Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-11-04 Cont ID  
Sent By hmoser Date 2021-11-04 Time 09:38 Rev Time 0.00
Received By hmoser Date 2021-11-04 Time 09:38 Sent To  
Notes
2021-11-04 09:41:0511/4/2021
 CONTRACTOR CALLED THEY ARE JUST CHANGING DUCTWORK. HM.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-11-03 Cont ID  
Sent By hmoser Date 2021-11-03 Time 13:40 Rev Time 0.00
Received By hmoser Date 2021-11-03 Time 12:45 Sent To  
Notes
2021-11-03 14:01:55PLAN DENIED
 1) REFER TO SECTION R403.3.6 AIR - HANDLING UNITS
 2020 FBC ( ENERGY CODE )
 2) REFER TO SECTION R403.7.1 EQUIPMENT SIZING.
 2020 FBC ( ENERGY CODE )
 3) PROVIDE EQUIPMENT SCHEDULE ON PLANS.
 PLAN REVIEW BY HAROLD MOSER