Plan Review Stops For Permit 21110446 |
Review Stop |
AD |
ADDRESSING |
Rev No |
2 |
Status |
P |
Date |
2022-08-01 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2022-08-01 |
Time |
15:19 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2022-08-01 |
Time |
15:19 |
Sent To |
|
|
Notes |
2022-08-01 15:20:54 | SCOPE OF WORK CHANGED, WORK NO LONGER HAPPENING IN | | GARAGE. |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
F |
Date |
2022-01-06 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2022-01-06 |
Time |
12:20 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2022-01-06 |
Time |
12:19 |
Sent To |
|
|
Notes |
2022-01-06 12:22:44 | GARAGE BUILDING BEING CONVERTED INTO HABITABLE SPACE. | | PLEASE COORDINATE WITH [email protected] FOR THE HABITABLE | | SPACE TO BE GIVEN AN ADDRESS. ALL ACCESSORY | | RESIDENTIAL/COMMERCIAL UNITS AND OR OTHER HABITABLE | | STRUCTURES WILL BE ISSUED A UNIQUE SECONDARY ADDRESS | | NUMBER PER CITY'S ADDRESSING POLICY. PLEASE HAVE THE | | OWNER CONTACT [email protected] OR CALL 561-805-6659 | | TOHAVE AN ADDRESS ASSIGNED TO THE BUILDING. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2022-08-12 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2022-08-12 |
Time |
13:52 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2022-08-12 |
Time |
13:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2022-07-29 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2022-07-29 |
Time |
07:59 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2022-07-29 |
Time |
07:59 |
Sent To |
|
|
Notes |
2022-07-29 08:04:28 | PETER E VALENTI | | BUILDING PLANS EXAMINER II | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | BUILDING REVIEW DENIED: | | | | FBC EC (R) 103.1.1.2, OWNER/OWNER AGENT MUST SIGN THE | | COMPLETED ENERGY CALCULATIONS FORM R-405. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2022-07-18 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2022-07-18 |
Time |
14:03 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2022-07-18 |
Time |
07:20 |
Sent To |
|
|
Notes |
2022-07-18 13:51:02 | PETER E VALENTI | | BUILDING PLANS EXAMINER II | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | BUILDING REVIEW DENIED: | | | | 2.) 2. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 | | IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | INCLUDED BOUNDARY LINE SURVEY. | | FBC R401.3 SITE DRAINAGE | | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER | | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT | | DOES NOT CREATE A HAZARD. | | LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM | | FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 | | INCHES WITHIN THE FIRST 10 FEET. | | | | 3. PLAN SHEET A-7 INDICATES R-30 BATT INSULATION AT | | ROOF. | | FBC B 107.2.1,PROVIDE, ON PLAN SHEETS THE WALL | | INSULATION TYPE FOR CMU/MASONRY AND WOOD FRAMING TO | | MATCH THE SUBMITTED ENERGY CALC. FORM R-405. | | FBC EC R 103.1.1.2, OWNER/OWNER AGENT MUST SIGN THE | | COMPLETED FORM R-405. | | | | | | 5.PROVIDE DESIGN PRESSURES FOR NEW ROOFING PER FIGURE | | R301.2(7) COMPONENT AND CLADDING PRESSURE ZONES | | R301.2.1.1WIND DESIGN REQUIRED. | | | | 6.PROVIDE ROOF SHEATHING FASTENER SCHEDULE PER DESIGN | | PRESSURES. | | TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING | | SCHEDULE FOR WOOD STRUCTURAL PANELS. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE?SUBMITTAL FORM. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2022-01-05 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2022-01-05 |
Time |
16:47 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2022-01-05 |
Time |
14:21 |
Sent To |
|
|
Notes |
