Plan Review Details - Permit 21091230
Plan Review Stops For Permit 21091230 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2021-11-08 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2021-11-08 |
Time |
20:20 |
Rev Time |
|
Received By |
fgiaquin |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2021-10-21 |
|
|
Cont ID |
|
Sent By |
bdolan |
Date |
2021-10-21 |
Time |
|
Rev Time |
0.00 |
Received By |
bdolan |
Date |
2021-10-19 |
Time |
15:06 |
Sent To |
|
|
Notes |
2021-10-21 11:08:03 | THE FOLLOWING COMMENTS WERE SUBMITTED BY LT. BRIAN | | DOLAN, DIVISION OF FIRE PREVENTION, WEST PALM BEACH | | FIRE RESCUE. | | | | 61G15-32.008 DESIGN OF FIRE ALARMS, SIGNALING SYSTEMS | | AND CONTROL SYSTEMS. | | (1) FIRE ALARMS, SIGNALING, AND CONTROL SYSTEMS | | INCLUDE, BUT ARE NOT LIMITED TO, FIRE PROTECTION | | SUPERVISION AND ALARM CIRCUITS, ACTIVATION CONTROLS, | | AND REMOTE SIGNALING. | | (2) THE FIRE PROTECTION SYSTEM DESIGN SPECIFICATIONS | | SHALL BE BASED ON APPLICABLE NFPA STANDARDS, WHEN | | AVAILABLE, OR ALTERNATIVE ENGINEERING SOURCES AND GOOD | | ENGINEERING PRACTICE WHEN REQUIRED, AND SHALL COMPLY | | WITH THE PROVISIONS OF RULE 61G15-33.006, F.A.C. | | SPECIFIC AUTHORITY 471.008, 471.033(2) FS. | | LAW IMPLEMENTED 471.033 FS. | | HISTORY--NEW 5-19-93, FORMERLY 21H-32.008. | | | | REQUIRED SMOKE CONTROL SYSTEM INCLUDING ALL COMPONENTS, | | RERLAYS, AND SEQUENCE OF OPERATION/EXPLAINATION OF | | SYSTEM DESIGN MUST BE SUBMITTED UNDER SEPERATE PERMIT, | | SUBJECT TO INSPECTIONS AND TESTING PRIOR TO | | CERTIFICATION. | | | | | | PER CITY CODES, ALL WORK IS SUBJECT TO FIELD | | INSPECTIONS AND APPROVAL. ALL ASPECTS OF THE SYSTEM | | SHALL BE TESTED TO ENSURE SYSTEMS FUNCTION AS DESIGNED. | | | | LT. BRIAN DOLAN | | DIVISION OF FIRE PREVENTION | | 561-804-4752 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2021-11-08 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2021-11-08 |
Time |
20:21 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2021-10-08 |
Time |
15:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2021-10-26 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-10-26 |
Time |
12:58 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-10-26 |
Time |
12:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2021-11-08 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2021-11-08 |
Time |
20:20 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2021-11-08 |
Time |
20:20 |
Sent To |
|
|
Notes |
|
|
|