Plan Review Stops For Permit 21100036 |
Review Stop |
AD |
ADDRESSING |
Rev No |
4 |
Status |
P |
Date |
2021-12-10 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2021-12-10 |
Time |
15:57 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2021-12-10 |
Time |
15:57 |
Sent To |
|
|
Notes |
2021-12-10 15:58:04 | APPLICATION AND PLANS UPDATED TO REFLECT ADDRESS FOR | | THE NORTH BUILDING OF 2709 SPRUCE AVE |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
3 |
Status |
F |
Date |
2021-11-15 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2021-11-15 |
Time |
12:38 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2021-11-15 |
Time |
12:38 |
Sent To |
|
|
Notes |
2021-11-15 12:39:03 | PLANS INDICATE THAT THE WORK IS BEING DONE ON 2709 | | SPRUCE AVE, PLEASE UPDATE THE PERMIT DOCUMENTATION TO | | REFLECT THE CORRECT ADDRESS. 501 26TH ST IS THE ADDRESS | | FOR THE PARCEL NOT FOR THE BUILDING WHERE THE WORK IS | | TO BE DONW, FOR QUESTIONS PLEASE EMAIL [email protected] | | OR CALL 561-805-6659 |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
2 |
Status |
F |
Date |
2021-11-04 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2021-11-04 |
Time |
14:28 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2021-11-04 |
Time |
14:28 |
Sent To |
|
|
Notes |
2021-11-04 14:32:17 | PLANS INDICATE THAT THE WORK IS BEING DONE ON 2709 | | SPRUCE AVE, PLEASE UPDATE THE PERMIT DOCUMENTATION TO | | REFLECT THE CORRECT ADDRESS. 501 26TH ST IS THE ADDRESS | | FOR THE PARCEL NOT FOR THE BUILDING WHERE THE WORK IS | | TO BE DONW, FOR QUESTIONS PLEASE EMAIL [email protected] | | OR CALL 561-805-6659 |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
F |
Date |
2021-10-01 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2021-10-01 |
Time |
15:46 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2021-10-01 |
Time |
15:46 |
Sent To |
|
|
Notes |
2021-10-01 15:48:53 | TWO BUILDINGS ON PARCEL, HOWEVER THE BUILDING WITH TWO | | GARAGE DOORS IS 2709 SPRUCE AVE, PLEASE CONFIRMT THAT | | THIS SI THE CORRECT ADDRESS. PLEASE RESPOND TO | | [email protected] OR CALL 561-805-6659 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2021-12-10 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2021-12-10 |
Time |
17:46 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2021-12-10 |
Time |
17:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2021-12-03 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2021-12-03 |
Time |
07:51 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2021-12-03 |
Time |
07:51 |
Sent To |
|
|
Notes |
2021-12-03 07:53:11 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | FROM PREVIOUS LIST: | | | | 1. THE DESIGN PRESSURE REQUIREMENTS FOR A 9'X7' GARAGE | | DOORS PER BCAIB IS +38.7/-48.3, EXPOSURE C. THE DOOR | | PROPOSED HAS A LIMITATION OF +38/-44. EITHER PROPOSE A | | DIFFERENT DOOR OR PROVIDE CALCULATIONS TO SHOW HOW YOU | | HAVE DETERMINED THAT THE DOOR MEETS THE DESIGN PRESSURE | | REQUIREMENTS FOR THIS STRUCTURE, FBC R 301. | | | | HTTPS://DISCOVER.PBCGOV.ORG/PZB/BUILDING/BCAB/BCAB_PROP | | RIETARY_WIND_LOAD_CHART_FOR_ALTERATIONS_LEVEL_I.PDF | | | | ADDITIONAL PRODUCT APPROVALS WAS UPLOADED THAT DO NOT | | MEET DESIGN PRESSURE REQUIREMENTS. THE PRODUCT APPROVAL | | UPLOADED ON 11/3 HAS A DESIGN PRESSURE LIMITATION OF | | +38 / -44 PSF. THAT DOES NOT MEET THE POSITIVE OR | | NEGATIVE DP REQUIREMENTS. | | | | NOTE THAT THERE ARE NOW 3 DIFFERENT PRODUCT APPROVALS | | UPLOADED. COORDINATE WITH [email protected] TO | | HAVE ALL DOCUMENTS REMOVED EXCEPT FOR: | | | | APPLICATION | | NOC | | PRODUCT APPROVAL | | PLAN SHOWING LOCATION OF PROPOSED DOORS | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2021-11-08 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-11-08 |
Time |
11:08 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-11-08 |
Time |
09:36 |
Sent To |
|
|
Notes |
2021-11-08 11:09:57 | BUILDING PLAN REVIEW | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | PLANS EXAMINER II PX3169/SFP306 | | INSPECTOR BN4338 | | BUILDING OFFICIAL BU1635 | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | DEVELOPMENT SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | (561) 805-6726 | | [email protected] | | | | CODES IN EFFECT: | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | NFPA 70 2017 EDITION NEC 2017 | | | | 2ND REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | NOTICE: THE STRUCTURE ON THIS PARCEL THAT HAS 2 OHD'S | | IS LOCATED AT 2709 SPRUCE AVE. | | | | NOTICE: COMMENTS FROM 1ST REVIEW HAVE NOT BEEN | | ADDRESSED. SEE BELOW. | | | | | | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. THE DESIGN PRESSURE REQUIREMENTS FOR A 9'X7' GARAGE | | DOORS PER BCAIB IS +38.7/-48.3, EXPOSURE C. THE DOOR | | PROPOSED HAS A LIMITATION OF +38/-44. EITHER PROPOSE A | | DIFFERENT DOOR OR PROVIDE CALCULATIONS TO SHOW HOW YOU | | HAVE DETERMINED THAT THE DOOR MEETS THE DESIGN PRESSURE | | REQUIREMENTS FOR THIS STRUCTURE, FBC R 301. | | | | HTTPS://DISCOVER.PBCGOV.ORG/PZB/BUILDING/BCAB/BCAB_PROP | | RIETARY_WIND_LOAD_CHART_FOR_ALTERATIONS_LEVEL_I.PDF | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2021-10-24 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2021-10-24 |
Time |
10:31 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2021-10-24 |
Time |
10:31 |
Sent To |
|
|
Notes |
2021-10-24 10:43:46 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. THE DESIGN PRESSURE REQUIREMENTS FOR A 9'X7' GARAGE | | DOORS PER BCAIB IS +38.7/-48.3, EXPOSURE C. THE DOOR | | PROPOSED HAS A LIMITATION OF +38/-44. EITHER PROPOSE A | | DIFFERENT DOOR OR PROVIDE CALCULATIONS TO SHOW HOW YOU | | HAVE DETERMINED THAT THE DOOR MEETS THE DESIGN PRESSURE | | REQUIREMENTS FOR THIS STRUCTURE, FBC R 301. | | | | HTTPS://DISCOVER.PBCGOV.ORG/PZB/BUILDING/BCAB/BCAB_PROP | | RIETARY_WIND_LOAD_CHART_FOR_ALTERATIONS_LEVEL_I.PDF | | | | |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
2 |
Status |
P |
Date |
2021-11-09 |
|
|
Cont ID |
|
Sent By |
amhamilt |
Date |
2021-11-09 |
Time |
14:29 |
Rev Time |
0.00 |
Received By |
amhamilt |
Date |
2021-11-09 |
Time |
14:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
P |
Date |
2021-10-27 |
|
|
Cont ID |
|
Sent By |
amhamilt |
Date |
2021-10-27 |
Time |
15:00 |
Rev Time |
0.00 |
Received By |
amhamilt |
Date |
2021-10-27 |
Time |
15:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2021-12-10 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2021-12-10 |
Time |
17:47 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2021-12-10 |
Time |
17:24 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2021-12-03 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2021-12-03 |
Time |
07:56 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2021-11-15 |
Time |
08:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2021-11-10 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2021-11-10 |
Time |
15:47 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2021-11-03 |
Time |
08:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2021-10-28 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2021-10-28 |
Time |
12:23 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2021-10-22 |
Time |
06:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |