Plan Review Details - Permit 21101422
Plan Review Stops For Permit 21101422
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2022-02-02 Cont ID  
Sent By rmcphers Date 2022-02-02 Time 08:02 Rev Time 0.00
Received By rmcphers Date 2022-02-02 Time 08:01 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2022-02-01 Cont ID  
Sent By rmcphers Date 2022-02-01 Time 13:48 Rev Time 0.00
Received By rmcphers Date 2022-02-01 Time 13:47 Sent To  
Notes
2022-02-01 13:48:50ASBESTOS LETTER PROVIDED NEEDS TO BE SIGNED BY THE
 CONTRACTOR -
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-11-18 Cont ID  
Sent By rmcphers Date 2021-11-18 Time 16:23 Rev Time 0.00
Received By rmcphers Date 2021-11-18 Time 16:23 Sent To  
Notes
2021-11-18 16:23:53PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-02-01 Cont ID  
Sent By rmcphers Date 2022-02-01 Time 13:55 Rev Time 0.00
Received By rmcphers Date 2022-02-01 Time 13:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-11-18 Cont ID  
Sent By rmcphers Date 2021-11-18 Time 16:26 Rev Time 0.00
Received By rmcphers Date 2021-11-18 Time 16:24 Sent To  
Notes
2021-11-18 16:26:44CONDO REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
  
 1) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 2). YOU CAN EMAIL ME THE PROPOSED TEST REPORTS TO
 VERIFY THAT THEY ARE TEST REPORTS BEFORE RESUBMITTING
 TO PROJECTDOX ( [email protected] )
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-11-04 Cont ID  
Sent By jleahy Date 2021-11-04 Time 16:28 Rev Time 0.00
Received By jleahy Date 2021-11-04 Time 16:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2021-11-05 Time   Rev Time 0.00
Received By bdolan Date 2021-11-05 Time 10:17 Sent To  
Notes
2021-11-01 12:42:14FIRE DEPARTMENT HAS NO OBJECTIONS TO PROJECT.
  
 ALL WORK IS SUBJECT TO FIELD INSPECTIONS.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-02-01 Cont ID  
Sent By rmcphers Date 2022-02-01 Time 13:56 Rev Time 0.00
Received By rmcphers Date 2022-01-27 Time 07:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-18 Cont ID  
Sent By rmcphers Date 2021-11-18 Time 16:27 Rev Time 0.00
Received By rmcphers Date 2021-10-29 Time 15:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2021-11-01 Cont ID  
Sent By medwards Date 2021-11-01 Time 09:15 Rev Time 0.00
Received By medwards Date 2021-11-01 Time 09:15 Sent To  
Notes
2021-11-01 09:15:56NO MECHANICAL WORK SHOWN FOR THIS PROJECT. ME

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-11-03 Cont ID  
Sent By lcrespo Date 2021-11-03 Time 06:13 Rev Time 0.00
Received By lcrespo Date 2021-11-03 Time 06:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-10-29 Cont ID  
Sent By mpeterso Date 2021-10-29 Time 16:03 Rev Time 0.00
Received By mpeterso Date 2021-10-29 Time 16:03 Sent To  
Notes
2021-10-29 16:04:00REVIEW OF SIGNATURE AND SEAL ON PAPER PLANS APPROVED,
 ROUTED TO STORAGE