Plan Review Details - Permit 21110479
Plan Review Stops For Permit 21110479 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2022-03-07 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-03-07 |
Time |
10:48 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-03-07 |
Time |
10:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2022-01-26 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-01-26 |
Time |
12:39 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-01-26 |
Time |
12:33 |
Sent To |
|
|
Notes |
2022-01-26 12:41:13 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | PLEASE SUBMIT A CAST BREAKDOWN OF THE LABOR AND | | MATERIAL FOR THIS PROJECT. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-01-26 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-01-26 |
Time |
12:41 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-01-14 |
Time |
06:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2022-03-07 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-03-07 |
Time |
10:49 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-03-07 |
Time |
10:49 |
Sent To |
|
|
Notes |
2022-03-07 10:49:56 | SEE PAGE E310 OF MASTER SET OF PLANS 20120907 JLEAHY |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2022-01-26 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-01-26 |
Time |
12:36 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-01-26 |
Time |
12:33 |
Sent To |
|
|
Notes |
2022-01-26 12:39:12 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | PLANS NOT SIGNED BY PERSON RESPONSIBLE FOR THE PLANS. | | | | PLANS SUBMITTED ELECTRONICALLY MUST BE DIGITALLY SIGNED | | AND SEALED BY THE ENGINEER OF RECORD | | | | FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR | | ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND | | SIGNED. | | EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN | | TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF | | APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX, | | OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER | | ORIGINAL WITH A WET SIGNATURE TO THE BUILDING DIVISION. | | SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO | | BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED | | DOCUMENTS ARE PREFERRED. | | |
|
|
|