Plan Review Details - Permit 21101014
Plan Review Stops For Permit 21101014
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-01-19 Cont ID  
Sent By jwitmer Date 2022-01-19 Time 13:44 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-11-30 Cont ID  
Sent By jwitmer Date 2021-11-30 Time 12:45 Rev Time 0.00
Received By jwitmer Date 2021-11-30 Time 11:30 Sent To  
Notes
2021-11-30 12:44:36WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21101014
 ADD: 2480 PRESIDENTIAL WAY # 501
 CONT: WRIGHT?S IMPACT WINDOW & DOOR LLC
 TEL: 561-588-7353
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. NOV. 30TH/ 2021
 ACTION: DENIED
  
 1) 2ND REQUEST. DRAWING 1 WRIGHT'S FLOOR PLAN NEEDS TO
 SHOW WHO THE AUTHOR IS OF THE PLAN. CERTIFICATION BY
 CONTRACTOR. 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT
 CREATED / DREW THE SET OF PLANS WILL NEED TO IDENTIFY
 THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE PRINT
 YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR THE
 TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
  
 2) COMPLIED. ALUMINIUM MULLION POST.
  
 3) COMPLIED.
 4) COMPLIED. THE END ZONE FOR THE BUILDING IS STATED TO
 BE 24 FEET FROM THE CORNER OF THE BUILDING.
  
 5A) 2ND REQUEST. SHEET S1 AND CALCULATIONS FOR NEW TUBE
 SUPPORTS SHEET 3 OF 13. THE END ZONE (5) IS STATED TO
 BE 24 FEET FROM THE CORNER OF THE BUILDING, BUT 2 AND 3
 ARE SHOWN TO BE IN WALL ZONE 4. OPENING 2 IS 8 FEET
 WIDE OPENING 3 IS 11 FEET WIDE OR 19 FEET OF OPENING
 AND POSSIBLY A 2-FOOT-WIDE COLUMN A TOTAL OF 21 FEET
 FROM THE CORNER. IT WOULD APPEAR OPENINGS 2 AND 3
 SHOULD ALSO BE IN THE END ZONE (5) WITH HIGHER
 PRESSURES.
 1ST ROUND OF COMMENTS. THE REVIEW OF THE SUBMITTED
 PRODUCT APPROVALS CAN NOT OCCUR WITH ALL OF THE
 UNKNOWNS LISTED IN COMMENT 4 AND 5.
  
 5B) 2ND REQUEST. W. P. B. 107.3.4. PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA
 ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND
 APPROVED IN WRITING (SHOP DRAWING STAMP OF APPROVAL) BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 6) NEW COMMENT. THE COVERSHEET C LIST CONSTRUCTION TYPE
 OF CONSTRUCTION TYPE AS V-B. PLEASE REVIEW THE 2020
 FBC-BUILDING CODE TABLE 504.4 FOR R2 OCCUPANCY
 CONSTRUCTION TYPE AS I-A. PLEASE UPDATE THE PLANS.
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-11-23 Cont ID  
Sent By jwitmer Date 2021-11-23 Time 16:12 Rev Time 0.00
Received By jwitmer Date 2021-11-23 Time 15:30 Sent To  
Notes
2021-11-23 16:12:02WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21101014
 ADD: 2480 PRESIDENTIAL WAY # 501
 CONT: WRIGHT?S IMPACT WINDOW & DOOR LLC
 TEL: 561-588-7353
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. NOV. 23RD/ 2021
 ACTION: DENIED
  
 1) DRAWING 1 WRIGHT?S FLOOR PLAN NEEDS TO SHOW WHO THE
 AUTHOR IS OF THE PLAN. CERTIFICATION BY CONTRACTOR.
 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT CREATED /
 DREW THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES
 AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME,
 SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE
 LICENSED IN AND PLANS DRAWN.
  
 2) DRAWING 1 WRIGHT?S FLOOR PLAN IT APPEARS IS TRYING
 TO CREATE A CORNER POST/ COLUMN BY USING (3) 2X5 S,
 COVER GAP WITH 5/8 INCH PLYWOOD AND WRAP WITH
 BREAK-METAL. PLEASE NOTE THERE IS NO INFORMATION AS TO
 WHAT TYPE OF METAL STUDS ARE GOING TO BE USED.
 ARCHITECTURAL OR STRUCTURAL, GAUGE, SCREW SIZE OR
 SPACING TO CREATE THE COLUMN, TOP AND BOTTOM PLATES,
 ANCHORS TO CONCRETE, ANCHORS INTO THE METAL COLUMN,
 TYPE OF ANCHORS AND SPACING TO SECURE THE PLYWOOD, TYPE
 OF MATERIAL AND THICKNESS TO SEPARATE THE STEEL SCREWS
 OF THE SUB SHEATHING AND ALUMINUM BREAK METAL TO STOP
 ELECTROLYSIS FROM OCCURRING. THIS STRUCTURE NEEDS TO BE
 ENGINEERED WITH CALCULATIONS FOR THE LATERAL FORCES IT
 IS GOING TO NEED TO RESIST WITH SAFETY FACTOR. SEE THE
 DEFINITIONS FOR ENGINEERING 2021 FS 471.005(7).
  
 3) MISSING 2020 FBC-B 1603.1.4 WIND DESIGN DATA. THE
 FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL BE
 SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 3.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 3.2. RISK CATEGORY.
  
 3.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1.
  
 3.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 3.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 3.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
  
 4) THE FLOOR PLAN STATES THIS IS A 220 FOOT HIGHRISE
 BUILDING BUT THERE WAS NO ENGINEERING SHEET FOR
 COMPONENTS AND CLADDING SUBMITTED NOR WHICH WINDOWS AND
 DOORS ARE IN WALL ZONE 4 AND 5. BUILDING END ZONES (5).
 THE FLOOR PLAN LAYOUT INDICATES THE WORK TO BE
 PERFORMED UNDER THIS PERMIT IS A CORNER UNIT OF A
 HIGHRISE BUILDING. THE WIND LOAD CHART UNDER NOTES
 STATES WHAT IS CONSIDERED AN END ZONE 10% OF THE LEAST
 HORIZONTAL DISTANCE OF THE BUILDING OR 40% OF THE MRH,
 BUT NOT LESS THAN 4% OF THE LEAST HORIZONTAL DISTANCE
 OR 3 FT. THE CONTRACTOR HAS NOT IDENTIFIED WHAT THE
 LEAST HORIZONTAL DISTANCE IS FOR THE BUILDING NOR THE
 LOCATION OF THE UNIT IN RELATIONSHIP TO THE BUILDING
 AND THE INTERCOASTAL WATERWAY. EXAMPLE ONLY. IF THE
 BUILDING HEIGHT IS APPROXIMATELY 180 FT. (MRH.) X 0.40=
 72 FEET. THIS WOULD PUT ALL OPENINGS IN WIND ZONE 5 OR
 10% OF THE LEAST HORIZONTAL DISTANCE OF THE BUILDING,
 ALSO UNKNOWN.
  
 5A) THE REVIEW OF THE SUBMITTED PRODUCT APPROVALS CAN
 NOT OCCUR WITH ALL OF THE UNKNOWNS LISTED IN COMMENT 4
 AND 5.
  
 5B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-01-19 Cont ID  
Sent By jwitmer Date 2022-01-19 Time 13:44 Rev Time 0.00
Received By jwitmer Date 2022-01-11 Time 12:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-11-30 Cont ID  
Sent By jwitmer Date 2021-11-30 Time 12:46 Rev Time 0.00
Received By jwitmer Date 2021-11-29 Time 06:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-23 Cont ID  
Sent By jwitmer Date 2021-11-23 Time 16:12 Rev Time 0.00
Received By jwitmer Date 2021-10-27 Time 05:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-01-19 Cont ID  
Sent By jwitmer Date 2022-01-19 Time 13:42 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-11-30 Cont ID  
Sent By jwitmer Date 2021-11-30 Time 12:46 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-11-23 Cont ID  
Sent By jwitmer Date 2021-11-23 Time 16:11 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2021-11-23 16:11:25DRAWING 1 WRIGHT?S FLOOR PLAN NEEDS TO SHOW WHO THE
 AUTHOR IS OF THE PLAN. CERTIFICATION BY CONTRACTOR.
 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT CREATED /
 DREW THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES
 AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME,
 SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE
 LICENSED IN AND PLANS DRAWN.
  
  