Plan Review Stops For Permit 21110989 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2022-03-22 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-03-22 |
Time |
16:01 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-03-22 |
Time |
16:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2022-02-15 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-02-15 |
Time |
14:15 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-02-15 |
Time |
14:01 |
Sent To |
|
|
Notes |
2022-02-15 14:15:54 | CAR CHARGING STATIONS | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) SPOT LIGHT SOLAR STRUCTURE IS SUBJECT TO WIND LOADS | | - PLEASE PROVIDE DETAILS FROM A DESIGN PROFESSIONAL TO | | MEET THE REQUIRED WIND LOADS FBC 1609 | | | | 2) PLEASE PROVIDE THE SOLAR CANOPY DETAILS FROM A | | DESIGN PROFESSIONAL - FOR THE SOLAR CANOPY SHOWN OVER | | THE TABLE (SOLAR ZONE) - WILL NEED TO MEET THE REQUIRED | | WIND LOADS FBC 1609 | | | | 3) SOLAR CANOPY DETAILS PROVIDED - DRAWING T1.0 AND THE | | PROVIDED CALCULATIONS SHOWS WIND DESIGN AS RISK | | CATEGORY II WITH WIND SPEED OF 169 MPH = RISK CATEGORY | | II REQUIRES A DESIGN WIND SPEED OF 170 MPH PER FBC WPB | | SECTION 120 | | | | 4) A SEPARATE PERMIT IS REQUIRED FOR THE MONUMENT | | SIGNAGE. | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2022-01-10 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-01-10 |
Time |
11:17 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-01-10 |
Time |
10:35 |
Sent To |
|
|
Notes |
2022-01-10 11:16:56 | CAR CHARGING STATIONS | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) THE ACCESSIBLE PARKING PLACE NEEDS TO BE MARKED | | (SIGNAGE) TO BE USED ONLY AS AN ACCESSIBLE SPACE PER | | FBC 502.6 - 502.6.1 | | EACH SUCH PARKING SPACE MUST BE STRIPED IN A MANNER | | THAT IS CONSISTENT WITH THE STANDARDS OF THE | | CONTROLLING JURISDICTION FOR OTHER SPACES AND | | PROMINENTLY OUTLINED WITH BLUE PAINT, | | | | 2) PLEASE PROVIDE THE SOLAR CANOPY DETAILS - WILL NEED | | TO MEET THE REQUIRED WIND LOADS FBC 1609 | | | | 3) SOLAR CANOPY MAY BE DEFERRED SUBMITTALS BY LISTING | | ITEMS TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS - | | 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS | | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS | | FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR | | DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE | | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE | | WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING | | OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED | | SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE | | IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. | | THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED | | UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN | | APPROVED BY THE BUILDING OFFICIAL. | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2022-03-31 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-03-31 |
Time |
15:55 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-03-31 |
Time |
15:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2022-02-24 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-02-24 |
Time |
14:53 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-02-22 |
Time |
11:37 |
Sent To |
|
|
Notes |
2022-02-24 15:02:04 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | 5TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | PART VIII ELECTRICAL | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | 1) THE FOLLOWING EQUIPMENT NEEDS TO SHOW THE LISTING | | FOR THE EQUIPMENT | | | | INSTALLATION AND USE. LISTED OR LABELED EQUIPMENT SHALL | | BE INSTALLED AND USED IN ACCORDANCE WITH ANY | | INSTRUCTIONS INCLUDED | | IN THE LISTING OR LABELING. | | LISTING. PRODUCT TESTING, EVALUATION, AND LISTING | | (PRODUCT CERTIFICATION) SHALL BE PERFORMED BY | | RECOGNIZED QUALIFIED ELECTRICAL | | TESTING LABORATORIES AND SHALL BE IN ACCORDANCE WITH | | APPLICABLE PRODUCT STANDARDS RECOGNIZED AS ACHIEVING | | EQUIVALENT | | AND EFFECTIVE SAFETY FOR EQUIPMENT INSTALLED TO COMPLY | | WITH THIS CODE. | | | | SOLAR TREE, BATTERY RACK, BESS NEA CONTROLLER, BESS | | IMM, BESS CONTROL CABINET, BESS FIREWALL, 7580 PT | | OVERALL DIMS, OPTOS, OUTDOOR LIQUID COOLING RACK, | | AIR INFLATOR, INVERTER MPS125 EHV, NBDC, NBSK. | | | | 2) PAGE E-201 | | | | FAULT CURRENT CALCULATION 110.9, 110.10 | | OVERCURRENT PROTECTION FOR NBDC UNITS 500, 200 NEEDS TO | | SHOW SOMWHERE WHAT SIZE BREAKERS ARE BEING USED. | | LISTING FOR THE LINE SIDE TAP IN THE NBSK 112500S | | 110.3, 110.9, 110.10 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2022-01-11 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-01-11 |
Time |
09:00 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-01-11 |
Time |
