Plan Review Details - Permit 21101084
Plan Review Stops For Permit 21101084
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-11-22 Cont ID  
Sent By cpuell Date 2021-11-22 Time 12:03 Rev Time 0.00
Received By cpuell Date 2021-11-22 Time 12:03 Sent To  
Notes
2021-11-22 12:04:091750 @ MPALM BEACH LAKES BLVD ADDRESS GIVEN FOR PROJECT

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-10-22 Cont ID  
Sent By cpuell Date 2021-10-22 Time 14:07 Rev Time 0.00
Received By cpuell Date 2021-10-22 Time 14:07 Sent To  
Notes
2021-10-22 14:08:07APPLICANT SHOULD HAVE COORDINATED WITH ADDRESSING TO BE
 ASSIGNED AN ADDRESS BEFORE SUBMITTING. PLEASE CONTACT
 [email protected] OR CALL 561-805-6659

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2022-05-12 Cont ID  
Sent By mpeterso Date 2022-05-12 Time 13:26 Rev Time 0.00
Received By mpeterso Date 2022-05-12 Time 13:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-02-05 Cont ID  
Sent By fgiaquin Date 2022-02-05 Time 15:30 Rev Time 0.00
Received By fgiaquin Date 2022-02-05 Time 14:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-12-21 Cont ID  
Sent By mpeterso Date 2021-12-21 Time 11:46 Rev Time 0.00
Received By mpeterso Date 2021-12-21 Time 11:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-11-19 Cont ID  
Sent By fgiaquin Date 2021-11-19 Time 21:44 Rev Time 0.00
Received By fgiaquin Date 2021-11-19 Time 20:15 Sent To  
Notes
2021-11-19 21:44:33ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. MINIMUM WIRE SIZE FOR 7.5KVA SINGLE PHASE STEP DOWN
 TRANSFORMER IS #12 CU. NEC 110.14C1A2
  
 2. PRIMARY OCP FOR 7.5 KVA TRANSFORMER SHOULD BE
 20AMPS. NEC 215.3A, 450.3B1. 240.4
  
 3. SECONDARY OCP FOR 7.5KVA TRANSFORMER SHOULD BE
 40AMPS MAX. NEC 215.3A 408.36
  
 4. EGC SHOWN FROM METER CAN TO SERVICE DISCONNECTING
 MEANS. THIS IS A PARALLEL PATH BACK TO GROUNDED
 CONDUCTOR. EGC ORIGINATES AT 1ST MEANS OF DISCONNECT ON
 LOAD SIDE. PLEASE REMOVE. NEC 250.24
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2022-01-20 Cont ID  
Sent By eschneid Date 2022-01-20 Time 16:43 Rev Time 0.00
Received By eschneid Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-05-27 Cont ID  
Sent By lmarchan Date 2022-05-27 Time 13:19 Rev Time 0.00
Received By lmarchan Date 2022-05-04 Time 09:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-03-16 Cont ID  
Sent By lmarchan Date 2022-03-16 Time 10:47 Rev Time 0.00
Received By lmarchan Date 2022-01-26 Time 08:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-21 Cont ID  
Sent By mpeterso Date 2022-01-21 Time 07:46 Rev Time 0.00
Received By lmarchan Date 2021-12-21 Time 12:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-19 Cont ID  
Sent By fgiaquin Date 2021-11-19 Time 21:44 Rev Time 0.00
Received By fgiaquin Date 2021-10-26 Time 07:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-05-12 Cont ID  
Sent By mpeterso Date 2022-05-12 Time 13:35 Rev Time 0.00
Received By mpeterso Date 2022-05-12 Time 13:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-02-05 Cont ID  
Sent By fgiaquin Date 2022-02-05 Time 17:50 Rev Time 0.00
Received By fgiaquin Date 2022-02-05 Time 17:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-12-21 Cont ID  
Sent By mpeterso Date 2021-12-21 Time 12:14 Rev Time 0.00
Received By mpeterso Date 2021-12-21 Time 12:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-11-19 Cont ID  
Sent By fgiaquin Date 2021-11-19 Time 21:44 Rev Time  
Received By fgiaquin Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2022-05-27 Cont ID  
Sent By eschneid Date 2022-05-27 Time 13:17 Rev Time 0.25
Received By eschneid Date 2022-05-27 Time 11:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2022-03-15 Cont ID  
Sent By eschneid Date 2022-03-15 Time 17:31 Rev Time 0.25
Received By eschneid Date 2022-03-15 Time 17:31 Sent To  
Notes
2022-03-15 17:32:19FAILED
  
 1) PROVIDE A SURVEY, PREPARED BY A FLORIDA LICENSED
 SURVEYOR, WHICH SHOWS THE LOCATION OF THE PROPOSED
 POLE, HANDHOLES, BORE PITS, THE UNDERGROUND ELECTRIC
 ROUTE, AND THE RIGHT-OF-WAY LINE SO THAT STAFF CAN
 VERIFY THAT THE WIRELESS COMMUNICATION FACILITY IS
 WITHIN THE RIGHT-OF-WAY AND NOT ON PRIVATE PROPERTY.
  
 2) THE WIRELESS FACILITY (POLE) SHOWN ON SHEET E201
 DOES NOT MEET THE CITY OF WEST PALM BEACH CONCEALMENT
 (STEALTH), STYLE REQUIREMENTS, NOR DOES IT MATCH THE
 POLE SHOWN ON SHEET A201. ALL PLANS NEED TO SHOW THE
 SAME, COMPLIANT STEALTH POLES.
  
 3) UTILITY FRAMES ARE NOT PERMITTED FOR WIRELESS
 FACILITIES BY THE CITY OF WEST PALM BEACH CITY CODE.
 THE FRAME SHOWN ON SHEETS E202 AND A201 IS NOT
 PERMITTED.
  
 4) THE WIRELESS FACILITY COMPLIES WITH CITY HEIGHT
 REQUIREMENTS. THE POLE COLOR AT THIS LOCATION SHALL BE
 RAL/RAYCAP 7040 WINDOW GREY.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-01-20 Cont ID  
Sent By eschneid Date 2022-01-20 Time 16:42 Rev Time 0.25
Received By eschneid Date 2022-01-20 Time 16:22 Sent To  
Notes
2022-01-20 16:42:41FAILED
  
 1) PROVIDE A SURVEY, PREPARED BY A FLORIDA LICENSED
 SURVEYOR, WHICH SHOWS THE LOCATION OF THE PROPOSED
 POLE, HANDHOLES, BORE PITS, THE UNDERGROUND ELECTRIC
 ROUTE, AND THE RIGHT-OF-WAY LINE SO THAT STAFF CAN
 VERIFY THAT THE WIRELESS COMMUNICATION FACILITY IS
 WITHIN THE RIGHT-OF-WAY AND NOT ON PRIVATE PROPERTY.
  
 2) PROVIDE A COPY OF THE PALM BEACH COUNTY RIGHT-OF-WAY
 APPROVAL IF THE SURVEY SHOWS THE PROPOSED WIRELESS
 COMMUNICATION FACILITY IN THE RIGHT-OF-WAY.
  
 3) THE PROPOSED WIRELESS FACILITY (POLE) DOES NOT MEET
 THE CITY OF WEST PALM BEACH CONCEALMENT (STEALTH),
 STYLE AND POSSIBLY THE HEIGHT REQUIREMENTS LISTED IN
 SECTIONS 78-411(E), 78-411(F) AND 78-411(G) OF THE CITY
 CODE. PROVIDE A POLE THAT MEETS THE CITY CODE
 REQUIREMENTS. NOTE: VERIZON HAS SHOWN POLES ON OTHER
 APPLICATIONS THAT MEET THE CITY CODE REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  