Plan Review Details - Permit 21110465
Plan Review Stops For Permit 21110465
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2022-03-17 Cont ID  
Sent By lmarchan Date 2022-03-17 Time 15:43 Rev Time 0.00
Received By lmarchan Date 2022-03-17 Time 15:43 Sent To  
Notes
2022-03-17 15:43:08SEE 21120216

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-11-29 Cont ID  
Sent By rmcdouga Date 2021-11-29 Time 08:04 Rev Time 0.00
Received By rmcdouga Date 2021-11-29 Time 08:04 Sent To  
Notes
2021-11-29 08:33:03PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) IT APPEARS THAT YOU INTEND TO REPLACE ALL OF THE
 PLUMBING IN A TWO STORY (4) UNIT APARTMENT BUILDING
 THAT WAS CONSTRUCTED IN 1930. THIS WORK WILL REQUIRE
 THE WALLS, FLOORS AND CEILINGS TO BE OPENED FOR ACCESS
 TO REPLACE THE EXISTING PLUMBING. THE TENANT SEPARATION
 WALLS BETWEEN THE UNITS ARE REQUIRED TO HAVE A ONE HOUR
 FIRE RESISTIVE RATING. A BUILDING CONTRACTOR IS
 REQUIRED TO OBTAIN A PERMIT TO COMPLETE THIS WORK. FBC
 AMENDMENTS 105.1
  
 2) PROVIDE A FULL SCOPE OF WORK. SPECIFY IF NEW
 FIXTURES, VANITIES AND KITCHEN CABINETS WILL BE
 INSTALLED. FBC AMENDMENTS 107.2.1
  
 3) PROVIDE AN EXISTING FLOOR PLAN AND A PROPOSED FLOOR
 PLAN. FBC AMENDMENTS 107.2
  
 4) SPECIFY THE LEVEL OF ALTERATION ON THE PLANS PER THE
 FBC EXISTING BUILDING CHAPTER 6.
  
 5) PROVIDE DETAILS FOR THE ONE HOUR FIRE RESISTANCE
 RATED TENANT SEPARATION WALLS AND FOR THE PROTECTION OF
 OPENINGS OR PENETRATIONS IN THESE WALLS. FBC 714
  
 6) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. PLEASE NOTE
 THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS
 MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-02-14 Cont ID  
Sent By aoliver Date 2022-02-14 Time 12:48 Rev Time 0.00
Received By aoliver Date 2022-02-09 Time 08:28 Sent To  
Notes
2022-02-14 12:55:07PERMIT CHANGED TO SUB OF 21120216 PER SH. REVIEWS WILL
 BE COMPLETED UNDER MASTER AO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-29 Cont ID  
Sent By rmcdouga Date 2021-11-29 Time 08:42 Rev Time 0.00
Received By rmcdouga Date 2021-11-23 Time 09:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-02-10 Cont ID  
Sent By lcrespo Date 2022-02-10 Time 13:13 Rev Time 0.00
Received By lcrespo Date 2022-02-10 Time 12:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-11-29 Cont ID  
Sent By lcrespo Date 2021-11-29 Time 07:51 Rev Time  
Received By lcrespo Date 2021-11-24 Time 12:45 Sent To  
Notes
2021-11-29 08:36:5611/29/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A DRAWING WAS SUBMITTED FOR PLUMBING WORK BUT THE
 CITY OF WEST PALM BEACH HAS NO RECORD OF A DEMO OR
 BUILDING WORK FOR THAT STRUCTURE. WOULD YOU PLEASE
 PROVIDE A LAYOUT OF WHAT IS BEING DEMO OR ADDED, THE
 SOURCE OF HOT WATER? SEPARATE PERMIT REQUIRED PER THE
 WPB AMENDMENTS TO THE FBC SEC. 105.1. PLEASE REFER TO
 BUILDING COMMENTS.
  
 2. WHERE ARE THE TWO UNITS ON THE SECOND FLOOR
 CONNECTING TO THE BUILDING DRAIN AND WHAT SIZE IS THE
 FIXTURE LOAD PER THE 2020 FBC TABLE 710.1(1) BUILDING
 DRAINS AND SEWER.
  
 3. WOULD YOU PLEASE SHOW THE LOCATION OF WATER HEATERS
 PER THE WPB AMEND TO FBC 107.2.1.
  
 4. IF WATER PIPING IS BEING REPLACED, PLEASE PROVIDE A
 WATER ISOMETRIC PER THE WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 5. A BACKFLOW DEVICE WILL BE REQUIRED ON THE WATER
 SERVICE AT THE METER A SEPARATE PERMIT WILL BE
 REQUIRED. PER WPB UTILITIES DEPARTMENT CROSS CONNECTION
 MANUAL.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-11-29 Cont ID  
Sent By lcrespo Date 2021-11-29 Time 08:37 Rev Time 0.00
Received By lcrespo Date 2021-11-29 Time 08:37 Sent To  
Notes
***NONE***