07:30 |
Sent To |
|
|
Notes |
2022-01-11 09:10:51 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | 1) PLEASE PROVIDE A COST BREAK DOWN OF ALL MATERIALS | | (CUSTOMER AND CONTRACTOR SUPPLIED) AND LABOR FOR THIS | | PROJECT. | | | | 2) PROVIDE LISTINGS AND CUT SHEETS FOR "ALL" EQUIPMENT | | BEING USED ON THIS PROJECT. 110.3 | | | | 3) DISPENSERS SHOW NO OVER CURRENT PROTECTION OTHER | | THAN THE MAIN AT 2500 AMPERES. | | | | 4) SEPARATE PERMIT FOR SIGNS REQUIRED. | | | | 5) NO DETAILS FOR CANOPY AND TREE SOLAR PROJECTS. |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
F |
Date |
2022-04-18 |
|
|
Cont ID |
|
Sent By |
rrossano |
Date |
2022-04-18 |
Time |
|
Rev Time |
0.00 |
Received By |
rrossano |
Date |
2022-04-18 |
Time |
|
Sent To |
I |
|
Notes |
2022-04-18 11:30:13 | 1. SHEETS C-200, C-203 | | A. REVISION #2 NOTE MENTIONS SHIFTING PROPOSED MANHOLE | | 16 FEET TO THE WEST TO AVOID ELECTRICAL CONDUITS. STAFF | | ASSUMES THIS IS REFERRING TO MH#1. HOW WILL THE SYSTEM | | CONNECT TO THE TWO EXISTING STORM PIPES GOING SOUTH OUT | | OF THE PROPOSED MH#1 IF THE MH IS SHIFTED TO THE WEST? | | B. SUGGEST REMOVING THE RAISED CURB OR MAKING IT | | MOUNTABLE TO THE SOUTH OF MH#1 UNLESS THE DRIVEWAY IS | | ENTRANCE ONLY. EXISTING CARS TURNING TO THE RIGHT MAY | | CLIP THE CORNER AND THE RAISED CURB. | | | | WITH REGARDS, | | TRACY L. WARD, P.E. | | SENIOR STORMWATER ENGINEER | | CITY OF WEST PALM BEACH | | ENGINEERING SERVICES DEPARTMENT | | 401 CLEMATIS ST., 4TH FLOOR | | WEST PALM BEACH, FL 33401 | | PHONE: 561-494-1120 | | FAX: 561-494-1116 | | CELL 561-351-0510 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2022-03-18 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2022-03-18 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2022-03-18 |
Time |
11:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2022-02-07 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2022-02-07 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2022-02-07 |
Time |
11:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2021-12-17 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2021-12-17 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2021-12-17 |
Time |
11:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2022-04-08 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-04-08 |
Time |
08:47 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-04-07 |
Time |
14:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2022-03-31 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-03-31 |
Time |
15:55 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-03-17 |
Time |
09:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2022-03-31 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-03-31 |
Time |
15:55 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-03-17 |
Time |
09:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2022-02-24 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-02-24 |
Time |
15:02 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-02-06 |
Time |
08:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-01-14 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2022-01-14 |
Time |
09:13 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2021-12-09 |
Time |
06:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
N |
Date |
2022-03-29 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2022-03-29 |
Time |
07:24 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2022-03-18 |
Time |
15:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2022-02-18 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2022-02-16 |
Time |
14:28 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2022-02-16 |
Time |
11:14 |
Sent To |
|
|
Notes |
2022-02-18 07:33:37 | 1ST REVIEW FBC-2020 PLUMBING | | PERMIT-21110989 | | 2/18/2022 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PROVIDE PLUMBING FIXTURE CALCULATIONS FOR THE | | FACILITY IN ACCORDANCE WITH SECTION AND TABLE 403.1 FBC | | P. THE PLANS DO NOT SHOW ANY RESTROOMS ONSITE. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
5 |
Status |
P |
Date |
2022-04-08 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-04-08 |
Time |
08:47 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-04-08 |
Time |
08:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
4 |
Status |
F |
Date |
2022-03-22 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-03-22 |
Time |
16:23 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-03-22 |
Time |
16:23 |
Sent To |
|
|
Notes |
