2021-10-25 11:20:25 | 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-21101008 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THIS IS AN APARTMENT BUILDING, PLEASE PROVIDE THE |
| MECHANICAL EQUIPMENT SIZING CALCULATIONS BASED ON |
| MANUAL N. FBC EC C403.2.1 |
| |
| 2) AS THIS IS AN APARTMENT BUILDING PLEASE SHOW THE |
| REQUIRED FIRE SEPARATION BETWEEN TENANTS. HOW IS THE |
| DUCT WORK FOR THE APARTMENTS ON THE FIRST FLOOR RUN TO |
| PREVENT THE NEED FOR RADIATION DAMPERS IN THE |
| CEILING/FLOOR ASSEMBLY? FBC M 607 |
| |
| 3) PLEASE SHOW THE DUCTWORK FOR THE BATH EXHAUST FANS |
| AND THE TERMINATION LOCATIONS. FBC M 501; FBCM 607 |
| |
| 4) PLEASE PROVIDE THE DRYER DUCT AND THE TERMINATION |
| LOCATIONS. HOW IS THIS DRYER DUCT PENETRATING THE FLOOR |
| OF THE UNIT ABOVE AND HOW ARE YOU PROTECTING THIS |
| PENETRATION? FBC M 504; FBC M 607 |
| |
| 5) IS THERE GOING TO BE A HOOD OVER THE RANGES? IF SO, |
| ARE THEY DUCTED TO THE OUTDOORS? FBC 107.2.1 |
| |
| 6) PLEASE SHOW THE CONDENSATE PIPING FOR EACH |
| MECHANICAL UNIT AND THE TERMINATION LOCATION. FBC M 307 |
| |
| 7) THE TITLE BLOCK FOR THIS PROJECT IS CALLING THIS A |
| ?PROPOSED RESIDENCE? PLEASE CLARIFY AS THIS IS AN |
| APARTMENT BUILDING. FBC 107.2.1 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |