Plan Review Details - Permit 21091150
Plan Review Stops For Permit 21091150
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-03-01 Cont ID  
Sent By jwitmer Date 2022-03-01 Time 13:35 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-11-10 Cont ID  
Sent By jwitmer Date 2021-11-10 Time 14:47 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2021-11-10 14:47:50TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-03-01 Cont ID  
Sent By jwitmer Date 2022-03-01 Time 14:03 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-03-01 14:03:36WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT:21091150
 ADD: 651 OKEECHOBEE BLVD. # 1110
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-644-3503
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. MARCH 01/2022
 ACTION: DENIED
  
 1) 2ND REVIEW. SHEET 02 IS SIGNED AND SEALED BY ENG.
 GEORGE FREIJO BUT THE ORIGINAL SHEET 01 IS NOT SIGNED
 AND SEALED BY A DESIGN PROFESSIONAL, ONCE A DESIGN
 PROFESSIONAL IS INVOLVED THEY TAKE OVER THE WHOLE
 PROJECT BOTH SHEETS NEED THE DESIGN PROFESSIONAL
 ELECTRONIC SIGNATURE AND SEAL.
  
 1ST ROUND COMMENTS. THE SUBMITTED FLOOR PLAN SHEET # 01
 WAS NOT DESIGNED BY A DESIGN PROFESSIONAL, EITHER AN
 ARCHITECT OR ENGINEER. SINCE THE FLOOR PLAN WAS NOT
 DESIGNED BY A DESIGN PROFESSIONAL THE CONTRACTOR MUST
 TAKE OWNERSHIP OF THE PLAN. CERTIFICATION BY
 CONTRACTOR. 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT
 CREATED / DREW THE SET OF PLANS WILL NEED TO IDENTIFY
 THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE PRINT
 YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR THE
 TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 2) 2ND REVIEW SHEET 01 NOT REVISED. 2020 FBC-B 2509.2
 BASE FOR TILE. MATERIALS USED AS A BASE FOR WALL TILE
 IN TUB AND SHOWER AREAS AND WALLS AND CEILING PANELS IN
 SHOWER AREAS SHALL BE OF MATERIALS LISTED IN TABLE
 2509.2 AND INSTALLED IN ACCORDANCE WITH MANUFACTURERS
 RECOMMENDATIONS. WATER RESISTANT GYPSUM BACKING BOARD
 SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C840 AND THE MANUFACTURERS
 RECOMMENDATIONS.
  
 3) 2ND REQUEST, SHEET 01 NOT REVISED. 2020 FBC-B
 SHOWERS & TUBS 1210.3. SHOWER COMPARTMENTS AND BATHTUBS
 WITH INSTALLED SHOWER HEADS SHALL BE FINISHED WITH A
 NONABSORBENT SURFACE TO A HEIGHT NOT LESS THAN 72
 INCHES ABOVE THE DRAIN INLET.
  
 4-5) COMPLIED.
  
 6) TUB ENCLOSURE WALLS AND OR SHOWER WALLS. TUB
 ENCLOSURE WALLS AND OR SHOWER WALLS WHICH ARE ALSO
 TENANT SEPARATION WALL WHICH WILL ALSO NEED TO SHOW
 COMPLIANCE WITH SECTION 420.2 SEPARATION WALLS AND FIRE
 PARTITIONS IN ACCORDANCE WITH SECTION 708 OF THE 2020
 FBC-BUILDING CODE.
  
 7) 2ND REQUEST. THE SUBMITTED DOCUMENTS FOR FLOOR
 UNDERLAYMENT DOES NOT MATCH, (2) DOCUMENTS WERE
 SUBMITTED FOR WHISPER MAT CS (FOR TILE AND OR MARBLE)
 AND A 3RD DOCUMENT FOR WHISERPAD FOR LAMINATE FLOORING.
  
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1. DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES, NO DISCREPANCIES.
  
 THE FLOOR PLAN STATES TO REPLACE THE EXISTING FLOOR W/
 NEW TILE OVER THIN SET. FLOOR INSULATION/ UNDERLAYMENT
 (FBC-B 2020) FOR TILE, STONE, MARBLE, VINYL LAMINATE
 FLOORING AND WOOD FLOORING ALL NEED TO HAVE HAD THE
 SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE
 FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS LISTED
 UNDER EACH OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR
 ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 7A) 2ND REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 7B) 2ND REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 7C) 2ND REQUEST. FLAME SPREAD- FBC-B 2020 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-11-10 Cont ID  
Sent By jwitmer Date 2021-11-10 Time 14:48 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2021-11-10 14:48:39WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT:21091150
 ADD: 651 OKEECHOBEE BLVD. # 1110
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-644-3503
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. NOV. 10TH/ 2021
 ACTION: DENIED
  
 1) THE SUBMITTED FLOOR PLAN SHEET # 01 WAS NOT DESIGNED
 BY A DESIGN PROFESSIONAL, EITHER AN ARCHITECT OR
 ENGINEER. SINCE THE FLOOR PLAN WAS NOT DESIGNED BY A
 DESIGN PROFESSIONAL THE CONTRACTOR MUST TAKE OWNERSHIP
 OF THE PLAN. CERTIFICATION BY CONTRACTOR. 107.3.4.3.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 2) 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS A
 BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS
 AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE
 FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND
 THE MANUFACTURE?S RECOMMENDATIONS.
  
 3) 2020 FBC-B SHOWERS & TUBS 1210.3. SHOWER
 COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS
 SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A
 HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
  
 4) POST TENSION SLAB/ NEW HOLES. THE PLAN IS SILENT AS
 IF THE LOCATION OF THE EXISTING TUB DRAIN IS GOING TO
 BE REUSED IN THE SAME LOCATION. IF NOT, THEN THE FLOOR
 SLAB WILL NEED TO BE X-RAYED TO FIND THE POST TENSION
 CHORD LOCATIONS. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 5) THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL
 ASSEMBLIES). IF A NEW FLOOR PENETRATION IS MADE FOR THE
 FUTURE SHOWER DRAIN, THEN YOU NEED TO SHOW COMPLIANCE
 WITH THE 2020 FBC-B SECTION 714.5.1.2.
 THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL
 ASSEMBLIES). THROUGH PENETRATIONS SHALL BE PROTECTED BY
 A THROUGH PENETRATION FIRESTOP SYSTEM INSTALLED IN
 ACCORDANCE WITH ASTM E814 OR UL 1479. THE SYSTEM SHALL
 HAVE AN F RATING / T RATING OF NOT LESS THAN 1 HOUR BUT
 NOT LESS THAN THE REQUIRED RATING OF THE FLOOR
 PENETRATED.
  
 6) TUB ENCLOSURE WALLS AND OR SHOWER WALLS. TUB
 ENCLOSURE WALLS AND OR SHOWER WALLS WHICH ARE ALSO
 TENANT SEPARATION WALL WHICH WILL ALSO NEED TO SHOW
 COMPLIANCE WITH SECTION 420.2 SEPARATION WALLS AND FIRE
 PARTITIONS IN ACCORDANCE WITH SECTION 708 OF THE 2020
 FBC-BUILDING CODE.
  
 7) THE FLOOR PLAN STATES TO REPLACE THE EXISTING FLOOR
 W/ NEW TILE OVER THIN SET. FLOOR INSULATION/
 UNDERLAYMENT (FBC-B 2020) FOR TILE, STONE, MARBLE,
 VINYL LAMINATE FLOORING AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 7A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 7B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 7C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-11-15 Cont ID  
Sent By jleahy Date 2021-11-15 Time 15:21 Rev Time 0.00
Received By jleahy Date 2021-11-15 Time 15:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-02-23 Cont ID  
Sent By pleduc Date 2022-02-23 Time   Rev Time 0.00
Received By pleduc Date 2022-02-23 Time 12:46 Sent To  
Notes
2022-02-23 12:51:59FIRE PROVISO:
  
 ENSURE FIRE RATED TENANT/CORRIDOR SEPARATION WALLS
 ARE MAINTAINED & REPAIRED IF DAMAGED.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-10-22 Cont ID  
Sent By pleduc Date 2021-10-22 Time   Rev Time 0.00
Received By pleduc Date 2021-10-22 Time 15:14 Sent To  
Notes
2021-10-22 15:21:58THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO FLOOR PLAN SUBMITTED THAT INDICATES THE
 LOCATION OF THE BATHROOM NOR IF IT IS LOCATED ALONG A
 TENANT SEPARATION/CORRIDOR WALL REQUIRING
 MAINTENANCE/REPAIR OF THE FIRE RATED WALL SHOULD THE
 DEMO DAMAGE THAT WALL.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE A FLOOR PLAN
 INDICATING THE LOCATION OF THE BATHROOM(S) AND A NOTE
 OF ACKNOWLEDGEMENT TO MAINTAIN THE FIRE RATING OF THE
 BATHROOM WALL IF APPLICABLE.
  
  
 2) PLEASE PROVIDE THE TILE TYPE I.E. CERAMIC, MARBLE,
 TERRACOTTA, STONE OR TILE PRODUCT TYPE I.E. VINYL OR
 VINYL PLANKS, CORK, WOOD.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-01 Cont ID  
Sent By jwitmer Date 2022-03-01 Time 14:05 Rev Time 0.00
Received By jwitmer Date 2022-02-22 Time 06:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-15 Cont ID  
Sent By jleahy Date 2021-11-15 Time 15:23 Rev Time 0.00
Received By jleahy Date 2021-10-18 Time 17:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-02-23 Cont ID  
Sent By ccole Date 2022-02-23 Time 15:43 Rev Time 0.00
Received By ccole Date 2022-02-23 Time 15:43 Sent To  
Notes
2022-02-23 15:46:082ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21091150
 2/23/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. NO RESPONSES TO THE 1ST
 REVIEW COMMENTS LISTED BELOWWERE PROVIDED. THE COMMENTS
 ARE LISTED BELOW. PLEASE NOTE THE ORIGINAL FLOOR PLAN
 DRAWING FOR UNIT 1110 UNDER THE BUILDING PERMIT-
 99061677 SHOWS A SHOWER IN BATH-2, HOWEVER YOUR PLAN
 SHOWS A BATHTUB. IF UNABLE TO MEET COMPLIANCE WITH THE
 COMMENTS PLEASE SEE THE NOTE AT THE BOTTOM OF THE
 REVIEW.
  
 1) SHEET 01: FAIR HOUSING ACCESSIBILITY GUIDELINES:
 BECAUSE THE BUILDING WAS CONSTRUCTED IN ACCORDANCE WITH
 THE ACCESSIBILITY REQUIREMENTS OF THE FAIR HOUSING ACT
 AND THE DESIGN GUIDELINES FOR USABLE BATHROOMS IN
 DWELLING UNITS, THE ALTERATIONS THAT ARE PROPOSED IN
 THE BATHROOM SHALL ALSO BE IN COMPLIANCE WITH THE FAIR
 HOUSING DESIGN ACT MANUAL. THE FAIR HOUSING
 ACCESSIBILITY GUIDELINES ARE ALSO INCLUDED IN THE
 FLORIDA ACCESSIBILITY CODE- 2020 7TH EDITION. REFER TO
 REQUIRMENT 7 USUABLE KITCHENS AND BATHROOMS AND PAGE
 7.33 IN THE FAIR HOUSING ACT DESIGN MANUAL.
  
 THE PLANS SHALL INDICATE WHICH USABLE BATHROOM
 SPECIFICATION IS THE BASIS OF DESIGN- TYPE A OR B.
 PLEASE REFER TO PAGES 7.34- 7.39 OF THE MANUAL FOR
 EXPLANATORY INFORMATION ON SPECIFICATION A & B. PLEASE
 REFER TO THE PAGES LISTED BELOW AND PROVIDE DIMENSIONED
 DETAILS FOR REVIEW:
  
 PAGES- 7.40-7.46 WATER CLOSET CLEAR FLOOR SPACE.
 PAGES- 7.47- 7.52: LAVATORY AND VANITY CLEAR FLOOR AND
 KNEE AND TOE CLEARANCES.
  
 PAGES 7.56- 7.59 SHOWER CLEAR FLOOR. BASED ON PAGE 7.57
 REGARDLESS OF WHICH SPECIFICATION IS THE BASIS OF
 DESIGN, A 30X48 INCH CLEAR FLOOR SPACE PARALLEL TO THE
 SHOWER SHALL BE PROVIDED, AND NO OTHER FIXTURE MAY
 OVERLAP THE CLEAR FLOOR SPACE. BASED ON THE LOCATION OF
 THE WATER CLOSET THE DRAWING IS NOT IN COMPLIANCE.
  
 2) SHEET 01: BASED ON EITHER SPECIFICATION A OR B
 PLEASE REFER TO PAGES 6.12- 6.13 AND PROVIDE AN
 ELEVATION DETAIL SHOWING THE SHOWER CONTROLS LOCATION,
 AND THE GRAB BAR AND SEAT REINFORCEMENT DETAILS. SHOW
 THE LENGTHS, WIDTHS AND HEIGHTS AND THE TYPE OF
 REINFORCEMENT MATERIAL TO BE USED. SEE SECTION 603.1
 FOR ALLOWABLE MATERIALS IN NON-COMBUSTIBLE BUILDINGS.
  
 PLEASE NOTE: AS AN ALTERNATIVE TO MEETING FAIR HOUSING
 COMPLIANCE FOR THE BATH ALTERATIONS, THE OWNER AND
 DESIGNER OF RECORD FOR THE PROPOSED PROJECT MAY PROVIDE
 A SIGNED AND NOTARIZED AFFIDAVIT WHICH WOULD INDICATE
 ACKNOWLEDGEMENT THAT THE PROPOSED DESIGN DOES NOT MEET
 THE REQUIREMENTS OF THE FAIR HOUSING ACCESSIBILITY
 GUIDELINES, BUT WILL ALSO REQUIRE THE OWNER TO AGREE TO
 REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF SALE IF
 REQUESTED BY THE BUYER. IF THIS OPTION IS CHOSEN,
 PLEASE SEND AN EMAIL TO [email protected] AND I WILL SEND A
 COPY OF THE FAIR HOUSING AFFIDAVIT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-11-01 Cont ID  
Sent By ccole Date 2021-11-01 Time 17:25 Rev Time 0.00
Received By ccole Date 2021-11-01 Time 16:39 Sent To  
Notes
2021-11-01 17:25:281ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21091150
 11/1/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 01: FAIR HOUSING ACCESSIBILITY GUIDELINES:
 BECAUSE THE BUILDING WAS CONSTRUCTED IN ACCORDANCE WITH
 THE ACCESSIBILITY REQUIREMENTS OF THE FAIR HOUSING ACT
 AND THE DESIGN GUIDELINES FOR USABLE BATHROOMS IN
 DWELLING UNITS, THE ALTERATIONS THAT ARE PROPOSED IN
 THE BATHROOM SHALL ALSO BE IN COMPLIANCE WITH THE FAIR
 HOUSING DESIGN ACT MANUAL. THE FAIR HOUSING
 ACCESSIBILITY GUIDELINES ARE ALSO INCLUDED IN THE
 FLORIDA ACCESSIBILITY CODE- 2020 7TH EDITION. REFER TO
 REQUIRMENT 7 USUABLE KITCHENS AND BATHROOMS AND PAGE
 7.33 IN THE FAIR HOUSING ACT DESIGN MANUAL.
 THE PLANS SHALL INDICATE WHICH USABLE BATHROOM
 SPECIFICATION IS THE BASIS OF DESIGN- TYPE A OR B.
 PLEASE REFER TO PAGES 7.34- 7.39 OF THE MANUAL FOR
 EXPLANATORY INFORMATION ON SPECIFICATION A & B. PLEASE
 REFER TO THE PAGES LISTED BELOW AND PROVIDE DIMENSIONED
 DETAILS FOR REVIEW:
  
 PAGES- 7.40-7.46 WATER CLOSET CLEAR FLOOR SPACE.
  
 PAGES- 7.47- 7.52: LAVATORY AND VANITY CLEAR FLOOR AND
 KNEE AND TOE CLEARANCES.
  
 PAGES 7.56- 7.59 SHOWER CLEAR FLOOR. BASED ON PAGE 7.57
 REGARDLESS OF WHICH SPECIFICATION IS THE BASIS OF
 DESIGN, A 30X48 INCH CLEAR FLOOR SPACE PARALLEL TO THE
 SHOWER SHALL BE PROVIDED, AND NO OTHER FIXTURE MAY
 OVERLAP THE CLEAR FLOOR SPACE. BASED ON THE LOCATION OF
 THE WATER CLOSET THE DRAWING IS NOT IN COMPLIANCE.
  
 PLEASE NOTE: AS AN ALTERNATIVE TO MEETING THE
 GUIDELINES FOR THE BATH ALTERATIONS, THE OWNER AND
 DESIGNER OF RECORD FOR THE PROPOSED PROJECT MAY PROVIDE
 A SIGNED AND NOTARIZED AFFIDAVIT WHICH WOULD INDICATE
 ACKNOWLEDGEMENT THAT THE PROPOSED DESIGN DOES NOT MEET
 THE REQUIREMENTS OF THE FAIR HOUSING ACCESSIBILITY
 GUIDELINES, BUT WILL ALSO REQUIRE THE OWNER TO AGREE TO
 REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF SALE IF
 REQUESTED BY THE BUYER. IF THIS OPTION IS CHOSEN,
 PLEASE SEND AN EMAIL TO [email protected] AND I WILL SEND A
 COPY OF THE FAIR HOUSING AFFIDAVIT.
  
 2) SHEET 01: BASED ON EITHER SPECIFICATION A OR B
 PLEASE REFER TO PAGES 6.12- 6.13 AND PROVIDE AN
 ELEVATION DETAIL SHOWING THE SHOWER CONTROLS LOCATION,
 AND THE GRAB BAR AND SEAT REINFORCEMENT DETAILS. SHOW
 THE LENGTHS, WIDTHS AND HEIGHTS AND THE TYPE OF
 REINFORCEMENT MATERIAL TO BE USED. SEE SECTION 603.1
 FOR ALLOWABLE MATERIALS IN NON-COMBUSTIBLE BUILDINGS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-03-01 Cont ID  
Sent By jwitmer Date 2022-03-01 Time 14:04 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-03-01 14:04:44) 2ND REVIEW. SHEET 02 IS SIGNED AND SEALED BY ENG.
 GEORGE FREIJO BUT THE ORIGINAL SHEET 01 IS NOT SIGNED
 AND SEALED BY A DESIGN PROFESSIONAL, ONCE A DESIGN
 PROFESSIONAL IS INVOLVED THEY TAKE OVER THE WHOLE
 PROJECT BOTH SHEETS NEED THE DESIGN PROFESSIONAL
 ELECTRONIC SIGNATURE AND SEAL.
  
 1ST ROUND COMMENTS. THE SUBMITTED FLOOR PLAN SHEET # 01
 WAS NOT DESIGNED BY A DESIGN PROFESSIONAL, EITHER AN
 ARCHITECT OR ENGINEER. SINCE THE FLOOR PLAN WAS NOT
 DESIGNED BY A DESIGN PROFESSIONAL THE CONTRACTOR MUST
 TAKE OWNERSHIP OF THE PLAN. CERTIFICATION BY
 CONTRACTOR. 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT
 CREATED / DREW THE SET OF PLANS WILL NEED TO IDENTIFY
 THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE PRINT
 YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR THE
 TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-11-15 Cont ID  
Sent By jleahy Date 2021-11-15 Time 15:22 Rev Time 0.00
Received By jleahy Date 2021-11-15 Time 15:21 Sent To  
Notes
2021-11-15 15:23:45ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLAN NOT SIGNED BY PERSON OF RECORD.