2022-03-22 16:25:57 | SIGNATURE REVIEW | | | | CORRECTIONS NEEDED - | | | | 1) DRAWINGS LABELED "EV CHARGING PLAZA CANOPY" SIGNED | | BY D. TODD ELAYER ON 2/18/22 AND THE "STRUCTURAL | | CALCULATIONS FOR THE LUMUS EV CHARGING PLAZA CANOPY" | | SIGNED BY D. TODD ELAYER DATED 2/17/22 DO NOT SHOW AS | | DIGITALLY SIGNED IN ADOBE READER - | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A | | CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED | | A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF | | E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES | | NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN | | DROP OFF THE ORIGINAL SIGNED AND SEALED | | DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING | | DIVISION AT THE CITY HALL. | | | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2022-02-22 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-02-22 |
Time |
10:21 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-02-22 |
Time |
10:21 |
Sent To |
|
|
Notes |
2022-02-22 10:22:46 | SIGNATURE FOR THE SURVEY IS OK, SENT TO STORAGE JLEAHY |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2022-02-15 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-02-15 |
Time |
14:16 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-02-15 |
Time |
14:16 |
Sent To |
|
|
Notes |
2022-02-15 14:25:49 | SIGNATURE REVIEW | | | | CORRECTIONS NEEDED - | | | | 1) THE SURVEY PROVIDED DOES NOT SHOW AS DIGITALLY | | SIGNED IN ADOBE READER - | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A | | CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED | | A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF | | E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES | | NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN | | DROP OFF THE ORIGINAL SIGNED AND SEALED | | DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING | | DIVISION AT THE CITY HALL. | | | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2022-01-10 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-01-10 |
Time |
11:17 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-01-10 |
Time |
11:17 |
Sent To |
|
|
Notes |
2022-01-10 11:18:39 | SIGNATURE REVIEW | | | | CORRECTIONS NEEDED - | | | | 1) ALL OF THE DRAWINGS DO NOT SHOW AS DIGITALLY SIGNED | | IN ADOBE READER - | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A | | CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED | | A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF | | E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES | | NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN | | DROP OFF THE ORIGINAL SIGNED AND SEALED | | DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING | | DIVISION AT THE CITY HALL. | | | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2022-03-25 |
|
|
Cont ID |
|
Sent By |
ckimmerl |
Date |
2022-03-25 |
Time |
11:56 |
Rev Time |
0.00 |
Received By |
ckimmerl |
Date |
2022-03-25 |
Time |
11:56 |
Sent To |
|
|
Notes |
2022-03-25 11:56:47 | PROVISO: APPROVED SITE PLANS (SHEET FSPR-1) SHOWS A | | PLANTER/GREENWALL INCLUDED ON THE SOUTH SIDE OF | | ENCLOSURE. PLEASE INCLUDE AND ADD BACK | | GREENWALL/PLANTER ELEMENT TO THE SOUTH SIDE OF | | ENCLOSURE ON THE SITE/CIVIL PLANS. PROPOSED TV UNIT CAN | | BE INCORPORATED WITHIN GREENWALL OR ABOVE PLANTER. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2022-02-23 |
|
|
Cont ID |
|
Sent By |
ckimmerl |
Date |
2022-02-23 |
Time |
15:19 |
Rev Time |
0.00 |
Received By |
ckimmerl |
Date |
2022-02-23 |
Time |
15:14 |
Sent To |
|
|
Notes |
2022-02-23 15:19:26 | PROVISO: APPROVED SITE PLANS (SHEET FSPR-1) SHOWS A | | PLANTER/GREENWALL INCLUDED ON THE SOUTH SIDE OF | | ENCLOSURE. PLEASE INCLUDE AND ADD BACK | | GREENWALL/PLANTER ELEMENT TO THE SOUTH SIDE OF | | ENCLOSURE ON THE SITE/CIVIL PLANS. PROPOSED TV UNIT CAN | | BE INCORPORATED WITHIN GREENWALL OR ABOVE PLANTER. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2022-01-13 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2022-01-13 |
Time |
08:23 |
Rev Time |
0.00 |
Received By |
ckimmerl |
Date |
2022-01-13 |
Time |
08:16 |
Sent To |
|
|
Notes |
2022-01-13 08:23:46 | 1. PLEASE PROVIDE ADDITIONAL INFORMATION THAT THE | | SIDEWALK ELEVATION IS MAINTAINED AS A LEVEL SURFACE | | ALONG THE DATURA FRONTAGE & ENTRANCE. | | | | 2. APPROVED SITE PLAN INCLUDED GREEN WALL ON THE | | SOUTHERN WALL OF THE EQUIPMENT ENCLOSURE. | | | | 3. IF THE DRIVEWAY ON DATURA IS TO BE A TWO-WAY, PLEASE | | INDICATE. | | | | 4. THE REMOVABLE FENCE SHALL BE UNDER A SEPARATE | | PERMIT. PLEASE REMOVE FENCE DETAILS FROM THIS PERMIT | | SET. FENCE SHALL ALSO BE OPAQUE/HAVE OPAQUE SCREENING | | AS IS REQUIRED. | | | | 5. SUBMIT SEPARATE LANDSCAPE PERMIT. | | | | 6. PLEASE PROVIDE DETAIL FOR THE PARKING STRIPING TO | | MEET CITY STANDARDS. | | | | 7. PLEASE INCLIDE DETAIL OF THE SOLAR CANOPY OVER THE | | PARKING LOT. | | | | 8. PLEASE PROVIDE DETAIL OF SOLAR TREES. | | | | 9. PLEASE INDICATE IF THE CONCRETE POLE BEHIND THE | | NOTHERN DECORATIVE COLUMN WILL BE REMOVED OR RELOCATED. |
|
|