Plan Review Details - Permit 21100054
Plan Review Stops For Permit 21100054
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-10-05 Cont ID  
Sent By cpuell Date 2021-10-05 Time 16:49 Rev Time 0.00
Received By cpuell Date 2021-10-05 Time 16:49 Sent To  
Notes
2021-10-05 16:49:29ADDRESS PREVIOUSLY AGREED UPON

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 2021-11-10 Cont ID  
Sent By scwelter Date 2021-11-10 Time 15:00 Rev Time 0.00
Received By scwelter Date 2021-11-10 Time 15:02 Sent To  
Notes
2021-11-10 15:02:15NOT REQUIRED FOR THIS PERMIT, HOWEVER DEVELOPMENT
 SUBJECT TO PUBLIC ART REQUIREMENT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-06-06 Cont ID  
Sent By rmcphers Date 2022-06-06 Time 10:23 Rev Time 0.00
Received By rmcphers Date 2022-06-06 Time 10:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-03-22 Cont ID  
Sent By rmcphers Date 2022-03-22 Time 14:42 Rev Time 0.00
Received By rmcphers Date 2022-03-22 Time 14:16 Sent To  
Notes
2022-03-22 14:28:34NEW GATEHOUSE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE CANOPY ATTACHMENT DETAILS FBC WPB
 107.2.1
  
 2) PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE
 PROVIDED PRODUCT APPROVAL THAT MEETS OR EXCEEDS THE
 REQUIRED WIND PRESSURES SHOWN ON DRAWING S100.
  
 3) ACCESSIBLE RESTROOM - RESTROOM ENTRY DOOR CANNOT
 SWING INTO THE FIXTURE CLEAR FLOOR SPACE - UNLESS YOU
 SHOW THE CLEAR FLOOR SPACE PER THE EXCEPTION - FBC A
 603.2.3 DOOR SWING.
 DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR
 CLEARANCE REQUIRED FOR ANY FIXTURE. EXCEPTIONS: 2.WHERE
 THE TOILET ROOM OR BATHING ROOM IS FOR INDIVIDUAL USE
 AND A CLEAR FLOOR SPACE COMPLYING WITH 305.3 IS
 PROVIDED WITHIN THE ROOM BEYOND THE ARC OF THE DOOR
 SWING, DOORS SHALL BE PERMITTED TO SWING INTO THE CLEAR
 FLOOR SPACE OR CLEARANCE REQUIRED FOR ANY FIXTURE.
  
 4) ACCESSIBLE RESTROOM - PLEASE SHOW THE DOOR
 MANEUVERING CLEARANCE (18" BESIDE THE LATCH SIDE) TO
 EXIT THE RESTROOM FBC 404.2.3
  
 5) CANOPY SHOP DRAWINGS MAY BE DEFERRED SUBMITTALS BY
 LISTING ITEMS TO BE DEFERRED ON THE CONSTRUCTION
 DOCUMENTS - 107.3.4.1 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-11-18 Cont ID  
Sent By rmcphers Date 2021-11-18 Time 08:54 Rev Time 0.00
Received By rmcphers Date 2021-11-17 Time 16:50 Sent To  
Notes
2021-11-18 08:54:27NEW GATEHOUSE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE CANOPY ATTACHMENT DETAILS FBC WPB
 107.2.1
  
 2) SIDING IS SUBJECT TO WIND LOADS - PLEASE SHOW ALL
 ATTACHMENTS FOR THE FIBER CEMENT SIDING OR PROVIDE A
 PRODUCT APPROVAL FBC 1609.1
  
 3) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS AND
 ROOFING SYSTEMS - ALL PRODUCT APPROVALS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD
 FBC WPB 107.3.4
  
 4) DRAWING S101 SHOWS TRUSS STRAPPING AS "DETAIL 20" -
 PLEASE CLARIFY.
  
 5) IF THE RESTROOM IS TO BE ACCESSIBLE - PLEASE SHOW
 ALL COMPONENTS ON THE FLOOR PLAN - GRAB BARS, FIXTURE
 CLEAR FLOOR SPACES, A CLEAR DOOR OPENING OF 32" (2/8
 DOOR DOES NOT PROVIDE A CLEAR 32" CLEAR OPENING) ETC.
 PER FBC ACCESSIBILITY
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-04-07 Cont ID  
Sent By mpeterso Date 2022-04-07 Time 08:48 Rev Time 0.00
Received By mpeterso Date 2022-04-07 Time 08:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-11-18 Cont ID  
Sent By jleahy Date 2021-11-18 Time 15:13 Rev Time 0.00
Received By jleahy Date 2021-11-18 Time 15:13 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2022-09-21 Cont ID  
Sent By rrossano Date 2022-09-21 Time   Rev Time 0.00
Received By rrossano Date 2022-09-21 Time   Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2022-05-23 Cont ID  
Sent By rrossano Date 2022-05-23 Time   Rev Time 0.00
Received By rrossano Date 2022-05-23 Time   Sent To  
Notes
2022-05-23 12:07:09UNDER FORMAL ENGINEERING SUBMITTAL REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2022-03-14 Cont ID  
Sent By rrossano Date 2022-03-14 Time   Rev Time 0.00
Received By rrossano Date 2022-03-14 Time   Sent To  
Notes
2022-03-14 12:01:08UNDER REVIEW AS FORMAL ENGINEERING SUBMITTAL E21090038.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2021-10-15 Cont ID  
Sent By rrossano Date 2021-10-15 Time   Rev Time  
Received By rrossano Date 2021-10-15 Time   Sent To  
Notes
2021-10-15 09:12:07UNDER REVIEW AS FORMAL ENGINEERING SUBMITTAL E21090038.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-03-08 Cont ID  
Sent By pleduc Date 2022-03-08 Time   Rev Time 0.00
Received By pleduc Date 2022-03-08 Time 13:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-10-08 Cont ID  
Sent By pleduc Date 2021-10-08 Time   Rev Time 0.00
Received By pleduc Date 2021-10-08 Time 13:13 Sent To  
Notes
2021-10-08 13:28:24THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF A 12' WIDE EXIT ROADWAY AT
 THE GATE HOUSE.
  
 THIS 12' WIDTH IS TOO NARROW/SMALL FOR A FIRE APPARATUS
 TO USE AND COULD CAUSE DAMAGE TO THE APPARATUS AND/OR
 PROPERTY.
  
 THE MINIMUM WIDTH FOR A FIRE LANE IS 20'
  
 PLEASE REVIEW AND CORRECT OR PROVIDE FOR ALTERNATIVES
 FOR EXITING FD APPARATUS.
  
  
 2) PROVIDE FOR THE LOCATION OF A FIRE EXTINGUISHERS AT
 THE GATE HOUSE.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-06-23 Cont ID  
Sent By lmarchan Date 2022-06-23 Time 08:25 Rev Time 0.00
Received By lmarchan Date 2022-05-11 Time 09:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-04-07 Cont ID  
Sent By mpeterso Date 2022-04-07 Time 08:48 Rev Time 0.00
Received By mpeterso Date 2022-03-07 Time 08:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-18 Cont ID  
Sent By aoliver Date 2022-01-18 Time 12:48 Rev Time 0.00
Received By aoliver Date 2021-10-08 Time 05:56 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-09-27 Cont ID  
Sent By lmarchan Date 2022-09-27 Time 16:47 Rev Time 0.00
Received By lmarchan Date 2022-06-08 Time 09:34 Sent To  
Notes
2022-08-19 10:21:58RECEIPT MU-2022-026593 - $2009.24 PAID
2022-06-08 09:35:216/8/22 EMAILED IMPACT FOR REVIEW PER SH'SS EMAIL -AO

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-11-18 Cont ID  
Sent By rmcphers Date 2021-11-18 Time 08:55 Rev Time 0.00
Received By rmcphers Date 2021-11-18 Time 08:55 Sent To  
Notes
2021-11-18 08:55:50PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-03-28 Cont ID  
Sent By medwards Date 2022-03-28 Time 06:12 Rev Time 0.00
Received By medwards Date 2022-03-28 Time 06:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-11-02 Cont ID  
Sent By medwards Date 2021-11-01 Time 15:25 Rev Time 0.00
Received By medwards Date 2021-11-01 Time 15:25 Sent To  
Notes
2021-11-02 06:16:471) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC 403.2.1
  
 2) PLEASE SHOW THAT THE CONDENSATE DRAIN IS TERMINATED
 TO THE OUTDOORS AND NOT INTO THE BATHROOM LAVITORY. WPB
 CODE OF ORDINANCES CHAPTER 90 SEC. 90- 126 NUMBER 5.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-05-21 Cont ID  
Sent By rwbrown Date 2022-05-21 Time 11:40 Rev Time 0.00
Received By rwbrown Date 2022-05-21 Time 11:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-03-22 Cont ID  
Sent By lcrespo Date 2022-03-09 Time 08:19 Rev Time 0.00
Received By lcrespo Date 2022-03-08 Time 15:55 Sent To  
Notes
2022-03-09 08:21:0803/09/22 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1) DONE.
  
 2) DONE.
  
