Plan Review Details - Permit 21110846
Plan Review Stops For Permit 21110846
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2022-03-31 Cont ID  
Sent By cpuell Date 2022-03-31 Time 14:42 Rev Time 0.00
Received By cpuell Date 2022-03-31 Time 14:42 Sent To  
Notes
2022-03-31 14:44:11PARCEL MERGED INTO A NEW PARCEL 74434328060200010 WITH
 THE NEW ADDRESS OF 475 CLAREMORE DR, UPDATED PERMIT

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2022-02-28 Cont ID  
Sent By cpuell Date 2022-02-28 Time 14:56 Rev Time 0.00
Received By cpuell Date 2022-02-28 Time 14:56 Sent To  
Notes
2022-02-28 14:58:07PER THE PLANS SUBMITTED, THE AREA OF WORK TO BE DONE
 ENCOMPASSES THE FOLLOWING PARCELS; 74434328060200012,
 74434328060200011, 74434328060200040 AND
 74434328060200050. EITHER A REPLAT OR A UNIT OF TITLE
 NEEDS TO BE APPLIED FOR. YOU WILL NEED TO CONTACT VINCE
 NOEL [email protected] OR CALL 561-494-1040 TO START THE
 UNITY OF TITLE PROCEDURE, A SINGLE PCN MUST BE ISSUED
 BY THE COUNTY. WHEN YOU CONTACT THE PROPERTY APPRAISERS
 YOU NEED TO REQUEST PRELIMINARY LETTER OF THE UNIFIED
 PCN. ONCE YOU HAVE RECEIVED THE PRELIMINARY LETTER
 PLEASE CONTACT [email protected] OR CALL 561-805-6659 TO
 BE ISSUED AN ADDRESS.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-12-23 Cont ID  
Sent By cpuell Date 2021-12-23 Time 11:35 Rev Time 0.00
Received By cpuell Date 2021-12-23 Time 11:35 Sent To  
Notes
2021-12-23 11:35:14PER THE PLANS SUBMITTED, THE AREA OF WORK TO BE DONE
 ENCOMPASSES THE FOLLOWING PARCELS; 74434328060200012,
 74434328060200011, 74434328060200040 AND
 74434328060200050. EITHER A REPLAT OR A UNIT OF TITLE
 NEEDS TO BE APPLIED FOR. YOU WILL NEED TO CONTACT VINCE
 NOEL [email protected] OR CALL 561-494-1040 TO START THE
 UNITY OF TITLE PROCEDURE, A SINGLE PCN MUST BE ISSUED
 BY THE COUNTY. WHEN YOU CONTACT THE PROPERTY APPRAISERS
 YOU NEED TO REQUEST PRELIMINARY LETTER OF THE UNIFIED
 PCN. ONCE YOU HAVE RECEIVED THE PRELIMINARY LETTER
 PLEASE CONTACT [email protected] OR CALL 561-805-6659 TO
 BE ISSUED AN ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-04-18 Cont ID  
Sent By rmcphers Date 2022-04-18 Time 11:09 Rev Time 0.00
Received By rmcphers Date 2022-04-18 Time 11:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-04-04 Cont ID  
Sent By rmcphers Date 2022-04-04 Time 10:01 Rev Time 0.00
Received By rmcphers Date 2022-04-04 Time 10:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-03-02 Cont ID  
Sent By rmcphers Date 2022-03-02 Time 11:06 Rev Time 0.00
Received By rmcphers Date 2022-03-02 Time 11:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-12-14 Cont ID  
Sent By rmcphers Date 2021-12-14 Time 14:18 Rev Time 0.00
Received By rmcphers Date 2021-12-14 Time 14:18 Sent To  
Notes
2021-12-14 14:25:08LIGHT POLES
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) LIGHT POLE DRAWINGS - SHOULD SHOW POLE HEIGHT,
 BURIAL DEPTH, POLE MODEL/DESIGNATION NUMBER, ETC.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2022-04-20 Cont ID  
Sent By mpeterso Date 2022-04-20 Time 15:36 Rev Time 0.00
Received By mpeterso Date 2022-04-20 Time 15:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2022-04-01 Cont ID  
Sent By mpeterso Date 2022-04-01 Time 14:27 Rev Time 0.00
Received By mpeterso Date   Time   Sent To  
Notes
2022-04-01 15:55:52ELECTRIC REVIEW FAILED
 1) METER IS INCORRECTLY DESCRIBE AS A 120/208 VOLT