2022-01-05 17:04:13 | BUILDING PLAN REVIEW | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | PLANS EXAMINER II PX3169/SFP306 | | INSPECTOR BN4338 | | BUILDING OFFICIAL BU1635 | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | DEVELOPMENT SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | (561) 805-6726 | | [email protected] | | | | CODES IN EFFECT: | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | NFPA 70 2017 EDITION NEC 2017 | | | | 1ST REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. PROVIDE DEMENSIONS TO PROPERTY LINES ON SITE PLAN. | | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED | | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY | | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF | | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE | | SITE,... AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN | | ACCURATE AND INCLUDED BOUNDARY LINE SURVEY. | | | | 2. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 | | IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | INCLUDED BOUNDARY LINE SURVEY. | | FBC R401.3 SITE DRAINAGE | | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER | | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT | | DOES NOT CREATE A HAZARD. | | LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM | | FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 | | INCHES WITHIN THE FIRST 10 FEET. | | | | 3. PROVIDE AN ENERGY SUBMITTAL. | | CEILING INSULATION ON PLAN PAGE A-1 IS LISTED AS R-19. | | WHAT TYPE OF INSULATION WILL BE INSTALLED? | | STATE THE EXT. WALL INSULATION TYPE AND R-VALUE ON | | PLAN. | | FBC 107.3.5.1.6 ENERGY CALCULATIONS ? PROVIDE AN ENERGY | | SUBMITTAL COMPLIANT WITH FBC-E 103; | | FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3 | | STORIES. | | FBC EC-R101.5.1.1.2 BUILDING THERMAL ENVELOPE | | ALTERNATIVE. | | R405.2 EC. | | | | 4. REFERENCE PAGE C-1 FOR THE FOLLOWING: | | BUILDING DATA: NEW A/C AREA IS STATED AS 224 SF. | | (PATIO/PORCH) | | WILL THE GARAGE CONVERSION BE CONDITIONED SPACE? | | PLEASE CLARIFY? | | | | 5.PROVIDE DESIGN PRESSURES FOR NEW ROOFING PER FIGURE | | R301.2(7) COMPONENT AND CLADDING PRESSURE ZONES | | R301.2.1.1WIND DESIGN REQUIRED. | | | | 6.PROVIDE ROOF SHEATHING FASTENER SCHEDULE PER DESIGN | | PRESSURES. | | TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING | | SCHEDULE FOR WOOD STRUCTURAL PANELS. | | | | 7. REFERENCE PLAN PAGE A-8 FOR THE FOLLOWING: | | ELEVATION VIEWS APPEAR TO BE A MIRROR IMAGE OF THE | | FLOOR PLAN. PLEASE CLARIFY? | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | 107.2.5. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | | | | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2022-06-30 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2022-06-30 |
Time |
10:32 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2022-06-30 |
Time |
10:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2022-01-03 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2022-01-03 |
Time |
10:13 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2022-01-03 |
Time |
10:56 |
Sent To |
|
|
Notes |
2022-01-03 10:19:19 | 1)CLOTHES CLOSET LIGHTS ARE TO COMPLY WITH NEC 410.16 | | 2)PLANS INCOMPLETE DISHWASHER, ICE BEVERAGE | | REFRIGERATOR RECEPTACLES NOT SHOWN. FBC 107.2 | | 3) LOAD CALCULATION DOES NOT LIST ALL LOADS AND IS | | UNREADABLE. FBC 107.2 | | 4) PLEASE DETAIL BETWEEN EXISTING AND NEW WORK, | | INCLUDING THE ELECTRIC SERVICE ,AS IT APPEARS MUCH OF | | THE STRUCTURE IS TO BE DEMOLISHED, INCLUDING ROOF AND | | TRUSSES. FBC 107.2 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2022-08-16 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2022-08-16 |
Time |
08:56 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2022-08-12 |
Time |
09:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2022-08-01 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2022-08-01 |
Time |
15:21 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2022-07-22 |
Time |
14:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2022-07-18 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2022-07-18 |
Time |
14:04 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2022-06-23 |
Time |
08:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-01-05 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2022-01-05 |
Time |
17:04 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-11-10 |
Time |
13:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2022-09-07 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2022-09-07 |
Time |
13:32 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2022-08-12 |
Time |
09:21 |
Sent To |
|
|
Notes |
2022-09-02 16:30:42 | MU-2022-038523-0000 - $22.46 PAID AO | 2022-08-12 09:21:43 | 8/12/22 EMAILED IMPACT OFFICE FOR REVIEW. LEM |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2022-01-05 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2022-01-05 |
Time |
16:01 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2022-01-05 |
Time |
16:00 |
Sent To |
|
|
Notes |
2022-01-05 16:01:40 | IMPACT FEE QUESTIONNAIRE | | | | PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. OUR PERMIT | | LIBRARIANS WILL SEND THE IMPACT FEE QUESTIONNAIRE TO | | THE PALM BEACH COUNTY IMPACT FEE OFFICE ON YOUR BEHALF. | | THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZ | | B/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | UPON APPROVAL AND PAYMENT OF FEES, PLEASE UPLOAD THE | | RECEIPT TO PROJECT DOX OR EMAIL IT TO | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2022-07-25 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2022-07-25 |
Time |
06:06 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2022-07-25 |
Time |
06:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2022-06-24 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2022-06-24 |
Time |
07:57 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2022-06-24 |
Time |
07:57 |
Sent To |
|
|
Notes |
2022-06-24 07:58:26 | 1) SHOW HOW THE SUPPLY BOX INSIDE THE MUD ROOM WILL TIE | | BACK TO AHU-1. ALSO SHOW THE DUCT SIZE REQUIRED. FBC | | 107.2.1 | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2021-11-19 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-11-19 |
Time |
07:11 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-11-19 |
Time |
07:11 |
Sent To |
|
|
Notes |
2021-11-19 07:11:25 | 1ST REVIEW FBC-2020 MECHANICAL | | PERMIT-21110446 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE PROVIDE EQUIPMENT SIZING CALCULATIONS FOR THE | | NEWLY CONDITIONED GUEST HOUSE. FBC EC R402.1 | | | | 2) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THE NEWLY | | CONDITIONED GUEST HOUSE. FBC EC R403.7 | | | | 3) PLEASE PROVIDE ANCHORAGE DETAILS FOR THE CONDENSING | | UNIT FOR THE GUEST HOUSE. FBC RES M1307.2 | | | | 4) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THE NEW | | ADDITION. FBC EC R402.1 | | | | 5) PLEASE PROVIDE THE MECHANICAL SIZING CALCULATIONS | | FOR THE NEW ADDITION. FBC EC R403.7 | | | | 6) PLEASE PROVIDE A MECHANICAL DRAWING SHOWING THE | | MECHANICAL SYSTEM AND DUCTWORK FOR THE NEW ADDITION. | | FBC 107.2.1 | | | | 7) PLEASE PROVIDE INFORMATION ON THE KITCHEN HOOD, CFM | | OF EXHAUST, MAKE UP AIR REQUIRED? FBC RES M1503.1 | | | | 8) PLEASE SHOW THE DRYER DUCT AND TERMINATION LOCATION. | | FBC RES M1502 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2022-07-25 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2022-07-25 |
Time |
05:54 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2022-07-25 |
Time |
05:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2022-06-24 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2022-06-24 |
Time |
09:24 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2022-06-24 |
Time |
09:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2021-11-29 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-11-29 |
Time |
11:55 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-11-29 |
Time |
11:30 |
Sent To |
|
|
Notes |
2021-11-29 11:56:17 | 11/29/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. PLEASE PROVIDE A PLUMBING ISOMETRIC RISER DIAGRAM | | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) | | RESIDENTIAL PLUMBING. | | | | 2. THE MASTER BATHROOM IS NOT VENTING THE TUBS | | CORRECTLY AND THE BATHROOM GROUP NEED TO BE SEPARATE | | FROM THE BUILDING DRAIN CATCHING OTHER FIXTURES UP | | STREAM PER THE 2020 FBC SEC. R P3101.2.1 VENTING | | REQUIRED AND P 3108.2.1HORIZONTAL WET VENT. | | | | 3. WOULD YOU PLEASE SHOW LOCATION OF THE NEW WATER | | HEATER PER THE WPB AMEND TO FBC 107.2.1 | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | | | | |
|
|
Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
Rev No |
1 |
Status |
P |
Date |
2022-11-14 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2022-11-14 |
Time |
16:25 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2022-11-14 |
Time |
16:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
P |
Date |
2022-07-18 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2022-07-18 |
Time |
14:03 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2022-07-15 |
Time |
09:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
P |
Date |
2022-01-05 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2022-01-05 |
Time |
16:43 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2022-01-05 |
Time |
14:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
4 |
Status |
P |
Date |
2022-07-29 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2022-07-29 |
Time |
08:05 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2022-07-29 |
Time |
08:05 |
Sent To |
|
|
Notes |
2022-07-29 08:09:06 | PETER E VALENTI | | BUILDING PLANS EXAMINER II | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | SIGNATURE REVIEW APPROVED BY REVIEW OF SURVEYOR | | SIGNED/SEALED PAPER SURVEY WITH SURFACE DRAINAGE | | INDICATERS. THE HAND SIGNED/SEALED DOCUMENT HAS BEEN | | ROUTED TO THE STORAGE BIN. |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2022-07-25 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2022-07-25 |
Time |
06:07 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2022-07-25 |
Time |
06:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2022-06-30 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2022-06-30 |
Time |
10:35 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2022-06-30 |
Time |
10:35 |
Sent To |
|
|
Notes |
2022-06-30 10:36:05 | ALL PLANS PASSED SIGNATURE REVIEW |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2021-11-12 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-11-12 |
Time |
14:36 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-11-12 |
Time |
14:26 |
Sent To |
|
|
Notes |
2021-11-12 14:48:33 | THE SIGNATURE OR SEAL IS NOT IN ACCORDANCE WITH FLORIDA | | ADMINISTRATIVE CODE PER 61G15-23.001, FLORIDA STATUTE | | 471. A COPY OF A SS IS NOT ACCEPTABLE, WOULD YOU PLEASE | | UPLOAD A DIGITAL SIGNATURE OR RESTAMP PLAN WITH AN | | ORIGINAL SIGNATURE. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2022-07-29 |
|
|
Cont ID |
|
Sent By |
vbroglia |
Date |
2022-07-29 |
Time |
13:22 |
Rev Time |
0.00 |
Received By |
vbroglia |
Date |
2022-07-29 |
Time |
13:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2022-07-05 |
|
|
Cont ID |
|
Sent By |
vbroglia |
Date |
2022-07-05 |
Time |
14:00 |
Rev Time |
0.00 |
Received By |
vbroglia |
Date |
2022-07-05 |
Time |
14:00 |
Sent To |
|
|
Notes |
2022-07-05 14:14:10 | 7/5/2022 FAILED | | | | PLEASE PROVIDE A SITE PLAN OR SURVEY WITH SETBACKS | | DEMONSTRATED | | PLEASE PROVIDE THE TOTAL HIEGHT ON ELEVATION PLANS FROM | | GRADE | | | | PLEASE NOTE: ACCESSORY STRUCTURE MAY NOT CONTAIN A FULL | | KITCHEN AND/OR STOVE, DUE TO THE ZONING SF7 THIS UNIT | | WILL NOT BE ALLOWED TO BE RENTED OUT. | | | | SEPARATE PERMIT REQUIRED FOR: | | FENCE/WALL, AWNINGS, GENERATOR, MECHANICAL/AC/POOL | | EQUIPMENT, POOLS, IRRIGATION, LANDSCAPE, DRIVEWAYS, | | OTHER. | | | | VALENTINA BROGLIA | | ASSOCIATE PLANNER | | [email protected] | | | | | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2022-01-03 |
|
|
Cont ID |
|
Sent By |
awooten |
Date |
2022-01-03 |
Time |
09:33 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2022-01-03 |
Time |
09:33 |
Sent To |
|
|
Notes |
2022-01-03 09:39:13 | 1/3/22- FAILED. INDICATE ON SITE PLAN THE SIDE SETBACK | | FOR THE NEW ADDITION. | | | | ANGELLA VANN | | 561-822-1441 | | [email protected] |
|
|