Plan Review Details - Permit 21110387
Plan Review Stops For Permit 21110387 |
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
N |
Date |
2022-03-17 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2022-03-17 |
Time |
15:43 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2022-03-17 |
Time |
15:43 |
Sent To |
|
|
Notes |
2022-03-17 15:43:35 | SEE 21120216 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2022-02-14 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-02-14 |
Time |
16:32 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-02-14 |
Time |
16:26 |
Sent To |
|
|
Notes |
2022-02-14 16:34:58 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | JAKE LEAHY | | BU1753, BN1165, PX163 | | [email protected] | | 561-805-6713 | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | BATHROOM IN UNIT "D" DOES NOT SHOW ANY ELECTRIC WORK. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2021-12-21 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2021-12-21 |
Time |
10:03 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2021-12-21 |
Time |
10:03 |
Sent To |
|
|
Notes |
2021-12-21 10:21:39 | ELECTRICAL PLAN REVIEW FAILED | | 1) PLEASE CHANGE ALL REFERENCES TO NEC 2020 CODE TO THE | | CURRENTLY ADOPTED 2017 NEC | | 2) PLEASE ENSURE ALL APPLICABLE 120-VOLT CIRCUITS | | COMPLY WITH ARC FAULT PROTECTION AS OTLINED IN NEC | | 210.12. A NOTE WILL SUFFICE | | 3) VERIFY VALUE OF ELECTRICAL ALTERATION AS PER WPB | | AMENDMENT 109.3 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2022-02-14 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2022-02-14 |
Time |
12:55 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2022-01-31 |
Time |
06:32 |
Sent To |
|
|
Notes |
2022-02-14 12:55:50 | PERMIT CHANGED TO SUB OF 21120216 PER SH. REVIEWS WILL | | BE COMPLETED UNDER MASTER AO |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2021-12-21 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2021-12-21 |
Time |
10:29 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2021-12-21 |
Time |
10:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
N |
Date |
2022-02-14 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-02-14 |
Time |
16:36 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-02-14 |
Time |
16:36 |
Sent To |
|
|
Notes |
2022-02-14 16:37:08 | SEE REVIEW FROM 12/21/21 | | | | PLANS NEED A VERIFIABLE DIGITAL SIGNATURE. |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2021-12-21 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2021-12-21 |
Time |
10:26 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2021-12-21 |
Time |
10:26 |
Sent To |
|
|
Notes |
2021-12-21 10:29:05 | SIGNATURE REVIEW FAILED | | DRAWING E-2 APPEARS TO BE A COPY OF THE ENGINEER OF | | RECORDS SIGNATURE. PLEASE CORRECT THIS AS OUTLINED | | BELOW | | | | PLANS SUBMITTED ELECTRONICALLY MUST BE DIGITALLY SIGNED | | AND SEALED BY THE ENGINEER OF RECORD | | FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR | | ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND | | SIGNED. | | EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN | | TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF | | APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX, | | OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER | | ORIGINAL WITH A WET SIGNATURE TO THE BUILDING DIVISION. | | SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO | | BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED | | DOCUMENTS ARE PREFERRED. | | | | PLEASE EMAIL [email protected] AND CC TO | | [email protected] | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|
|
|