 METER CAN. PLEASE DETAIL IT CORRECTLY. FBC 107.2
 2) RISER DIAGRAM DETAILS (2) SETS OF 500MCM RHU AS
 FEEDERS TO THE EXISTING 1000-AMP MDP. THESE CONDUCTORS
 ARE INADEQUATELY SIZED AS PER NEC 240.4(C). OVERCURRENT
 DEVICE OVER 800-AMPERES, THE AMPACITY OF CONDUCTORS IT
 PROTECTS SHALL BE EQUAL TO OR GREATER THE RATING OF THE
 OVERCURRENT DEVICE. PLEASE CORRECT WITH APPROPRIATELY
 SIZED CONDUCTORS.
 2) THE RISER DIAGRAM DOES NOT DETAIL GROUND FAULT
 PROTECTION AS REQUIRED PER NEC 215.10 FOR DISCONNECTS
 OF 480 VOLT,1000AMP SYSTEMS. PLEASE DETAIL THAT THIS
 GROUND FAULT PROTECTION EXISTS OR WILL BE INSTALLED.
 3) PLEASE PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION
 AND ENSURE EQUIPMENT RATING IS SUFFICIENT AS PER NEC
 110.9. PLEASE INCLUDE A NOTE TO ENSURE LABLEING TO IS
 TO BE APPLIED ON EQUIPMENT AS PER NEC 110.24
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-03-08 Cont ID  
Sent By mpeterso Date 2022-03-08 Time 13:29 Rev Time 0.00
Received By mpeterso Date 2022-03-08 Time 13:29 Sent To  
Notes
2022-03-08 13:57:03ELECTRIC REVIEW FAILED
 1) PLEASE PROVIDE DETAIL AS TO EXISTING 1000-AMP MDP TO
 ENSURE COMPLIANCE WITH NEC 110,26 AND OTHER APPLICABLE
 CODES
 2) NO RECORD EXISTS FOR EXISTING 1000-AMP SERVICE AT
 THIS ADDRESS. PLEASE PROVIDE MORE INFORMATION REGADING
 THIS SERVICE. FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-12-13 Cont ID  
Sent By mpeterso Date 2021-12-13 Time 10:21 Rev Time 0.00
Received By mpeterso Date 2021-12-13 Time 10:21 Sent To  
Notes
2021-12-13 10:22:52 PLEASE CORRECT
 1) SERVICE POINT DETAILS INDICATE #2 RHW CU FEEDER
 CONDUCTORS FROM SERVICE POINT ?A? TO SERVICE POINT ?B?
 WITH 125-AMP OVERCURRENT PROTECTION. NEC TABLE 310.15
 (B)(16) STATES AMPACITY OF THIS CONDUCTOR AT 115-AMPS
 2) PLAN ALSO STATES THERE ARE NO EXISTING LOADS AT
 EXISTING SERVICE POINT ?A?. IS THERE MORE THAN ONE
 SERVICE AT THE EXISTING STORAGE BUILDING? PLEASE DETAIL
 LOCATIONS OF EXISTING SERVICES AT THE EXISTING
 BUILDINGS AND WHAT ELECTRICAL LOADS THESE SERVICES
 SUPPLY. F.B.C.107.3.5.1.2
 3) NEC210.20 (A) OVERCURRENT PROTECTION OF 20-AMPS IS
 NOT ADEQUATE TO SUPPLY TENNIS COURT LIGHT CIRCUITS WITH
 A CONTINUOUS LOAD OF 17.3-AMPS
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-04-21 Cont ID  
Sent By lmarchan Date 2022-04-21 Time 15:06 Rev Time 0.00
Received By lmarchan Date 2022-04-14 Time 09:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-04-11 Cont ID  
Sent By lmarchan Date 2022-04-11 Time 15:11 Rev Time 0.00
Received By lmarchan Date 2022-03-31 Time 09:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2022-03-09 Time   Rev Time 0.00
Received By aoliver Date 2022-02-28 Time 07:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-12-27 Cont ID  
Sent By aoliver Date 2021-12-27 Time 17:23 Rev Time 0.00
Received By aoliver Date 2021-11-20 Time 09:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2022-04-20 Cont ID  
Sent By dbattles Date 2022-04-20 Time 16:15 Rev Time 0.00
Received By dbattles Date 2022-04-20 Time 16:15 Sent To  
Notes
2022-04-20 16:17:06MULTI PAGE UPLOADED INTO SIGNATURE FOLDER.
 IF ANOTHER ROUND OF REVIEWS OCCURS ANY NEW SHEETS WILL
 NEED TO BE REVIEWED FOR SIGNATURE.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2022-04-18 Cont ID  
Sent By rmcphers Date 2022-04-18 Time 11:03 Rev Time 0.00
Received By rmcphers Date 2022-04-18 Time 11:03 Sent To  
Notes
2022-04-18 11:04:24SIGNATURE REVIEW
  
