2021-11-29 08:36:56 | 11/29/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. A DRAWING WAS SUBMITTED FOR PLUMBING WORK BUT THE |
| CITY OF WEST PALM BEACH HAS NO RECORD OF A DEMO OR |
| BUILDING WORK FOR THAT STRUCTURE. WOULD YOU PLEASE |
| PROVIDE A LAYOUT OF WHAT IS BEING DEMO OR ADDED, THE |
| SOURCE OF HOT WATER? SEPARATE PERMIT REQUIRED PER THE |
| WPB AMENDMENTS TO THE FBC SEC. 105.1. PLEASE REFER TO |
| BUILDING COMMENTS. |
| |
| 2. WHERE ARE THE TWO UNITS ON THE SECOND FLOOR |
| CONNECTING TO THE BUILDING DRAIN AND WHAT SIZE IS THE |
| FIXTURE LOAD PER THE 2020 FBC TABLE 710.1(1) BUILDING |
| DRAINS AND SEWER. |
| |
| 3. WOULD YOU PLEASE SHOW THE LOCATION OF WATER HEATERS |
| PER THE WPB AMEND TO FBC 107.2.1. |
| |
| 4. IF WATER PIPING IS BEING REPLACED, PLEASE PROVIDE A |
| WATER ISOMETRIC PER THE WPB AMEND TO FBC |
| 107.3.5.1.3(13) |
| |
| 5. A BACKFLOW DEVICE WILL BE REQUIRED ON THE WATER |
| SERVICE AT THE METER A SEPARATE PERMIT WILL BE |
| REQUIRED. PER WPB UTILITIES DEPARTMENT CROSS CONNECTION |
| MANUAL. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |