Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2021-10-28 Cont ID  
Sent By amhamilt Date 2021-10-28 Time 10:53 Rev Time 0.00
Received By amhamilt Date 2021-10-28 Time 10:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-18 Cont ID  
Sent By lmarchan Date 2022-03-18 Time 09:35 Rev Time 0.00
Received By lmarchan Date 2021-12-16 Time 09:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-29 Cont ID  
Sent By lmarchan Date 2021-10-29 Time 10:37 Rev Time 0.00
Received By lmarchan Date 2021-10-22 Time 10:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2021-12-17 Cont ID  
Sent By medwards Date 2021-12-17 Time 10:01 Rev Time 0.00
Received By medwards Date 2021-12-17 Time 10:01 Sent To  
Notes
2021-12-17 10:01:54PLEASE ADDRESS THE 1ST CYCLE REVIEW COMMENTS BELOW:
  
 2) AS THIS IS AN APARTMENT BUILDING PLEASE SHOW THE
 REQUIRED FIRE SEPARATION BETWEEN TENANTS. HOW IS THE
 DUCT WORK FOR THE APARTMENTS ON THE FIRST FLOOR RUN TO
 PREVENT THE NEED FOR RADIATION DAMPERS IN THE
 CEILING/FLOOR ASSEMBLY? FBC M 607
  
 3) PLEASE SHOW THE DUCTWORK FOR THE BATH EXHAUST FANS
 AND THE TERMINATION LOCATIONS. FBC M 501; FBCM 607
  
 4) PLEASE PROVIDE THE DRYER DUCT AND THE TERMINATION
 LOCATIONS. HOW IS THIS DRYER DUCT PENETRATING THE FLOOR
 OF THE UNIT ABOVE AND HOW ARE YOU PROTECTING THIS
 PENETRATION? FBC M 504; FBC M 607
  
 5) IS THERE GOING TO BE A HOOD OVER THE RANGES? IF SO,
 ARE THEY DUCTED TO THE OUTDOORS? FBC 107.2.1
  
 6) PLEASE SHOW THE CONDENSATE PIPING FOR EACH
 MECHANICAL UNIT AND THE TERMINATION LOCATION. FBC M 307
  
 7) THE TITLE BLOCK FOR THIS PROJECT IS CALLING THIS A
 ?PROPOSED RESIDENCE? PLEASE CLARIFY AS THIS IS AN
 APARTMENT BUILDING. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-10-25 Cont ID  
Sent By medwards Date 2021-10-25 Time 11:20 Rev Time 0.00
Received By medwards Date 2021-10-25 Time 11:20 Sent To  
Notes
2021-10-25 11:20:251ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21101008
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS IS AN APARTMENT BUILDING, PLEASE PROVIDE THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS BASED ON
 MANUAL N. FBC EC C403.2.1
  
 2) AS THIS IS AN APARTMENT BUILDING PLEASE SHOW THE
 REQUIRED FIRE SEPARATION BETWEEN TENANTS. HOW IS THE
 DUCT WORK FOR THE APARTMENTS ON THE FIRST FLOOR RUN TO
 PREVENT THE NEED FOR RADIATION DAMPERS IN THE
 CEILING/FLOOR ASSEMBLY? FBC M 607
  
 3) PLEASE SHOW THE DUCTWORK FOR THE BATH EXHAUST FANS
 AND THE TERMINATION LOCATIONS. FBC M 501; FBCM 607
  
 4) PLEASE PROVIDE THE DRYER DUCT AND THE TERMINATION
 LOCATIONS. HOW IS THIS DRYER DUCT PENETRATING THE FLOOR
 OF THE UNIT ABOVE AND HOW ARE YOU PROTECTING THIS
 PENETRATION? FBC M 504; FBC M 607
  
 5) IS THERE GOING TO BE A HOOD OVER THE RANGES? IF SO,
 ARE THEY DUCTED TO THE OUTDOORS? FBC 107.2.1
  
 6) PLEASE SHOW THE CONDENSATE PIPING FOR EACH
 MECHANICAL UNIT AND THE TERMINATION LOCATION. FBC M 307
  
 7) THE TITLE BLOCK FOR THIS PROJECT IS CALLING THIS A
 ?PROPOSED RESIDENCE? PLEASE CLARIFY AS THIS IS AN
 APARTMENT BUILDING. FBC 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-10-22 Cont ID  
Sent By mpeterso Date 2021-10-22 Time 11:01 Rev Time 0.00
Received By mpeterso Date 2021-10-22 Time 11:01 Sent To  
Notes
2021-10-22 11:05:06FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS. A COPY OF A SIGNED
 PLAN IS NOT CONSIDERED AN ORIGINAL.
  
 IT APPEARS THAT PLAN LABELED ?M1 AND M2? AERE COPIES OF
 A DIGITALLY SEALED AND SIGNED PLAN. PLEASE CORRECT
 THESE ISSUES BY PROPERLY SIGNING AND SEALING THEM AS
 DESCRIBED BELOW.
 EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF
 APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX,
 OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER
 ORIGINAL WITH A WET SIGNATURE TO THE BUILDING DIVISION.
 SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO
 BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED
 DOCUMENTS ARE PREFERRED.
  
 PLEASE EMAIL [email protected] AND CC TO
 [email protected]
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop Z ZONING
Rev No 1 Status N Date 2021-10-28 Cont ID  
Sent By amhamilt Date 2021-10-28 Time 10:56 Rev Time 0.00
Received By amhamilt Date 2021-10-28 Time 10:56 Sent To  
Notes
2021-10-28 11:01:06THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
  
 PLEASE PROVIDE SITE SURVEY WITH SETBACKS OF AC
 CONDENSING UNITS FROM PROPERTY LINE.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 561.822.1428
 [email protected]
  