Plan Review Details - Permit 21111211
Plan Review Stops For Permit 21111211
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2021-12-27 Cont ID  
Sent By jwitmer Date 2021-12-27 Time 15:08 Rev Time 0.00
Received By jwitmer Date 2021-12-27 Time 15:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-12-27 Cont ID  
Sent By jwitmer Date 2021-12-27 Time 15:52 Rev Time 0.00
Received By jwitmer Date 2021-12-27 Time 15:07 Sent To  
Notes
2021-12-27 15:07:28WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21111211
 ADD: 319 CLEMATIS ST. # 300
 CONT: TBD/ TO BE DETERMINED
 TEL: ???
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A0.2 ADA NOTES SHOWS A HIGH/ LOW WATER
 FOUNTAIN AND WOULD MEET COMPLIANCE WITH THE 2020
 FBC-ACCESSIBILITY CODE SECTION 211.2 MINIMUM NUMBER. NO
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7. THE LIFE SAFETY PLAN NOR SHEET A1.1 SHOW
 EXISTING DRINKING FOUNTAINS IN THE COMMON AREA OF THIS
 FLOOR, AND THERE IS NO NOTE STATING THERE ARE ADA
 DRINKING FOUNTAINS COMPLYING WITH 211.2 MINIMUM NUMBER
 OF ACCESSIBLE DRINKING FOUNTAINS ON THE FLOOR ABOVE OR
 FLOOR BELOW. THE WATER COOLER SHOWN ON SHEETS A1.1 AND
 A3.2 DOES NOT SHOW COMPLIANCE FOR ACCESSIBLE DRINKING
 FOUNTAINS.
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-01-07 Cont ID  
Sent By jleahy Date 2022-01-07 Time 15:16 Rev Time 0.00
Received By jleahy Date 2022-01-07 Time 15:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-12-03 Cont ID  
Sent By pleduc Date 2021-12-03 Time   Rev Time 0.00
Received By pleduc Date 2021-12-03 Time 14:00 Sent To  
Notes
2021-12-03 14:04:34FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-07 Cont ID  
Sent By jleahy Date 2022-01-07 Time 15:16 Rev Time 0.00
Received By jleahy Date 2021-12-02 Time 09:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-12-07 Cont ID  
Sent By medwards Date 2021-12-07 Time 10:54 Rev Time 0.00
Received By medwards Date 2021-12-07 Time 10:50 Sent To  
Notes
2021-12-07 10:59:13SHEET P3.1; THE CONDENSATE DRAIN PIPE MUST MEET THE
 MINIMUM SIZE.
  
 307.2.2 DRAIN PIPE MATERIALS AND SIZES. COMPONENTS OF
 THE CONDENSATE DISPOSAL SYSTEM SHALL BE CAST IRON,
 GALVANIZED STEEL, BRASS, COPPER AND COPPER ALLOY,
 CROSS-LINKED POLYETHYLENE, POLYETHYLENE, ABS, CPVC,
 PVC, OR POLYPROPYLENE PIPE OR TUBING. COMPONENTS SHALL
 BE SELECTED FOR THE PRESSURE AND TEMPERATURE RATING OF
 THE INSTALLATION. JOINTS AND CONNECTIONS SHALL BE MADE
 IN ACCORDANCE WITH THE APPLICABLE PROVISIONS OF CHAPTER
 7 OF THE FLORIDA BUILDING CODE, PLUMBING RELATIVE TO
 THE MATERIAL TYPE. CONDENSATE WASTE AND DRAIN LINE SIZE
 SHALL BE NOT LESS THAN 3/4-INCH (19.1 MM) INTERNAL
 DIAMETER AND SHALL NOT DECREASE IN SIZE FROM THE DRAIN
 PAN CONNECTION TO THE PLACE OF CONDENSATE DISPOSAL.
 WHERE THE DRAIN PIPES FROM MORE THAN ONE UNIT ARE
 MANIFOLDED TOGETHER FOR CONDENSATE DRAINAGE, THE PIPE
 OR TUBING SHALL BE SIZED IN ACCORDANCE WITH TABLE
 307.2.2.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-12-15 Cont ID  
Sent By ccole Date 2021-12-15 Time 14:56 Rev Time 0.00
Received By ccole Date 2021-12-15 Time 12:12 Sent To  
Notes
2021-12-15 14:57:001ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21111211
 12/15/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P2.1 & P5.1: THE ISO SHOWS THE SINK PUMP VENT
 PIPE CONNECTING TO THE EXISTING RISER BUT SINK PUMP
 DETAIL SHOWS AN AAV- WHICH IS CORRECT?- SEC 906.5 FBC
 P.
  
 2) P2.1: PLEASE SHOW THE LOCATIONS OF THE REQUIRED
 CHECK VALVE AND FULL OPEN VALVES ON THE DISCHARGE PIPE,
 AND SHOW HOW ACCESS TO THE VALVES WILL BE PROVIDED-
 SEC. 712.2 FBC P.
  
 3) A1.1: SHOW THE CLEAR FLOOR SPACE APPROACH DIAGRAMS
 AND DIMENSIONS AT WATER DISPENSER, DISHWASHER AND
 REFRIGERATOR- SECTIONS 305, 804.6.3 & 804.6.6 FBC ACC.
  
 4) A1.1 & A3.2: PROVIDE AN ELEVATION DETAIL OR NOTE TO
 VERIFY THE FREEZER INSIDE THE REFRIGERATOR HAS A
 MINIMUM OF 50 PERCENT OF FREEZER SPACE 54-INCHES
 MAXIMUM FROM THE FINISHED FLOOR.
  
 D) A1.1 & A3.2: SHOW THE HEIGHT OF THE WATER DISPENSER
 CONTROL AND INDICATE COMPLIANCE WITH SEC. 308- REACH
 RANGES, AND 309- OPERABLE PARTS. PLEASE SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE DISPENSER
 INDICATING ADA COMPLIANCE- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-01-07 Cont ID  
Sent By jleahy Date 2022-01-07 Time 15:16 Rev Time 0.00
Received By jleahy Date 2022-01-07 Time 15:05 Sent To  
Notes
***NONE***