 CORRECTIONS NEEDED
  
 1) DRAWINGS - SHEETS 01,02,03,04,05,06,07 DO NOT SHOW
 AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-04-04 Cont ID  
Sent By rmcphers Date 2022-04-04 Time 10:09 Rev Time 0.00
Received By rmcphers Date 2022-04-04 Time 10:09 Sent To  
Notes
2022-04-04 10:10:57SIGNATURE REVIEW
  
 CORRECTIONS NEEDED
  
 1) DRAWINGS LABELED "LOCATION OF POLES 3&4" AND
 "LOCATION OF POLES 4&5" DO NOT SHOW AS DIGITALLY SIGNED
 IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-03-02 Cont ID  
Sent By rmcphers Date 2022-03-02 Time 11:12 Rev Time 0.00
Received By rmcphers Date 2022-03-02 Time 11:12 Sent To  
Notes
2022-03-02 11:14:15SIGNATURE REVIEW
  
 CORRECTIONS NEEDED
  
 1) ALL OF THE DRAWINGS DO NOT SHOW AS DIGITALLY SIGNED
 IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-12-14 Cont ID  
Sent By rmcphers Date 2021-12-14 Time 14:27 Rev Time 0.00
Received By rmcphers Date 2021-12-14 Time 14:25 Sent To  
Notes
2021-12-14 14:33:11SIGNATURE REVIEW
  
 DRAWINGS NEED TO BE SIGNED AND SEALED BY THE DESIGNER
 FBC 107.2.1
  
 ALL OF THE DRAWINGS DO NOT SHOW AS DIGITALLY SIGNED IN
 ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop Z ZONING
Rev No 4 Status P Date 2022-04-21 Cont ID  
Sent By llouie Date 2022-04-21 Time   Rev Time 0.00
Received By llouie Date 2022-04-21 Time   Sent To  
Notes
2022-04-21 15:04:15SCOPE OF PERMIT IS FOR LIGHTING/LIGHT POLE FIXTURES
 ONLY. ALL OTHER STRUCTURAL ELEMENTS/SITE IMPROVEMENTS
 (I.E. LANDSCAPING, PARKING LOT, FENCE/WALL, ETC.)
 REQUIRE SEPARATE PERMITS.

Review Stop Z ZONING
Rev No 3 Status F Date 2022-04-11 Cont ID  
Sent By llouie Date 2022-04-11 Time   Rev Time 0.00
Received By llouie Date 2022-04-11 Time   Sent To  
Notes
2022-04-11 13:52:25** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SITE PLAN (6 COURTS) IS NOT CONSISTENT WITH THE
 PLANS THAT ARE BEING APPROVED FOR THE TENNIS COURT
 PROJECT (SCOPE OF WORK HAS BEEN CHANGED FROM 6 COURTS
 TO 4 COURTS). ALL PLANS ASSOCIATED WITH THE PROJECT
 MUST MATCH FOR CONSISTENCY.
  
 2.) MAKE SURE THAT WHEN SUBMITTING THE CORRECT/MATCHING
 SITE PLAN THAT SETBACK DISTANCES FROM THE POLE FIXTURES
 TO THE PROPERTY LINE(S) ARE PROVIDED. A MINIMUM POLE
 SETBACK OF 5 FT. FROM THE PROPERTY LINE IS REQUIRED.
  
 3.) A PHOTOMETRIC PLAN MATCHING THE APPROVED PLANS FOR
 THE TENNIS COURTS (4 COURTS) MUST BE PROVIDED WITH THE
 SUBMITTAL.
  
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: GC (TENNIS COURTS).
  