 3) SHOW ON THE PLAN ALL DIMENSIONS FOR THE RESTROOM AND
 ALL CLEAR FLOOR SPACE FOR THE PLUMBING FIXTURES PER FBC
 ACC SEC. 604.8.1.6.
  
 THE CLEAR FLOOR SPACE FOR THE TURNING RADIUS HAS THE
 DOOR SWINGING INTO IT. PLEASE SHOW THAT A 30? X 40?
 WILL NOT INTERFERE WITH THE DOOR'S SWING OR HAVE THE
 DOOR SWING OUT PER THE 2020 FBC ACC. SEC. 603.2.3DOOR
 SWING.
  
 4) THE BACKFLOWS FOR THE IRRIGATION AND DOMESTIC WATER
 SYSTEMS WILL REQUIRE A SEPARATE PERMIT. THE
 MANUFACTURER'S SPECIFICATIONS AND A SEPARATE PLUMBING
 PERMIT SHALL BE SUBMITTED BEFORE INSTALLING THESE
 DEVICES. THE DEVICES MUST BE INSTALLED BY A LICENSED
 PLUMBING CONTRACTOR.F.S.489.103.
  
 SHEET C 007 IS NOT AVAILABLE ON THE SET OF PLANS
 SUBMITTED. WOULD YOU PLEASE PROVIDE PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 5) DONE.
  
 6) WHERE IS THE LOCATION OF THE WATER SOURCE? A
 BACKFLOW PREVENTION DEVICE WILL BE REQUIRED WHEN
 HOOKING TO THE WATER SERVICE. 602.2 POTABLE WATER
 REQUIRED. 608.13 BACKFLOW PROTECTION. MEANS OF
 PROTECTION AGAINST BACKFLOW SHALL BE PROVIDED IN
 ACCORDANCE WITH SECTIONS 608.13.1 THROUGH 608.13.10.
  
 THE SHEET IN RESPONSE IS NOT AVAILABLE ON THE SET OF
 PLANS SUBMITTED. WOULD YOU PLEASE PROVIDE PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 7) DONE.
  
 8) DONE.
  
 9) DONE.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-11-04 Cont ID  
Sent By abelisle Date 2021-11-04 Time 07:16 Rev Time 0.00
Received By abelisle Date 2021-11-04 Time 06:07 Sent To  
Notes
2021-11-04 07:16:221ST REVIEW FBC-2020 PLUMBING
 PERMIT-21100054
 11/4/2021
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHOW THE LOCATION OF THE DRINKING FOUNTAINS ON THE
 ARCHITECTURAL FLOOR PLAN AND THE PLUMBING FLOOR PLAN.
 WPB AMEND. TO FBC SEC. 107.2.1.
 2) A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER
 FBCACCESS. SEC. 211.2 & FBC-PLUMBING SEC. 410.3.
 3) SHOW ON THE PLAN ALL DIMENSIONS FOR THE RESTROOM AND
 ALL CLEAR FLOOR SPACE FOR THE PLUMBING FIXTURES PER FBC
 ACC SEC. 604.8.1.6
 4) THE BACKFLOWS FOR THE IRRIGATION SYSTEM AND THE
 DOMESTIC WATER SYSTEM WILL REQUIRE A SEPARATE PERMIT.
 MANUFACTURER'S SPECIFICATIONS AND A SEPARATE PLUMBING
 PERMIT SHALL BE SUBMITTED PRIOR TO THE INSTALLATION OF
 THESE DEVICES. THE DEVICES MUST BE INSTALLED BY A
 LICENSED PLUMBING CONTRACTOR.F.S.489.103.
 5) ALL BACKFLOW DEVICES MUST BE LEAD-FREE. LEAD-FREE
 (LF) SHALL BE INCLUDED IN THE SERIAL NUMBER OR STAMPED
 ON THE BODY OF THE DEVICE. ANY DEVICE THAT HAS BEEN
 ALTERED AFTER BEING ASSEMBLED BY THE MANUFACTURER WILL
 NOT BE APPROVED.
 6) WHERE IS THE LOCATION OF THE WATER SOURCE? WHEN
 HOOKING TO THE WATER SERVICE A BACKFLOW PREVENTION
 DEVICE WILL BE REQUIRED. 602.2 POTABLE WATER REQUIRED.
 608.13 BACKFLOW PROTECTION. MEANS OF PROTECTION AGAINST
 BACKFLOW SHALL BE PROVIDED IN ACCORDANCE WITH SECTIONS
 608.13.1 THROUGH 608.13.10.
 7) THE CURRENT CODE CYCLE IS FLORIDA BUILDING CODE 2020
 7TH EDITION. PLEASE REMOVE AND UPDATE THE PLANS TO
 REFLECT THE CURRENT CODE CYCLE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 8) SEPERATE PERMIT AND PLANS ARE REQUIRED FOR
 IRRIGATION WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 9) A SERVICE SINK IS REQUIRED, PLEASE INDICATE WHERE
 ONE WILL BE LOCATED ON THE PLANS WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2022-06-06 Cont ID  
Sent By rmcphers Date 2022-06-06 Time 10:24 Rev Time 0.00
Received By rmcphers Date 2022-06-06 Time 10:24 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2022-03-22 Cont ID  
Sent By rmcphers Date 2022-03-22 Time 14:41 Rev Time 0.00
Received By rmcphers Date 2022-03-22 Time 14:41 Sent To  
Notes
2022-03-22 14:42:11SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-11-18 Cont ID  
Sent By rmcphers Date 2021-11-18 Time 08:55 Rev Time 0.00
Received By rmcphers Date 2021-11-18 Time 08:55 Sent To  
Notes
2021-11-18 08:56:54SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-06-06 Cont ID  
Sent By rmcphers Date 2022-06-06 Time 10:27 Rev Time 0.00
Received By rmcphers Date 2022-06-06 Time 10:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-03-22 Cont ID  
Sent By rmcphers Date 2022-03-22 Time 14:52 Rev Time 0.00
Received By rmcphers Date 2022-03-22 Time 14:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-11-18 Cont ID  
Sent By rmcphers Date 2021-11-18 Time 09:10 Rev Time 0.00
Received By rmcphers Date 2021-11-18 Time 09:10 Sent To  
Notes
2021-11-18 09:14:02SIGNATURE REVIEW
  
