Plan Review Details - Permit 21110704
Plan Review Stops For Permit 21110704
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-12-09 Cont ID  
Sent By medwards Date 2021-12-09 Time 06:56 Rev Time 0.00
Received By medwards Date 2021-12-08 Time 16:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-18 Cont ID  
Sent By medwards Date 2021-11-18 Time 13:24 Rev Time 0.00
Received By medwards Date 2021-11-17 Time 09:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-12-09 Cont ID  
Sent By medwards Date 2021-12-09 Time 06:54 Rev Time 0.00
Received By medwards Date 2021-12-09 Time 06:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-11-18 Cont ID  
Sent By medwards Date 2021-11-18 Time 13:19 Rev Time 0.00
Received By medwards Date 2021-11-18 Time 13:19 Sent To  
Notes
2021-11-18 13:24:05THE LOAD CALCULATIONS IS CALLING FOR 600 CFM'S OF
 SUPPLY FOR THE MECHANICAL SYSTEM BUT THE REGISTERS ON
 THE MECHANICAL DRAWING ADD UP TO 690 CFM'S. PLEASE BE
 CONSISTENT ON BOTH SUBMITTALS. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-11-18 Cont ID  
Sent By medwards Date 2021-11-18 Time 13:24 Rev Time 0.00
Received By medwards Date 2021-11-18 Time 13:24 Sent To  
Notes
***NONE***