 * LANDSCAPE PERMIT #22020765 (ISSUED - 4 COURTS SHOWN).
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2022-03-09 Cont ID  
Sent By llouie Date 2022-03-09 Time   Rev Time 0.00
Received By llouie Date 2022-03-09 Time   Sent To  
Notes
2022-03-09 14:53:12** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SIGNED AND SEALED UPDATED SURVEY OF THE PROPERTY IS
 REQUIRED. A SURVEY WAS NOT PROVIDED WITH THE PERMIT
 APPLICATION.
  
 [12/27/2021 REPEAT COMMENT: NOT ADDRESSED. NO SURVEY
 PROVIDED WITH THE RESUBMITTAL AND THE SURVEY MUST
 REFLECT THE PARCEL(S) OF THE SCOPE OF WORK ONLY.]
  
  
 2.) PLANS SHALL BE CONSISTENT WITH THE APPLICATION FOR
 THE PROPOSED CREATION OF THE GREENE SCHOOL COMMERCIAL
 PLANNED DEVELOPMENT (CPD) TO WHICH THE PARCELS IS
 PROPOSED TO BE A PART OF.
  
 [12/27/2021 REPEAT COMMENT: TO DATE, STAFF IS STILL
 WAITING ON THE RESUBMITTAL FOR THE PROPOSED GREENE
 SCHOOL CPD APPLICATION. STAFF MUST BE ABLE TO REVIEW
 FOR CONSISTENCY WITH THE PERMIT APPLICATION AND THE
 PROPOSED PLANNED DEVELOPMENT APPLICATION.]
  
  
 3.) THE PHOTOMETRIC PLAN MUST SHOW PHOTOMETRIC SPILL
 OVER BEYOND THE PROPERTY LINES. PER THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS), ANY SOURCE OF
 ILLUMINATION SHALL NOT EXCEED ONE FOOT CANDLE AT OR
 BEYOND THE PROPERTY LINES. [ZLDR S.94-207(D)]
  
 [12/27/2021 REPEAT COMMENT: THANK YOU FOR PROVIDING THE
 PHOTOMETRIC PLAN; HOWEVER, THE PHOTOMETRIC PLAN IS NOT
 CONSISTENT WITH THE STANDARDS OF THE ZLDRS.]
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: GC/PROPOSED GREENE SCHOOL CPD
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-12-27 Cont ID  
Sent By llouie Date 2021-12-27 Time   Rev Time 0.00
Received By llouie Date 2021-12-27 Time   Sent To  
Notes
2021-12-27 13:14:37** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SIGNED AND SEALED UPDATED SURVEY OF THE PROPERTY IS
 REQUIRED. A SURVEY WAS NOT PROVIDED WITH THE PERMIT
 APPLICATION.
  
 2.) A UNIT OF TITLE IS REQUIRED TO JOIN THE ADJACENT
 PARCEL, WHICH SEEMS TO BE A PART OF THE PROJECT AREA.
  
 3.) PLANS SHALL BE CONSISTENT WITH THE APPLICATION FOR
 THE PROPOSED CREATION OF THE GREENE SCHOOL COMMERCIAL
 PLANNED DEVELOPMENT (CPD) TO WHICH THE PARCELS IS
 PROPOSED TO BE A PART OF.
  
 4.) A 5 FT WIDE LANDSCAPE BUFFER IS REQUIRED ALONG THE
 BISCAYNE DRIVE PROPERTY LINE. [ZLDR S.94-443]
  
 5.) SHOW SETBACK DISTANCE OF THE LIGHT POLE FIXTURES TO
 THE PROPERTY LINE(S). A MINIMUM 5 FT. IS REQUIRED FROM
 THE PROPERTY LINES.
  
 6.) HOW TALL ARE THE POLE FIXTURES? FIXTURE DETAILS
 REQUIRED.
  
 7.) THE FOLLOWING NOTE SHALL BE PROVIDED IN THE PLANS
 FOR CONSISTENCY WITH THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDRS): ALL OUTDOOR LIGHTING SHALL BE
 SHIELDED TO REDUCE GLARE AND SHALL BE ARRANGED TO
 REFLECT LIGHT OR GLARE AWAY FROM ALL ADJACENT
 RESIDENTIAL DISTRICTS, ADJACENT RESIDENCES, OR PUBLIC
 THROUGHFARES. [ZLDR S.94-309.A.]
  
 8.) A PHOTOMETRIC PLAN IS REQUIRED.
  
  
 NOTES:
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: GC/PROPOSED GREENE SCHOOL CPD
  