MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7-C5
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-12-30 Cont ID  
Sent By llouie Date 2021-12-30 Time   Rev Time  
Received By llouie Date 2021-12-30 Time   Sent To  
Notes
2021-12-30 09:20:13** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PLEASE PROVIDE PROOF THAT THE PROPERTY OWNER IS THE
 HOLDER OF RIPARIAN RIGHTS. PROOF OF RIPARIAN RIGHTS MAY
 BE INCLUDED IN THE DEED FOR THE LAND, ETC. [ZLDR
 S.94-313.A.2.A.]
  
 2.) LOCATION AND SETBACK OF ANY PORTION OF THE DOCK,
 PILINGS, BOATLIFTS, AND OTHER MOORING-RELATED
 FACILITIES SHALL BE CONSTRUCTED IN THE MIDDLE ONE-THIRD
 OF THE LOT ON WHICH A DOCK IS CONSTRUCTED, AS EXTENDED
 INTO THE WATERWAY. THE MIDDLE ONE-THIRD IS NOT DEPICTED
 ACCURATELY IN THE PLANS AND SHALL BE REVISED TO
 ACCURATELY REFLECT THE MIDDLE ONE THIRD OF THE LOT.
 [ZLDR S.94-313.H.]
  
 3.) THE MAXIMUM DOCK LENGTH SHALL NOT EXCEED 100 FT. IN
 LENGTH. ACCORDING TO THE PROVIDED PLANS, THE PROPOSED
 LENGTH OF THE DOCK IS 130 FT. LONG. [ZLDR S.94-313.I.]
  
 4.) THE MAXIMUM WIDTH OF A DOCK SHALL NOT EXCEED 10 FT.
 FINGER PIERS AND TERMINAL PLATFORMS WHICH ARE
 PERPENDICULAR TO THE DOCK AND PARALLEL TO THE SEAWALL,
 BULKHEAD, OR RIPARIAN PROPERTY LINE MAY BE GREATER THAN
 10 FT. IN WIDTH (MEASURED PARALLEL TO THE DOCK)
 PROVIDED THAT THEY REMAIN WITHIN THE MIDDLE ONE-THIRD
 OF THE PROPERTY AND DO NOT EXCEED 10 FT. IN LENGTH
 (MEASURED PERPENDICULAR TO THE DOCK). THE PLANS FOR THE
 DOCK DO NOT COMPLY WITH THE DIMENSIONAL REQUIREMENTS
 FOR DOCK WIDTH. [ZLDR S.94-313.J.]
  
 5.) AT LEAST ONE LADDER SHALL BE PROVIDED FOR EACH
 DOCK, EXTENDING FROM THE DOCK SURFACE TO TWO FEET BELOW
 THE MEAN WATER LINE. THE LADDER HAS NOT BEEN DEPICTED
 IN THE PLANS. [ZLDR S.94-313.L.]
  
 6.) BOAT LIFT(S) SHALL BE DESIGNED BY A REGISTERED
 PROFESSIONAL ENGINEER AND SHALL BE REVIEWED UNDER A
 SEPARATE PERMIT APPLICATION; HOWEVER, THE PLANS MUST
 CLEARLY SHOW WHERE THE BOAT LIFTS WILL BE LOCATED IN
 RELATION TO THE OVERALL DOCK AND THE MIDDLE ONE-THIRD
 OF THE LOT. A PLAN SHEET IMPLIES A BOAT LIFT WILL BE
 DESIGNED INTO THE DOCK; HOWEVER, THE PLACEMENT/LOCATION
 OF THE BOAT LIFT IS NOT PROVIDED IN THE SITE PLAN.
 [ZLDR S.94-313.H. AND Q.]
  
 7.) WILL THERE BE LIGHTING FOR THE DOCK? ANY LIGHT
 FIXTURES FOR THE DOCK MUST BE SHOWN IN THE PLANS;
 HOWEVER, IT MUST BE APPROVED UNDER A SEPARATE PERMIT.
 PER S.94-313.P. OF THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS), ARTIFICIAL LIGHTING
 MAY BE INSTALLED ON A DOCK FOR SECURITY OR SAFETY BUT
 SHALL NOT LIGHT SURROUNDING PROPERTIES. BLINKING OR
 INTERMITTENT LIGHTS ARE PROHIBITED. IF LIGHTS ARE TO BE
 PROVIDED, PLEASE PROVIDE A NOTE INDICATING THAT
 LIGHTING WILL BE REVIEWED UNDER A SEPARATE PERMIT AND A
 NOTE STATING THAT THE LIGHTING SHALL NOT LIGHT
 SURROUNDING PROPERTIES; BLINKING OR INTERMITTENT LIGHTS
 ARE PROHIBITED.
  
 8.) SINCE THE PROPERTY IS NON-CONTIGUOUS TO THE WATER,
 WILL THERE BE A SECURITY FENCE INSTALLED? IF SO,
 DETAILS SHALL BE PROVIDED WITH THE PERMIT PLANS THAT
 ARE CONSISTENT WITH THE DESIGN REQUIREMENTS OF THE
 ZLDRS. [ZLDR S.94-313.4.A.]
  
 9.) THE FOLLOWING NOTES SHALL BE PROVIDED IN THE PLANS
 FOR CONSISTENCY WITH THE ZONING REGULATIONS FOR DOCK
 CONSTRUCTION: * THE DOCK IS FOR PRIVATE USE ONLY. * ALL
 DOCKS SHALL HAVE WATER-RESISTANT REFLECTIVE NUMERALS
 CORRESPONDING TO THE STREET ADDRESS OF THE UPLAND
 PROPERTY AND SHALL BE VISIBLE FROM THE WATERWAY.
  
 10.) A DOCK COVENANT IS REQUIRED. THE CONVENANT NEEDS
 TO BE RECORDED BEFORE A PERMIT FOR DOCK CONSTRUCTION IS
 ISSUED.
  
  
 NOTES:
  
 * PLEASE NOTE THAT IF ANY OF THE DIMENSIONAL
 REQUIREMENTS CANNOT BE MET, WAIVERS MUST BE GRANTED
 THROUGH THE CLASS A SPECIAL USE PERMIT PROCESS. THIS
 REQUIRES A SEPARATE APPLICATION AND FEES TO BE
 PROCESSED AND REVIEWED BY THE DEVELOPMENT SERVICES
 DEPARTMENT- PLANNING DIVISION. THE APPLICATION IS
 REQUIRED TO GO THROUGH THE PUBLIC HEARING PROCESS AND
 THE CLASS A SPECIAL USE PERMIT MUST BE GRANTED APPROVAL
 BY THE CITY COMMISSION.
  
 * ANY REVISIONS/RESUBMITTAL MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7-C5
  