Plan Review Details - Permit 21110886
Plan Review Stops For Permit 21110886 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2022-02-09 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2022-02-09 |
Time |
08:12 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2022-02-09 |
Time |
08:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2021-12-27 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2021-12-27 |
Time |
10:33 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2021-12-27 |
Time |
10:33 |
Sent To |
|
|
Notes |
2021-12-27 10:35:52 | IT APPEARS DRAWINGS "FA1 AND FA2" ARE COPIES OF A | | SIGNED AND SEALED DRAWINGS OF THE ENGINEER OF RECORD. | | PLANS SUBMITTED ELECTRONICALLY MUST BE DIGITALLY SIGNED | | AND SEALED BY THE ENGINEER OF RECORD | | | | FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR | | ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND | | SIGNED. | | | | EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN | | TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF | | APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX, | | OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER | | ORIGINAL WITH A WET SIGNATURE TO THE BUILDING DIVISION. | | SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO | | BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED | | DOCUMENTS ARE PREFERRED. | | | | PLEASE EMAIL [email protected] AND CC TO | | [email protected] | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2022-01-31 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2022-01-31 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2022-01-31 |
Time |
12:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2021-11-22 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2021-11-22 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2021-11-22 |
Time |
12:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2022-02-09 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2022-02-09 |
Time |
08:13 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2022-02-09 |
Time |
08:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2021-12-27 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2021-12-27 |
Time |
10:36 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2021-12-27 |
Time |
10:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2022-02-08 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2022-02-08 |
Time |
14:11 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2022-02-08 |
Time |
14:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2021-11-24 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-11-24 |
Time |
13:26 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-11-24 |
Time |
13:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2022-02-08 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2022-02-08 |
Time |
14:11 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2022-02-08 |
Time |
14:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2021-12-27 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2021-12-27 |
Time |
10:36 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2021-12-27 |
Time |
10:36 |
Sent To |
|
|
Notes |
2021-12-27 10:36:16 | IT APPEARS DRAWINGS "FA1 AND FA2" ARE COPIES OF A | | SIGNED AND SEALED DRAWINGS OF THE ENGINEER OF RECORD. | | PLANS SUBMITTED ELECTRONICALLY MUST BE DIGITALLY SIGNED | | AND SEALED BY THE ENGINEER OF RECORD | | | | FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR | | ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND | | SIGNED. | | | | EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN | | TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF | | APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX, | | OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER | | ORIGINAL WITH A WET SIGNATURE TO THE BUILDING DIVISION. | | SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO | | BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED | | DOCUMENTS ARE PREFERRED. | | | | PLEASE EMAIL [email protected] AND CC TO | | [email protected] | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|
|
|