Plan Review Details - Permit 21110885
Plan Review Stops For Permit 21110885
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-02-10 Cont ID  
Sent By cpuell Date 2022-02-10 Time 12:49 Rev Time 0.00
Received By cpuell Date 2022-02-10 Time 12:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-01-12 Cont ID  
Sent By aaponte Date 2022-01-12 Time 10:14 Rev Time 0.00
Received By cthroop Date 2022-01-11 Time 11:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-12-20 Cont ID  
Sent By jleahy Date 2021-12-20 Time 15:00 Rev Time 0.00
Received By jleahy Date 2021-12-20 Time 14:54 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2021-12-07 Cont ID  
Sent By amhamilt Date 2021-12-07 Time 15:13 Rev Time 0.00
Received By amhamilt Date 2021-12-07 Time 15:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-02-08 Cont ID  
Sent By lmarchan Date 2022-02-08 Time 13:32 Rev Time 0.00
Received By rwbrown Date 2022-02-01 Time 15:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-12 Cont ID  
Sent By cthroop Date 2022-01-12 Time 10:14 Rev Time 0.00
Received By cthroop Date 2021-11-29 Time 16:09 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-02-02 Cont ID  
Sent By lmarchan Date 2022-02-02 Time 15:49 Rev Time 0.00
Received By lmarchan Date 2022-02-02 Time 11:24 Sent To  
Notes
2022-02-02 11:24:30RECEIPT MU-2022-004487 - $2235.84 PAID

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-12-15 Cont ID  
Sent By rbrown Date 2021-12-15 Time 10:58 Rev Time 0.00
Received By rbrown Date 2021-12-15 Time 10:58 Sent To  
Notes
2021-12-15 11:05:49DERREK MOORE, IMPACT FEE MANAGER, PALM BEACH COUNTY,
 AGREED TO SUPPORT THE ISSUANCE OF FOUNDATION PERMIT #
 21101067 PRIOR TO PAYMENT OF IMPACT FEES WITH THE
 CONDITION THAT THIS BUILDING PERMIT NOT BE ISSUED UNTIL
 THE OWNER HAS PAID THE IMPACT FEES, AND "WHEN THE
 PROJECT IS READY FOR IMPACT FEE ASSESSMENT, PLEASE HAVE
 THE PERMITTEE RESUBMIT THE EXISTING USE CREDIT
 APPLICATION FOR CONSIDERATION AT THAT TIME."
  
 ROBERT BROWN, BUILDING OFFICIAL
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-02-03 Cont ID  
Sent By medwards Date 2022-02-03 Time 13:00 Rev Time 0.00
Received By medwards Date 2022-02-03 Time 13:00 Sent To  
Notes
2022-02-03 13:13:39APPROVED WITH PRIVISO'S:
  
 THE AHU MUST MEET CLEARANCE FROM COMBUSTIBLE MATERIAL
 BASED ON FBC RES M1306.1
  
 THE CONDENSING CLOTHES DRYER MUST BE LISTED AND
 LABELED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-12-01 Cont ID  
Sent By medwards Date 2021-12-01 Time 16:33 Rev Time 0.00
Received By medwards Date 2021-12-01 Time 16:33 Sent To  
Notes
2021-12-01 16:33:251ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21110885
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE EQUIPMENT SIZING CALCULATIONS HAVE AN ADDRESS OF
 1213 N SAPODILLA AVE BUT THE APPLICATION HAS 1225 N
 SAPODILLA AVE. PLEASE SUBMIT THE ENERGY CALCULATIONS
 WITH THE CORRECT ADDRESS. FBC 107.2.1
  
 2) PLEASE PROVIDE A MECHANICAL DRAWING THAT INCLUDES
 THE DUCTWORK AND SIZES. IF THERE IS A CHANGE AND AN AS
 BUILT WILL HAVE TO BE COMPLETED AT A LATER DATE THEN IS
 WHEN AN AS BUILT MUST BE SUBMITTED AS A REVISION. YOU
 CANNOT PUT A NOTE ON THE MECHANICAL DRAWING WITH NO
 DUCTWORK SAYING AN AS BUILT WILL BE PROVIDED AT LATER
 DATE. FBC 107.2.1
  
 3) PLEASE SHOW THE CONDENSATION PIPE SIZE, MATERIAL AND
 TERMINATION LOCATION. FBC RES M1411.3
  
 4) PLEASE SHOW THE EXHAUST DUCT FOR THE BATH FANS AND
 THE TERMINATION LOCATIONS. FBC RES M1507.4
  
 5) PLEASE INDICATE IF A HOOD IS TO BE INSTALLED ABOVE
 THE RANGE. IF SO IS IT VENTED TO THE EXTERIOR? WHAT IS
 THE CFM?S OF EXHAUST? IS MAKE UP AIR REQUIRED? FBC RES
 M1503.3 AND 1503.4
  
 6) PLEASE SHOW THE RETURN AIR PATH FROM ROOMS WITH
 DOORS BACK TO THE AHU. FBC RES M1602.3
  
 7) IS THERE GOING TO BE A LAUNDRY AREA IN THIS HOME? IF
 SO PLEASE SHOW THE DRYER EXHAUST DUCT AND TERMINATION
 LOCATION. FBC RES M1502
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-02-08 Cont ID  
Sent By rwbrown Date 2022-02-08 Time 13:32 Rev Time 0.00
Received By rwbrown Date 2022-02-08 Time 13:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-11-30 Cont ID  
Sent By abelisle Date 2021-11-30 Time 17:20 Rev Time 0.00
Received By abelisle Date 2021-11-30 Time 16:59 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2022-01-12 Cont ID  
Sent By cthroop Date 2022-01-12 Time 10:14 Rev Time 0.00
Received By cthroop Date 2022-01-12 Time 10:14 Sent To  
Notes
2022-01-12 10:15:19PROVISO ON PLAN PAGE A-2: ROOFING REQUIRES A SEPERATE
 PERMIT. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-01-12 Cont ID  
Sent By cthroop Date 2022-01-12 Time 07:44 Rev Time 0.00
Received By cthroop Date 2022-01-11 Time 11:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-02-07 Cont ID  
Sent By ckimmerl Date 2022-02-07 Time 11:32 Rev Time 0.00
Received By ckimmerl Date 2022-02-07 Time 11:32 Sent To  
Notes
2022-02-07 11:27:54LANDSCAPE SHALL BE SUBMITTED UNDER A SEPARATE PERMIT.

Review Stop Z ZONING
Rev No 1 Status F Date 2021-12-21 Cont ID  
Sent By aaponte Date 2021-12-21 Time 15:13 Rev Time 0.00
Received By ckimmerl Date 2021-12-21 Time 16:04 Sent To  
Notes
2021-12-21 16:08:501. PLEASE RESUBMIT DRAWINGS TO REFLECT THE APPROVED
 RELOCATION AND FOUNDATION PERMIT #21101067.
 - BUILDING NEEDS TO BE ADJUSTED TO MEET THE REQUIRED
 SETBACKS. SITE CONDITIONS SHOULD REFLECT THE APPROVED
 PERMITS FOR THE PROPERTY.
  
 2. PLEASE SUBMIT ANY OF THE REQUIRED PERMITS FOR THE
 PROJECT SITE: LANDSCAPE PERMIT, IRRIGATION PERMITS,
 TREE ALTERATION PERMITS, FENCE PERMITS, DRIVEWAY
 PERMIT, ETC. AS IS NECESSARY.