2021-11-19 08:02:53 | PLAN REVIEW BUILDING FLOORING |
| |
| CHRISTOPHER S. THROOP, C.B.O., CFM |
| PLANS EXAMINER II PX3169/SFP306 |
| INSPECTOR BN4338 |
| BUILDING OFFICIAL BU1635 |
| ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| DEVELOPMENT SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| SOW: REPLACE CARPET WITH LAMINATE FLOORING. |
| |
| 1. THE PROPOSED WHISPER MAT CS UNDERLAYMENT IS FOR |
| CERAMIC TILE. PROVIDE AN APPROVED UNDERLAYMENT FOR THE |
| PROPOSED LAMINATE FLOORING. |
| |
| NOTICE: ASTM TEST REPORTS ARE REQUIRED - MANUFACTURER |
| SPEC SHEETS ARE NOT ACCEPTABLE DUE TO DISCREPANCIES |
| BETWEEN SPEC SHEETS/BROCHURES AND TEST REPORTS FOR SOME |
| MANUFACTURERS (NOT NECESSARILY THE MANUFACTURER |
| SELECTED; THIS IS A GENERAL COMMENT). |
| |
| 2. PROVIDE THE TEST REPORTS FOR PROPOSED UNDERLAYMENT |
| BASED ON EXISTING SITE CONDITIONS. |
| |
| 3. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM?S, |
| E-84, E-90 & E-492. |
| FBC 1207.2 AIR-BORNE SOUND. ASTM E ? 90-04 |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E ? 492-09 |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC SPACE OR SERVICE |
| AREA WITHIN THE STRUCTURE SHALL HAVE AN IMPACT |
| INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 (45 |
| IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E |
| 492. |
| |
| FBC 603.1 FLAME SPREAD SEC 803.1.1, PROVIDE TEST DATA |
| IN ACCORDANCE WITH ASTM E 84 OR UL 723 |
| FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| OR UL 723 |
| FBC 804.4.1 TEST REQUIREMENT. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RE-SUBMITTING, PLEASE UPLOAD YOUR DOCUMENTS TO |
| PROJECT DOX. |
| DO NOT E-MAIL DOCUMENTS TO THE PLANS EXAMINER. |
| |
| |