Plan Review Details - Permit 21110731
Plan Review Stops For Permit 21110731
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-12-17 Cont ID  
Sent By pvalenti Date 2021-12-17 Time 06:40 Rev Time 0.00
Received By pvalenti Date 2021-12-17 Time 06:20 Sent To  
Notes
2021-12-17 06:48:02PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
  
 ITEMS A & B NOTED ABOVE: THE SUBMITTED SOUND TEST
 REPORTS FOR THE REQUIRED ASTM E90 & ASTM E492 ARE FOR
 DROPPED CEILING AND WOOD FRAMED TRUSS FLOORS. THOSE
 REPORTS ARE NOT APPLICABLE. WHAT IS REQUIRED IS THE
 TEST REPORTS FOR A CONCRETE DECK (YOU WILL HAVE TO
 VERIFY 6" OR 8" THICKNESS) WITH NO DROPPED CEILING.
  
 ITEM C NOTED ABOVE: THE OTHER TEST REPORT REQUIRED THAT
 HAS NOT BEEN SUBMITTED IS ASTM E 84. THAT'S FOR THE
 FLAME SPREAD.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-11-22 Cont ID  
Sent By cwalker Date 2021-11-22 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2021-11-22 11:07:47PROVIDE THE CRITICAL RADIANT FLUX FOR FIRE PERFORMANCE
 OF FLOORING MATERIALS AND UNDERLAYMENT TO BE INSTALLED.
 NFPA 101 10.2.7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-12-17 Cont ID  
Sent By pvalenti Date 2021-12-17 Time 06:57 Rev Time 0.00
Received By pvalenti Date 2021-11-17 Time 09:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-12-17 Cont ID  
Sent By pvalenti Date 2021-12-17 Time 06:40 Rev Time 0.00
Received By pvalenti Date 2021-12-17 Time 06:40 Sent To  
Notes
***NONE***