Plan Review Details - Permit 21091369
Plan Review Stops For Permit 21091369
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-12-22 Cont ID  
Sent By pvalenti Date 2021-12-22 Time 16:37 Rev Time 0.00
Received By pvalenti Date 2021-12-22 Time 14:29 Sent To  
Notes
2021-12-23 05:48:07PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 FBC B 107.3.4, AT TIME OF INSPECTION, PROVIDE PRODUCT
 APPROVAL/MANUFACTURER'S SPECIFICATIONS FOR WALL
 LOUVER/EXHAUST TERMINATION VENT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-11-01 Cont ID  
Sent By jwitmer Date 2021-11-01 Time 14:04 Rev Time 0.00
Received By jwitmer Date 2021-11-01 Time 13:33 Sent To  
Notes
2021-11-01 14:03:57WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT:21091369
 ADD:1804 N. FLAGLER DR. # C
 CONT: ATLANTIC GENERAL CONTRACTING
 TEL: ???
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. NOV. 01/2021
 ACTION: DENIED
  
 1) SHEET 1.0 ELECTRICAL, MECHANICAL WALL DETAILS AND
 FLOOR PLAN. THE FLOOR PLAN INDICATES A NEW PEDICURE
 STATIONS (4) TO CAPTURE FUMES AT THE SOURCE. THE FLOOR
 PLAN NOR DOES THE PERMIT APPLICATION GIVE AN ACCURATE
 DESCRIPTION OF HOW THE WALL IS TO BE BUILT WITH 4
 RISERS WITHIN THE WALL? THE EXTERIOR WALL DOES NOT
 PROVIDE WHERE THE 4 X 14 TRUNK LINE IS TO PENETRATE
 WITHOUT GOING THROUGH THE CONCRETE BEAM NOR COLUMNS ON
 EACH SIDE OF THE WINDOWS WITHIN THE CBC EXTERIOR WALL?
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2A) COMPONENTS & CLADDING. PLEASE SUBMIT THE COMPONENTS
 AND CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(C) WALL LOUVERS
  
 2B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 3) THE PERMIT VALUE OF $500.00 DOLLARS IS EXTREMELY LOW
 FOR THE BUILDING, ELECTRICAL & MECHANICAL WORK THAT IS
 TO BE ACCOMPLISHED UNDER THIS PERMIT.
 109.3 BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-12-22 Cont ID  
Sent By jleahy Date 2021-12-22 Time 15:34 Rev Time 0.00
Received By jleahy Date 2021-12-22 Time 15:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-10-28 Cont ID  
Sent By jleahy Date 2021-10-28 Time 16:22 Rev Time 0.00
Received By jleahy Date 2021-10-28 Time 16:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-12-13 Cont ID  
Sent By pleduc Date 2021-10-05 Time   Rev Time 0.00
Received By cwalker Date 2021-12-13 Time 06:55 Sent To  
Notes
2021-12-13 06:56:47PASSED CRW
2021-10-05 13:25:06THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS LIMITED DETAIL OF THE VENTING SYSTEM,
 INCLUDING PRODUCT TYPE,LENGHTS, JOINT/FASTENING SYSTEM
 AND THE ENDING VENTILATION POINT ON THE EXTERIOR TO
 INCLUDE DIMENSIONS TO ALL NEARBY EQUIPMENT AND
 OPENINGS.
  
 PLEASE PROVIDE DETAILS
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-12-22 Cont ID  
Sent By pvalenti Date 2021-12-22 Time 16:37 Rev Time 0.00
Received By pvalenti Date 2021-12-22 Time 09:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-01 Cont ID  
Sent By jwitmer Date 2021-11-01 Time 14:04 Rev Time 0.00
Received By jwitmer Date 2021-09-30 Time 12:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-12-22 Cont ID  
Sent By medwards Date 2021-12-22 Time 14:50 Rev Time 0.00
Received By medwards Date 2021-12-22 Time 14:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-11-30 Cont ID  
Sent By medwards Date 2021-10-01 Time 06:41 Rev Time 0.00
Received By medwards Date 2021-10-01 Time 06:41 Sent To  
Notes
2021-10-01 06:44:33 
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-12-22 Cont ID  
Sent By ccole Date 2021-12-22 Time 12:43 Rev Time 0.00
Received By ccole Date 2021-12-22 Time 12:43 Sent To  
Notes
2021-12-22 12:45:41REVIEW OF SIGNATURE AND SEAL ON PAPER PLANS APPROVED
 AND PLANS ROUTED TO STORAGE- CLC.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-10-01 Cont ID  
Sent By lcrespo Date 2021-10-01 Time 15:23 Rev Time 0.00
Received By lcrespo Date 2021-10-01 Time 15:23 Sent To  
Notes
2021-10-01 15:23:57PLANS ARE DIGITALLY SIGNED AND SEAL. ONLY WHEN THE
 PLANS ARE SUBMITTED DIGITALLY IS THIS ALLOWED.
 61G15-23.005. PLANS SUBMITTED IN PAPER FORM ARE
 REQUIRED TO BE SEALED AND WET SIGNED BY THE DESIGN
 PROFESSIONAL. 61G15-23.001.