Plan Review Details - Permit 21091451
Plan Review Stops For Permit 21091451
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-06-03 Cont ID  
Sent By mpeterso Date 2022-06-03 Time 14:20 Rev Time 0.00
Received By mpeterso Date 2022-06-03 Time 14:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-04-27 Cont ID  
Sent By jleahy Date 2022-04-27 Time 16:15 Rev Time 0.00
Received By mpeterso Date 2022-04-27 Time 16:15 Sent To  
Notes
2022-04-27 16:21:09ELECTRIC REVIEW FAILED
 1) MECHANICHAL EQUIPMENT SCHEDULE DETAILS CHANGE TO A
 SINGLE A/C. PANEL SCHEDULES STILL REFLECT 2 A/C
 SYSTEMS. PLEASE PROVIDE PANEL SCHEDULES DETAILING
 CORRECT CONDUCTOR SIZES AND OVERCURRENT PROTECTION.FBC
 107.2
 2) PLEASE PROVIDE AN UPDATED LOAD CALCULATION FOR
 ELECTRIC PANEL. NEC 215.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-03 Cont ID  
Sent By mpeterso Date 2022-06-03 Time 14:22 Rev Time 0.00
Received By mpeterso Date 2022-06-01 Time 08:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-28 Cont ID  
Sent By rmcdouga Date 2022-04-28 Time 13:10 Rev Time 0.00
Received By rmcdouga Date 2022-04-06 Time 09:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-04-26 Cont ID  
Sent By medwards Date 2022-04-26 Time 08:51 Rev Time 0.00
Received By medwards Date 2022-04-26 Time 08:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-06-03 Cont ID  
Sent By mpeterso Date 2022-06-03 Time 14:21 Rev Time 0.00
Received By mpeterso Date 2022-06-03 Time 14:21 Sent To  
Notes
2022-06-03 14:22:21ALL PLAN SIGNATURES PASSED

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-04-28 Cont ID  
Sent By rmcdouga Date 2022-04-28 Time 11:34 Rev Time 0.00
Received By rmcdouga Date 2022-04-28 Time 11:34 Sent To  
Notes
2022-04-28 11:36:15ELECTRICAL SHEET E5.1 IS NOT DIGITALLY SIGNED AND
 SEALED BY THE ENGINEER. ELECTRONICALLY SUBMITTED
 DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT OR
 ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE
 OPTION TO SUBMIT THE SIGNED AND SEALED PAPER VERSION OF
 DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE BEEN
 APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 481 & FAC 61G1 OR FS 471 & FAC 61G15
2022-04-26 08:52:00MECHANICAL DIGITAL SIGNATURES APPROVED ME