Plan Review Details - Permit 21110389
Plan Review Stops For Permit 21110389 |
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
3 |
Status |
P |
Date |
2022-02-11 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2022-02-11 |
Time |
14:58 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2022-02-11 |
Time |
14:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
2 |
Status |
F |
Date |
2022-02-02 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2022-02-02 |
Time |
14:44 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2022-02-02 14:44:43 | TO THE BUILDING CONTRACTOR: | | PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION | | THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE. | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | RENOVATION.HTML | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | [email protected]. THE INFORMATION SHOULD BE IN | | PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE | | INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT | | LINE. | | | | JAMES A. WITMER BN, PX, SFP, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | DEPARTMENT | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | TEL: 561-805-6717 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
1 |
Status |
F |
Date |
2021-12-22 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2021-12-22 |
Time |
08:04 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2021-12-22 |
Time |
07:18 |
Sent To |
|
|
Notes |
2021-12-22 08:04:07 | TO THE BUILDING CONTRACTOR: | | PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION | | THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE. | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | RENOVATION.HTML | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | [email protected]. THE INFORMATION SHOULD BE IN | | PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE | | INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT | | LINE. | | | | JAMES A. WITMER BN, PX, SFP, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | DEPARTMENT | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | TEL: 561-805-6717 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
P |
Date |
2022-02-22 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2022-02-22 |
Time |
07:06 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
F |
Date |
2022-02-16 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2022-02-16 |
Time |
10:30 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2022-02-16 |
Time |
10:29 |
Sent To |
|
|
Notes |
2022-02-16 10:30:04 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION | | SERVICES/ BUILDING DIVISION | | 2020 FBC- BUILDING PLAN REVIEW | | W. P. B. PERMIT: 21110389 | | ADD: 2450 PRESIDENTIAL WAY # 607 | | CONT: J & M CONTRACTORS OF S FLORIDA/ (PLANS BY: J & M | | CONTRACTORS OF S FLORIDA) | | TEL: 561-718-7040 | | E-MAIL: [email protected] | | | | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | BUILDING CODE, BUILDING. | | | | 5TH REVIEW | | DATE: TUES. FEB. 16TH/2022 | | ACTION: DENIED | | | | 1) SHEET A-1: | | 1A-C) COMPLIED. | | | | 1D) THE PLAN SHOWS LIGHT FIXTURES IN THE LIVING ROOM | | CEILING BUT THERE IS NO MENTION OF THIS IS AN EXISTING | | DROPPED CEILING? IF NOT PLEASE PROVIDE A FRAMING | | DETAIL, TYPE OF FRAMING, GAUGE, SPACING AND ANCHORING | | TO THE CONCRETE DECK ABOVE, TYPE OF FINISH MATERIAL AND | | THICKNESS. 107.2.1.2 ADDITIONAL INFORMATION IS | | REQUIRED. | | | | 1E-F) COMPLIED. | | | | 1G) 4TH REQUEST. THERE ARE THREE FLOORING NOTES: | | 1G)(1) FLOORING THROUGHOUT EXCEPT FOR THE MASTER | | BATHROOM. WHAT TYPE OF FLOORING!!!!!!!!! | | 1G)(2)FLOORING REQUIREMENTS. SECTION 1207.3 STRUCTURE | | BORNE SOUND. SOUND PROOFING: PROFLEX 90 MSC 90 MIL. TO | | BE INSTALLED UNDER NEW TILE FLOORING. | | 1G)(3) TYPICAL INTERIOR METAL WALL SECTION. CONCRETE | | FLOORS ADD TILE PER OWNER. | | WHICH ONES DO WE USE, CLARIFY PLEASE? NEW FILE UPLOADED | | FOR PROFLEX LV200 FOR USE WITH LUXURY VINYL PLANK OR | | LUXURY VINYL TILE FLOORING. | | | | 2) COMPLIED. CERTIFICATION BY CONTRACTOR. 107.3.4.3. | | NOTE ALL 3 PLANS WILL NEED TO MATCH!!!! | | | | | | 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS | | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT | | REVIEW CYCLE. | | | | | | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING | | FROM CITY HALL. | | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM | | PART-TIME/ RETIRED. | | | | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET | | BACK INTO THE OFFICE CALL | | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. | | THANK YOU. | | | | JAMES A. WITMER BN, PX, SFP, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | DEPARTMENT | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | TEL: 561-805-6717 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2022-02-15 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2022-02-15 |
Time |
11:05 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2022-02-15 11:05:14 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION | | SERVICES/ BUILDING DIVISION | | 2020 FBC- BUILDING PLAN REVIEW | | W. P. B. PERMIT: 21110389 | | ADD: 2450 PRESIDENTIAL WAY # 607 | | CONT: J & M CONTRACTORS OF S FLORIDA/ (PLANS BY: J & M | | CONTRACTORS OF S FLORIDA) | | TEL: 561-718-7040 | | E-MAIL: [email protected] | | | | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | BUILDING CODE, BUILDING. | | | | 4TH REVIEW | | DATE: TUES. FEB. 15TH/2022 | | ACTION: DENIED | | | | 1) SHEET A-1: | | 1A-C) COMPLIED. | | | | 1D) THE PLAN SHOWS LIGHT FIXTURES IN THE LIVING ROOM | | CEILING BUT THERE IS NO MENTION OF THIS IS AN EXISTING | | DROPPED CEILING? IF NOT PLEASE PROVIDE A FRAMING | | DETAIL, TYPE OF FRAMING, GAUGE, SPACING AND ANCHORING | | TO THE CONCRETE DECK ABOVE, TYPE OF FINISH MATERIAL AND | | THICKNESS. 107.2.1.2 ADDITIONAL INFORMATION IS | | REQUIRED. | | | | 1E-F) COMPLIED. | | | | 1G) 4TH REQUEST. THERE ARE THREE FLOORING NOTES: | | 1G)(1) FLOORING THROUGHOUT EXCEPT FOR THE MASTER | | BATHROOM. WHAT TYPE OF FLOORING!!!!!!!!! | | 1G)(2)FLOORING REQUIREMENTS. SECTION 1207.3 STRUCTURE | | BORNE SOUND. SOUND PROOFING: PROFLEX 90 MSC 90 MIL. TO | | BE INSTALLED UNDER NEW TILE FLOORING. | | 1G)(3) TYPICAL INTERIOR METAL WALL SECTION. CONCRETE | | FLOORS ADD TILE PER OWNER. | | WHICH ONES DO WE USE, CLARIFY PLEASE? NEW FILE UPLOADED | | FOR PROFLEX LV200 FOR USE WITH LUXURY VINYL PLANK OR | | LUXURY VINYL TILE FLOORING. | | | | 2) COMPLIED. CERTIFICATION BY CONTRACTOR. 107.3.4.3. | | NOTE ALL 3 PLANS WILL NEED TO MATCH!!!! | | | | | | 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS | | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT | | REVIEW CYCLE. | | | | | | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING | | FROM CITY HALL. | | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM | | PART-TIME/ RETIRED. | | | | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET | | BACK INTO THE OFFICE CALL | | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. | | THANK YOU. | | | | JAMES A. WITMER BN, PX, SFP, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | DEPARTMENT | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | TEL: 561-805-6717 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2022-02-11 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2022-02-11 |
Time |
14:59 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2022-02-11 |
Time |
14:58 |
Sent To |
|
|
Notes |
2022-02-11 15:06:03 | PETER E VALENTI | | BUILDING PLANS EXAMINER II | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | BUILDING REVIEW DENIED: | | | | THE SUBMITTED FLOORING UNDERLAYMENT PROFLEX MSC 90 IS | | APPROVED FOR AN 8" SLAB, THIS SLAB APPEARS TO BE A 6" | | THICK SLAB. PLEASE PROVIDE THE TEST REPORTS THAT SHOW | | THE 6" SLAB WILL WORK WITH PROFLEX MSC 90 WITH A | | DROPPED DRYWALL CEILING (IF THAT'S THE CASE). |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2022-02-01 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2022-02-01 |
Time |
12:59 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2022-02-01 12:58:52 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION | | SERVICES/ BUILDING DIVISION | | 2020 FBC- BUILDING PLAN REVIEW | | W. P. B. PERMIT: 21110389 | | ADD: 2450 PRESIDENTIAL WAY # 607 | | CONT: J & M CONTRACTORS OF S FLORIDA | | TEL: 561-718-7040 | | E-MAIL: [email protected] | | | | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | BUILDING CODE, BUILDING. | | | | 2ND REVIEW | | DATE: TUES. FEB. 01/2022 | | ACTION: DENIED | | | | 1) SHEET A-1: | | 1A-F) COMPLIED | | | | 1G) THE FLOOR PLAN NOW STATES THE FLOOR UNDERLAYMENT TO | | BE INSTALLED IS PROFLEX 90 MSC. THE CITY HAS NEVER SEEN | | THE PRODUCT PROFLEX 90 MSC TESTED FOR A 6 INCH CONCRETE | | SLAB FOR EITHER MARBLE OR TILE. | | FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, | | STONE, MARBLE, VINYL LAMINATE FLOORING AND WOOD | | FLOORING ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT | | TESTED FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND | | MEET THE QUALIFICATIONS LISTED UNDER EACH OF THE | | STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO | | DROPPED CEILING: | | PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR | | TYPE II BUILDINGS SHOWING COMPLIANCE WITH: | | | | 1G)(1) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND. | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. | | | | 1G)(2) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS, | | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR | | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E | | 90. | | | | 1G)(3) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | 2) 2ND REQUEST. THERE ARE 3 DIFFERENT CONTRACTORS FROM | | 3 DIFFERENT TRADES, A GENERAL CONTRACTOR, ELECTRICAL | | CONTRACTOR AND PLUMBING CONTRACTOR EACH TAKING | | RESPONSIBILITY FOR THE ONE SUBMITTED SHEET. | | | | FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE | | DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR | | NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE | | PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD | | HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND | | PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER | | ONE SHEET | | | | 1ST ROUND OF COMMENTS. CERTIFICATION BY CONTRACTOR. | | 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT CREATED / | | DREW THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES | | AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME, | | SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE | | LICENSED IN AND PLANS DRAWN. | | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE | | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) | | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) | | (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT | | WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE | | CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. | | THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET | | OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR | | OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME | | AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN | | AND PLANS DRAWN. | | FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE | | DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR | | NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE | | PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD | | HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND | | PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER | | ONE SHEET. | | | | | | 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS | | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT | | REVIEW CYCLE. | | | | | | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING | | FROM CITY HALL. | | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM | | PART-TIME/ RETIRED. | | | | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET | | BACK INTO THE OFFICE CALL | | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. | | THANK YOU. | | | | JAMES A. WITMER BN, PX, SFP, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | DEPARTMENT | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | TEL: 561-805-6717 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2021-12-22 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2021-12-22 |
Time |
08:02 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2021-12-22 |
Time |
07:18 |
Sent To |
|
|
Notes |
2021-12-22 08:02:55 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION | | SERVICES/ BUILDING DIVISION | | 2020 FBC- BUILDING PLAN REVIEW | | W. P. B. PERMIT: 21110389 | | ADD: 2450 PRESIDENTIAL WAY # 607 | | CONT: J & M CONTRACTORS OF S FLORIDA | | TEL: 561-718-7040 | | E-MAIL: [email protected] | | | | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | DATE: WED. DEC. 22/2021 | | ACTION: DENIED | | | | 1) SHEET A-1: | | 1A) THE HEADING OF EXISTING BUILDING CODE LIST THE | | LEVEL OF ALTERATION AS LEVEL 1. PLEASE NOTE IN THE | | BEDROOM # 2 BATH THERE IS THE RECONFIGURATION OF SPACE | | WITH THE REMOVAL OF THE TUB FOR NEW SHOWER, CURB, TILE | | DRAIN COVER AND VALVE. RECONFIGURE OF SPACE BATH# 2 | | REMOVE SWING DOOR AND RECONFIGURE TO POCKET DOOR. | | LAUNDRY REMOVAL OF SINK. | | LEVEL 2 ALTERANITIONS, 2020 EXIST. BUILD. CODE. SECTION | | 603. LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF | | SPACE, THE ADDITION OR ELIMINATION OF ANY DOOR OR | | WINDOW, THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM, | | OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT. | | | | 1B) THE FLOOR PLAN INDICATES IN SHOWERS THE REMOVAL OF | | WALL TILE BUT THERE IS NO REFERENCE TO THE TYPE OF | | BACKER BOARD TO BE INSTALLED. PLEASE SHOW COMPLIANCE | | WITH 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS | | A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS | | AND CEILING PANELS IN SHOWER AREAS SHALL BE OF | | MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN | | ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER | | RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE | | FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN | | INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND | | THE MANUFACTURE?S RECOMMENDATIONS. | | | | 1C) 2020 FBC-B SHOWERS & TUBS 1210.3. SHOWER | | COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS | | SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A | | HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET. | | | | 1D) THE PLAN SHOWS LIGHT FIXTURES IN THE LIVING ROOM | | CEILING BUT THERE IS NO MENTION OF THIS IS AN EXISTING | | DROPPED CEILING? IF NOT PLEASE PROVIDE A FRAMING | | DETAIL, TYPE OF FRAMING, GAUGE, SPACING AND ANCHORING | | TO THE CONCRETE DECK ABOVE, TYPE OF FINISH MATERIAL AND | | THICKNESS. 107.2.1.2 ADDITIONAL INFORMATION IS | | REQUIRED. | | | | 1E) THE LIVING ROOM FLOOR PLAN ALSO INDICATES TO ADD A | | 2 INCH DROP CEILING THIS ROOM ONLY, IS THIS A DROP 2 | | INCHES LOWER THAT THE EXISTING CEILING OR A 2 INCH | | DROPPED SOFFIT? 107.2.1.2. ADDITIONAL INFORMATION | | REQUIRED, CLARIFICATION. | | | | 1F) PROJECT CODE REFERENCES: THE 2020 FBC-RESIDENTIAL | | CODE, PLEASE NOTE THE RESIDENTIAL CODE IS FOR ONE & TWO | | FAMILY DWELLINGS (R-3 OCCUPANCIES). THE CODE REFERENCE | | SHOULD BE THE 2020 FBC-BUILDING CODE FOR (R2 | | OCCUPANCIES, CONDOMINIUMS & APARTMENTS). | | | | 1G) THERE ARE THREE FLOORING NOTES: | | 1G)(1) NEW FLOORING THROUGHOUT EXCEPT FOR THE MASTER | | BATHROOM. | | 1G)(2)FLOORING REQUIREMENTS. SECTION 1207.3 STRUCTURE | | BORNE SOUND. SOUND PROOFING: SUPER SAM 125 TO | | BE INSTALLED UNDER NEW MARBLE. | | 1G)(3) TYPICAL INTERIOR METAL WALL SECTION. CONCRETE | | FLOORS ADD VINYL/ TILE/CARPET PER OWNER | | WHICH ONES DO WE USE, CLARIFY PLEASE? NOTE WE WILL | | UPLOAD REPORTS FOR SUPER SAM 125 FOR MARBLE AND TILE IF | | THIS IS THE CHOICE OF FINISH FLOOR MATERIAL. | | | | 2) CERTIFICATION BY CONTRACTOR. 107.3.4.3. THE | | CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET OF | | PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF | | THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND | | LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND | | PLANS DRAWN. | | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE | | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) | | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) | | (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT | | WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE | | CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. | | THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET | | OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR | | OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME | | AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN | | AND PLANS DRAWN. | | FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE | | DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR | | NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE | | PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD | | HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND | | PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER | | ONE SHEET. | | | | | | 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS | | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT | | REVIEW CYCLE. | | | | | | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING | | FROM CITY HALL. | | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM | | PART-TIME/ RETIRED. | | | | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET | | BACK INTO THE OFFICE CALL | | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. | | THANK YOU. | | | | JAMES A. WITMER BN, PX, SFP, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | DEPARTMENT | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | TEL: 561-805-6717 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2022-02-24 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-02-24 |
Time |
13:54 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-02-24 |
Time |
13:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2022-02-08 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-02-08 |
Time |
15:03 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-02-08 |
Time |
14:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2021-12-20 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-12-20 |
Time |
13:58 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-12-20 |
Time |
13:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2022-02-22 |
|
|
Cont ID |
|
Sent By |
cwalker |
Date |
2022-02-22 |
Time |
|
Rev Time |
0.00 |
Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2022-01-28 |
|
|
Cont ID |
|
Sent By |
cwalker |
Date |
2022-01-28 |
Time |
|
Rev Time |
0.00 |
Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2021-11-12 |
|
|
Cont ID |
|
Sent By |
cwalker |
Date |
2021-11-12 |
Time |
|
Rev Time |
|
Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2021-11-12 10:42:11 | PROVIDE INFORMATION ON THE CRITICAL RADIANT FLUX OF THE | | FLOORING TO BE INSTALLED. NFPA 101 10.2.7, | | ALL FIRE AND LIFE SAFETY SYSTEMS SHALL BE MAINTAINED IN | | AN OPERABLE CONDITION AND PROTECTED FROM DAMAGE. NFPA | | 101 43.6.4 & 43.6.5 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2022-02-24 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-02-24 |
Time |
13:54 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-02-18 |
Time |
09:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2022-02-16 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2022-02-16 |
Time |
10:30 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2022-02-16 |
Time |
10:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2022-02-15 |
Time |
|
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2022-02-15 |
Time |
07:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2022-02-11 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2022-02-11 |
Time |
15:39 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2022-02-11 |
Time |
14:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2022-02-08 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-02-08 |
Time |
15:04 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-01-27 |
Time |
08:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2021-12-22 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2021-12-22 |
Time |
08:08 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2021-11-10 |
Time |
06:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2022-02-23 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2022-02-23 |
Time |
11:22 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2022-02-23 |
Time |
10:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2022-02-02 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2022-02-02 |
Time |
08:37 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2022-02-01 |
Time |
15:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2021-11-29 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2021-11-29 |
Time |
16:46 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2021-11-29 |
Time |
16:03 |
Sent To |
|
|
Notes |
2021-11-29 16:46:48 | 1ST REVIEW FBC-2020 PLUMBING | | PERMIT- 21110389 | | 11/29/2021 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET A-1: PROVIDE A WATER HEATER EQUIPMENT SCHEDULE | | INDICATING THE MAKE AND MODEL, GALLON SIZE AND | | EFFICIENCY RATING- SECTION 107.2.1 WPB AND C404.2 FBC | | EC. | | | | 2) A-1: PROVIDE A SHOWER PAN DETAIL- SECTION 421.5.2 | | FBC P. CLARIFY IF THE EXISTING DRAIN WILL BE RE-USED OR | | A NEW DRAIN WILL BE INSTALLED. | | | | 3) A-1: SHOW THE LOCATIONS OF THE NEW WASHING MACHINE | | SHUTOFF VALVES TO SHOW ACCESS WILL BE PROVIDED- SECTION | | 606.3 FBC P. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
4 |
Status |
P |
Date |
2022-02-24 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-02-24 |
Time |
13:54 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-02-24 |
Time |
13:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2022-02-11 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2022-02-11 |
Time |
15:15 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2022-02-11 |
Time |
15:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2022-02-01 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2022-02-01 |
Time |
13:00 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2022-02-01 13:00:13 | 2ND REQUEST. THERE ARE 3 DIFFERENT CONTRACTORS FROM 3 | | DIFFERENT TRADES, A GENERAL CONTRACTOR, ELECTRICAL | | CONTRACTOR AND PLUMBING CONTRACTOR EACH TAKING | | RESPONSIBILITY FOR THE ONE SUBMITTED SHEET. | | FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE | | DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR | | NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE | | PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD | | HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND | | PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER | | ONE SHEET | | | | 1ST ROUND OF COMMENTS. CERTIFICATION BY CONTRACTOR. | | 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT CREATED / | | DREW THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES | | AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME, | | SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE | | LICENSED IN AND PLANS DRAWN. | | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE | | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) | | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) | | (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT | | WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE | | CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. | | THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET | | OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR | | OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME | | AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN | | AND PLANS DRAWN. | | FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE | | DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR | | NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE | | PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD | | HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND | | PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER | | ONE SHEET. | | | | JAMES A. WITMER BN, PX, SFP, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | DEPARTMENT | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | TEL: 561-805-6717 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2021-12-22 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2021-12-22 |
Time |
08:08 |
Rev Time |
|
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2021-12-22 08:08:11 | SHEET A-1 IS NOT DRAWN BY A DESIGN PROFESSIONAL, SHOWS | | ELECTRICAL, PLUMBING AND BUILDING COMPONENTS ON THE | | SAME SHEET. | | CERTIFICATION BY CONTRACTOR. 107.3.4.3. THE CONTRACTOR | | (QUALIFIER) THAT CREATED / DREW THE SET OF PLANS WILL | | NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. | | PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE | | NUMBER FOR THE TRADE YOU ARE LICENSED IN AND PLANS | | DRAWN. | | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE | | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) | | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) | | (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT | | WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE | | CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. | | THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET | | OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR | | OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME | | AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN | | AND PLANS DRAWN. | | FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE | | DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR | | NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE | | PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD | | HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND | | PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER | | ONE SHEET. | | |
|
|
|