 DRAWINGS M0-00, M0-01, M0-02, M0-03, M1-01 DO NOT SHOW
 AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2022-06-22 Cont ID  
Sent By jroach Date 2022-06-22 Time 12:55 Rev Time 0.00
Received By jroach Date 2022-06-21 Time 14:23 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2022-03-18 Cont ID  
Sent By jroach Date 2022-03-18 Time 12:22 Rev Time 0.00
Received By jroach Date 2022-03-18 Time 12:22 Sent To  
Notes
2022-03-18 12:25:51ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 03.18.2022
 PERMIT NO.: 21100054
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. [ PARTIALLY SATISFIED ] - PLEASE CLARIFY THE
 AUTOTURN THAT IS SHOWN ON THE ELECTRICAL SITE PLAN ? IT
 IS SHOWING THE VEHICLE TURNING THROUGH THE PROPOSED
 GUARD HOUSE. THE AUTOTURN SHOULD CORRECTLY SHOW THE
 ABILITY FOR VEHICLES TO TURN AROUND BEFORE THE GATE IF
 ENTRY INTO THE DEVELOPMENT IS DENIED.
  
 1.1 [ NEW COMMENT ] - THE NEW AUTOTURN ANALYSIS SHOWS
 VEHICLES HAVING TO MAKE A 3-POINT TURN TO TURN AROUND,
 AS WELL AS DRIVING OVER THE GRASS AREA.
  
 2. [ SATISFIED ] - IS THE LIGHTING ALONG THE NORTH SIDE
 OF THE ROADWAY PROPOSED/NEW? LIGHTING SHOULD BE
 SHIELDED AWAY FROM ADJACENT RESIDENTIAL PROPERTIES,
 PREFERABLY NOT EXCEEDING 0.5 FOOTCANDLES WHEN MEASURED
 AT THE RESIDENTIAL PROPERTY LINE.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-01-18 Cont ID  
Sent By jroach Date 2022-01-18 Time 12:01 Rev Time 0.00
Received By jroach Date 2022-01-18 Time 12:01 Sent To  
Notes
2022-01-18 12:04:46ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 01.18.2022
 PERMIT NO.: 21100054
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE CLARIFY THE AUTOTURN THAT IS SHOWN ON THE
 ELECTRICAL SITE PLAN ? IT IS SHOWING THE VEHICLE
 TURNING THROUGH THE PROPOSED GUARD HOUSE. THE AUTOTURN
 SHOULD CORRECTLY SHOW THE ABILITY FOR VEHICLES TO TURN
 AROUND BEFORE THE GATE IF ENTRY INTO THE DEVELOPMENT IS
 DENIED.
  
 2. IS THE LIGHTING ALONG THE NORTH SIDE OF THE ROADWAY
 PROPOSED/NEW? LIGHTING SHOULD BE SHIELDED AWAY FROM
 ADJACENT RESIDENTIAL PROPERTIES, PREFERABLY NOT
 EXCEEDING 0.5 FOOTCANDLES WHEN MEASURED AT THE
 RESIDENTIAL PROPERTY LINE.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved